10.7 Detention Ponds<br />

A detention pond is a traditional stormwater quantity control device that is designed for peak<br />

discharge control. Detention ponds are designed to completely drain after the design storm<br />

passes. Figure 10-11 illustrates a detention pond.<br />

10.7.1 Applicability<br />

Detention ponds are not effective as water quality treatment devices and can only be used for<br />

water quantity control (i.e., detention).<br />

10.7.2 Design Criteria<br />

Design detention ponds so that discharge rates do not exceed calculated pre-development<br />

peak runoff rates for the storms given in Chapter 5.<br />

Design outlet structures so that detention volume is released within 24 hours.<br />

Provide an emergency spillway sized to discharge the peak runoff from the 100-year storm<br />

assuming the principal spillway is clogged, without overtopping the crest.<br />

Provide a minimum of 1 foot of freeboard above the calculated high water elevation for the<br />

100-year storm.<br />

Embankment heights shall not exceed 20 feet (measured from the downstream toe) and<br />

storage volumes shall not exceed 25 acre-feet and shall not be less than 0.3-acre feet.<br />

Regional facilities may exceed these limits, but they must comply with the applicable<br />

requirements of the Kentucky Division of Water.<br />

Design earthen embankments with side slopes not steeper than 3:1 (horizontal to vertical).<br />

Provide anti-seep collars where the spillway barrel passes through the embankment.<br />

Stabilize earthen embankments immediately with temporary or permanent vegetation in<br />

accordance with requirements of Chapter 11.<br />

Design ponds to be placed outside the receiving stream except when a pond is designed as a<br />

regional detention pond and LFUCG has approved its use as a regional pond.<br />

Reserve adequate access from public or private right-of-way by establishing a maintenance<br />

easement. Design the access to be at least 10 feet wide and not steeper than 5:1 (h:v).<br />

Design the access way to connect to the embankment so that equipment can access the top of<br />

the embankment on a slope not steeper than 5:1 (h:v).<br />

Provide a minimum 25-foot wide buffer strip between the pond and the nearest property line.<br />

Landscape the buffer strip with low-maintenance native grasses, shrubs, and trees. Provide a<br />

STORMWATER MANUAL 10-22 January 1, 2009<br />