5-Implementation<br />
• Send<strong>in</strong>g <strong>time</strong> stamps to SCADA<br />
Step<br />
Action<br />
1 Create the eight tags as I/O variables between PAC and SCADA for each DB.<br />
DB1_xxx is for RTC mode, DB2_xxx is for NTP mode, and DB3_xxx is for<br />
ERT mode.<br />
Time stamps RTC<br />
mode sent to Vijeo<br />
Citect.<br />
Time stamps NTP<br />
mode sent to Vijeo<br />
Citect.<br />
Time stamps ERT<br />
mode sent to Vijeo<br />
Citect.<br />
2 Use the TS_DataBase_To_VJC DFB to send the <strong>time</strong> stamps to SCADA.<br />
3 Use the TimeStamp<strong>in</strong>g_xxx( ) function <strong>in</strong> SCADA to get the <strong>time</strong> stamps from<br />
the PAC.<br />
Note: TimeStamp<strong>in</strong>g_RTC( ) is for RTC mode, TimeStamp<strong>in</strong>g_NTP( ) is for<br />
NTP mode, and TimeStamp<strong>in</strong>g_ERT( ) is for ERT mode.<br />