Address NO. Description Default Maximum Minimum Unit<br />

9628 COM-40 Input Num 2 8 0<br />

9629 COM-41 Input 1 0005 FFFF 0000 HEX<br />

962A COM-42 Input 2 0006 FFFF 0000 HEX<br />

962B COM-43 Input 3 0000 FFFF 0000 HEX<br />

962C COM-44 Input 4 0000 FFFF 0000 HEX<br />

962D COM-45 Input 5 0000 FFFF 0000 HEX<br />

962F COM-46 Input 6 0000 FFFF 0000 HEX<br />

9630 COM-47 Input 7 0000 FFFF 0000 HEX<br />

9631 COM-48 Input 8 0000 FFFF 0000 HEX<br />

9643 COM-67 Comm Update 0 1 0<br />

COM-01 [Opt B/D]<br />

• Indicates <strong>Option</strong> <strong>board</strong>s installed. This value is automatically set when the <strong>board</strong>s are installed.<br />

COM-02 [ Opt Mode ]<br />

• Determines whether Run/Stop/Reference Frequency is set via Communication.<br />

Value Display Description<br />

0 None Disabled<br />

1 Command Run/Stop setting via Communication<br />

2 Freq Frequency setting via Communication<br />

3 Cmd + Freq Run/Stop/Reference Frequency via Communication<br />

COM-03 [ Opt Version ]<br />

• Displays version of <strong>Option</strong> Board.<br />

COM-20 [ Profi MAC ID ]<br />

• Sets MAC ID of profibus. The MAC ID must have a unique value in network.<br />

COM-30 [ Output Num ]<br />

• Sets the number of Read area address only.<br />

• Arrange COM #31~38 for using and set 1 to 8<br />

COM-40 [ Input Num ]<br />

• Sets the number of Write area address only.<br />

• Arrange COM #41~48 for using and set 1 to 8<br />

COM-67 [ Comm Update ]<br />

• In case of changing parameter concerned with communication, the changing contents use as<br />

updating.<br />

<br />

Address No Description Factory default Setting range<br />

945C I/O #92<br />

0 :None(Keep RUN)<br />

Driving method when lost<br />

0 (None) 1 :Free Run/ Stop<br />

Communication Cmd<br />

2 :Decel Stop<br />

945D I/O #93<br />

Decision time of<br />

Communication Cmd lost<br />

1.0s 1.0~120.0s<br />

• In case that COM #02 1(Command) ~ 3 (Cmd + Freq), it drives by setting value of I/O #48 during<br />

the time of I/O #49 while lost communication command.