Initial start-upFurther step-by-step instructions (continued)Update the LON particiapant list on Vitocontrol-S, <strong>WB2B</strong>Only possible if all users are connected <strong>and</strong> the control unit is encoded as fault manager (coding 79 : 1 factory defaultsetting)Note:In each heating system, only one Vitotronic may be encoded as fault manager.1. Press w <strong>and</strong> simultaneouslyfor approx. 2 s.The participant check is initiated.2. Press D.The participant list is updatedafter approx. 2 min.Participant check completed.Example of a LON systemVitocontrol-S Vitotronic 200-H Vitotronic 200-HVitocomLONLONLONParticipant no. 5Code ”77:5”Participant no. 10Set code ”77:10”Participant no. 11Set code ”77:11”Participant no. 99Send time via LONCode ”7b:1”Accept time via LONSet code ”81:3”Accept time via LONSet code ”81:3”Time received via LONTransmit outdoor temperaturevia LONSet code ”97:2”Receive outdoor temperaturevia LONSet code ”97:1”Device receives the timeCarrying out a participant checkThe communication with the system devices connected to the fault manager is tested by means of a participant check.Preconditions: The control unit must be programmed as fault manager (code 79:1). The LON participant number must be programmed in all control units(see page 31). The fault manager participant list must be up to date.Participant checkF01 : 011Consecutivenumber in theparticipant listParticipantnumber1. Press w <strong>and</strong> simultaneously forapprox. 2 seconds.2. Select the required participant with<strong>and</strong> .3. Activate check with .”Check” flashes until its completion.The display <strong>and</strong> all key illuminationsof the selected participant flash forapprox. 60 seconds. During communication betweenboth devices ”Check OK” isdisplayed. ”Check not OK” is displayed, if nocommunication is established.Check the LON connection <strong>and</strong>coding.4. To check further participantsproceed as described under points 2<strong>and</strong> 3.5. Press w <strong>and</strong> simultaneously forapprox. 1 second.5414 553 v1.432

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!