e. One playpipe for 1-1/2 inch hose with 1/2 inch shutoff nozzle or<br />

combination nozzle.<br />

f. Two adapter fittings, 2-1/2 to 1-1/2 inch.<br />

g. Two spanners for 1-1/2 inch hose.<br />

2.1.2.9 Indicator Posts<br />

UL 789. Provide for gate valves where indicated.<br />

2.1.2.10 Valve Boxes<br />

Provide a valve box for each gate valve on buried piping. Valve boxes shall<br />

be of cast iron of a size suitable for the valve on which it is to be used<br />

and shall be adjustable. Cast-iron boxes shall have a minimum cover and<br />

wall thickness of 3/16 inch. Provide a round head. Cast the word "WATER"<br />

on the lid. The least diameter of the shaft of the box shall be 5 1/4<br />

inches. Cast-iron box shall have a heavy coat of bituminous paint.<br />

2.1.2.<strong>11</strong> Valve Pits<br />

Valve pits shall be constructed at locations indicated or as required above<br />

and in accordance with the details shown.<br />

2.1.2.12 Turbine Type Meters<br />

Turbine type meters shall conform to AWWA C701 Class II. The main casing<br />

shall be bronze with stainless steel external fasteners. Registers shall be<br />

straight-reading type, shall be permanently sealed and shall read in U.S.<br />

gallons. Connections shall be suitable to the type of pipe and conditions<br />

encountered. Register type shall be an encoder type remote register<br />

designed in accordance with AWWA C707. Meters shall comply with the<br />

accuracy and capacity requirements of AWWA C701.<br />

2.1.2.13 Propeller Type Meters<br />

Propeller type meters shall conform to AWWA C704. Registers shall be<br />

straight-reading type, shall be permanently sealed and shall read in U.S.<br />

gallons. Connections shall be suitable to the type of pipe and conditions<br />

encountered. Register type shall be an encoder-type remote register<br />

designed in accordance with AWWA C707. Meters shall comply with the<br />

accuracy and capacity requirements of AWWA C703.<br />

2.1.2.14 Meter Vaults<br />

Large meters shall be installed in reinforced concrete vaults manufactured<br />

in accordance with Section 03 40 <strong>00</strong>.<strong>00</strong> 10 PLANT-PRECAST CONCRETE PRODUCTS<br />

FOR BELOW GRADE CONSTRUCTION. Large meters shall be installed in reinforced<br />

concrete vaults in accordance with the details shown on the drawings.<br />

2.1.2.15 Sleeve-Type Mechanical Couplings<br />

Couplings shall be designed to couple plain-end piping by compression of a<br />

ring gasket at each end of the adjoining pipe sections. The coupling shall<br />

consist of one middle ring flared or beveled at each end to provide a gasket<br />

SECTION <strong>33</strong> <strong>11</strong> <strong>00</strong> Page 18