<strong>Report</strong> <strong>No</strong>.: 1<br />

Sulphate<br />

Method<br />

Number of<br />

results<br />

% of total Median Sat. (%)<br />

Ion Chromatography 6 22.2% 271.40 100%<br />

Turbidimetry 17 63.0% 266.40 65%<br />

other 4 14.8% 266.50 75%<br />

Fluoride<br />

Method<br />

Number of<br />

results<br />

% of total Median Sat. (%)<br />

Ion Chromatography 6 25.0% 0.24 ---<br />

Spectrophotometry 14 58.3% 0.48 ---<br />

other 4 16.7% 0.38 ---<br />

Comments: in case of using ion chromatography method, the analysis should be done by using<br />

a suitable effluent and removal of interferences.<br />

Conductivity<br />

Method<br />

Number of<br />

results<br />

% of total Median Sat. (%)<br />

Conductivity Meter 24 88.9% 1399.50 88%<br />

other 3 11.1% 1408.00 67%<br />

Total Dissolved Solids<br />

Method<br />

Number of<br />

results<br />

% of total Median Sat. (%)<br />

Drying @ 180°C 12 46.2% 945.50 100%<br />

Calculation 4 15.4% 903.50 100%<br />

other 10 38.5% 777.00 90%<br />

7-3- Overall performance<br />

Samples have been collected and prepared according to standard methods for the examination<br />

of water and wastewater.<br />

Assigned values for each parameter have been determined form the participants results in this<br />

program and statistical calculations.<br />

In case of fluoride, due to the variations in the results the evaluation of participants performance<br />

is not possible. Since the analysis of fluoride is a very sensitive procedure and diferrent<br />

parameters such as sample and standards temperature can affect the measurement process so<br />

it is expected to improve the test methods results by carefully take the above mentioned<br />

cautions into consideration.<br />