Occupancy Detector Interface (441)<br />

The 441 Occupancy Detector Interface allows connection of<br />

a customer specified occupancy sensor to a DIGIDIM-DALI<br />

system. The input accepts a volt free normally closed contact.<br />

The pre-wired encapsulated circuit board is intended for<br />

mounting inside the wiring space of the sensor.<br />

Key Features<br />

• Includes a 12 Volt DC supply (15 mA max) to power the<br />

sensor<br />

• Fits into the wiring space behind the sensor<br />

• Input for normally closed (NC) switch supports alarm<br />

conditions<br />

• Fully programmable using DIGIDIM Toolbox and Designer<br />

software.<br />

Technical Data<br />

DALI consumption: 10 mA + sensor supply < 25 mA max<br />

Sensor supply:<br />

12 V @ 15 mA maximum<br />

(non-isolated)<br />

Overload protection: ±7 V<br />

Short-circuit current: 0.5 mA maximum<br />

Debounce period: 50 ms<br />

Ambient temperature: 0…40 °C<br />

Relative humidity: 90 % max, non-condensing<br />

IP rating: 40<br />

Dimensions<br />

20 mm<br />

30 mm<br />

170 mm<br />

50 mm<br />

mm<br />

10<br />

Encapsulated printed circuit board, weight 12 g<br />

Product Order Code: 441<br />

Connections<br />

0V<br />

1<br />

2<br />

+12V<br />

0V<br />

DA+<br />

DA-<br />

Input e.g. Alarm (normally closed)<br />

Unused<br />

Sensor supply<br />

DALI<br />

DA+<br />

DA-<br />

DALI<br />

DA+<br />

DA-<br />

60<br />