same time. Lifter-lock bolts shall be forged silicon-bronze Ford Meter Box Co. standard 27/32<br />

inches. The meter pit cover shall be the equal <strong>of</strong> Type C-3 with 11 ½-inch lid as manufactured<br />

by the Ford Meter Box Company.<br />

5.11 Outside Meter Yoke - Meter yokes shall be <strong>of</strong> the riser type with a valve inlet. The body<br />

<strong>of</strong> the yoke shall be cast iron with a brass valve inlet end and a brass ell outlet end. The ends<br />

shall be connected to the yoke with brass lock nuts. The valve shall be <strong>of</strong> the inverted key angle<br />

type. The yoke shall contain a brass expansion connection to allow for connecting or<br />

disconnecting a meter. The inlet and outlet shall be for copper pipe connections. The yoke shall<br />

be the equal <strong>of</strong> Y502 for ¾-inch service and Y504 for 1-inch service manufactured by the Ford<br />

Meter Box Company or approved equal.<br />

6.0 Gate Valves and Resilient Wedge (R/W) Valves<br />

6.1 General – Valves <strong>of</strong> the sizes and types specified or shown on the construction drawings<br />

shall be provided for the proper completion <strong>of</strong> the work included under the project.<br />

Operating nuts, handwheels, gaskets, bolts and nuts, and all necessary appurtenances for a<br />

complete installation <strong>of</strong> the valves and gates shall be furnished with the valves. If valves are not<br />

underground they shall be cleaned and painted after installation.<br />

Complete details <strong>of</strong> all valves to be used on the project shall be submitted to the <strong>City</strong> for<br />

approval prior to shipment. All valves shall open right (clockwise).<br />

6.2 Type <strong>of</strong> Valve - The construction drawings may state which type <strong>of</strong> valve is to be used. If<br />

the type is not stated and only the size is given, either the gate type or resilient wedge type with a<br />

minimum working pressure <strong>of</strong> 250 PSI may be used.<br />

6.3 Valve Boxes - A valve box shall be provided for every operating nut <strong>of</strong> a buried gate valve,<br />

with operating mechanism fully protected with a cast iron case. The valve box shall not transmit<br />

shock or stress to the valve. It shall be centered and plumb over the wrench nut <strong>of</strong> the valve.<br />

The box cover shall be flush with the finished pavement or at such other level as may be directed<br />

by the <strong>City</strong> Engineer. The assembly shall consist <strong>of</strong> three pieces and a cover. The cover shall be<br />

marked “Water” where the pressure main is installed for water service. The valve box shall be<br />

screw-type, cast iron with 5 ¼-inch shaft. A round base that will enclose the valve bonnet shall<br />

be furnished with 6-inch and 8-inch valves. An oval base shall be supplied with valves larger<br />

than 8-inches.<br />

6.4 Gate Valves - Gate valves for buried pipe lines shall be iron body, bronze mounted, doubledisc,<br />

gate valves with non-rising stems having either parallel or inclined seats in accordance with<br />

“Metal-seated Gate Valves for Water Supply Service” AWWA C500 or “Resilient-seated Gate<br />

8 February 2007