catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
True power monitoring of 1- and 3-phase loads<br />
Functions<br />
WatchDog pro<br />
Power factor and power measurement<br />
G2BI1 400V12A in 1-phase mains G2BI1 400V12A in 3-phase mains Connections<br />
< Power factor and power measurement in 1- or 3-phase mains<br />
< RMS measurement of one phase voltage and current of one phase<br />
< Monitoring of motor / generator / capacitive / inductive loads<br />
< 2 Measurement range 1,2kW and 4,8kW<br />
< Measurement range adjustment via Central Unit<br />
< Reinforced insulation of the measuring circuits<br />
< Measured value transmitting via standard bus<br />
< Width 22,5mm<br />
< Industrial design<br />
N<br />
Type<br />
G2CI1 400V12A<br />
i<br />
k<br />
L1 L2 L3<br />
i<br />
k<br />
L1 L2 L3<br />
Phase voltage = 3 x U 1<br />
G2BI1 400V12A in 3-phase mains with current transformer<br />
L1<br />
L2<br />
L3<br />
Width 22,5mm<br />
i<br />
k<br />
L1 L2 L3<br />
Connections<br />
Dimensions<br />
Art.No. (PQ1) 2500450<br />
Art.No. (PQ10) -<br />
EAN13-Code 9008662005877<br />
Measured variable<br />
Measured values<br />
Measuring input current<br />
Measured range<br />
Voltage range<br />
Controls<br />
Indicators (LEDs)<br />
Businterface<br />
True power • Apparent power • Reactive power • Power factor • Phase voltage • Phase current<br />
AC Sinus (10 to 400Hz)<br />
PF, P, S, Q, U eff<br />
, I eff<br />
6A • 12A<br />
1,2kW • 4,8kW<br />
1-phase loads: to 415VAC<br />
3-phase loads: to 415/240VAC<br />
Address adjustment:<br />
Address range 1 to 99<br />
U • Err • Com<br />
Standardbus (RS485)<br />
Overvoltage cat. III (in accordance with IEC 60664-1)<br />
Rated surge voltage<br />
Supply<br />
6kV<br />
24V DC from local interface<br />
Output -<br />
Width<br />
Certificates<br />
Mechanical<br />
Design<br />
Terminal capacity<br />
Ambient<br />
conditions<br />
Accessories -<br />
22,5mm<br />
CE • GOST<br />
Self-extinguishing plastic housing, IP rating IP20 • Mounted on DIN-rail TS 35 in accordance with EN 60715 • Mounting position: any •<br />
Shockproof terminal connection according to VBG 4 (PZ1 required), IP rating IP20 • Tightening torque: max. 1Nm<br />
1 x 0.5 to 2.5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0.5 to 1.5mm² with/without multicore cable end<br />
• 2 x 2.5mm² flexible without multicore cable end<br />
Ambient temperature: -25 to +55°C (in accordance with IEC 60068-1); -25 to +40°C (in accordance with UL 508) • Storage temperature: -25<br />
to +70°C • Transport temperature: -25 to +70°C • Relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Absolute<br />
humidity: 1g to 25g H 2<br />
O/m 3 (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree: 2 (in accordance with IEC 60664-1) • Vibration<br />
resistance: 10 to 55Hz 0.35mm (in accordance with IEC 60068-2-6) • Shock resistance: 15g 11ms (in accordance with IEC 60068-2-27)<br />
7<br />
Page 176<br />
www.tele-online.com Page 177