Troubleshooting – Vitotronic <strong>100</strong>, <strong>HC1</strong>Faults displayed at the programming unit (continued)FaultcodeSystem characteristics *1 Cause RemedyBurner in a fault mode No flame signal is present. Check ionization electrode <strong>and</strong>f4cable, measure the ionizationcurrent, check the gas pressure,check the gas valve, ignition,ignition module, ignition electrodes<strong>and</strong> condensate drain. Press “ERESET”.The gas valve closes too late. Check gas valve <strong>and</strong> both controlf8wiring <strong>and</strong> connections. Press “ERESET”.Fan speed too low at burner start. Check fan, fan supply cables, fanf9power supply <strong>and</strong> control. Press “ERESET”.Fan not at st<strong>and</strong>still. Check the fan, the fan connectingfacables <strong>and</strong> fan control. Press “ERESET”.fcGas valve faulty or faultymodulation valve control; or ventsystem blocked.Check the gas valve. check the ventsystem. Press “E RESET”.Burner blocked Burner control unit fault. Check ignition electrodes <strong>and</strong>fdconnecting cables. Check the boilercoding card. Check whether astrong interference (EMC) fieldexists near the equipment; press“E RESET”. Replace control unit ifthe fault persists.Burner blocked or in a fault mode Strong interference (EMC) field Restart the equipment. Replace thefenearby, or faulty main PCB.control unit if the equipment will notffNo faultcodedisplayedStrong interference (EMC) fieldnearby, or internal fault.restart.Boiler/burner in st<strong>and</strong>still Flow switch open Check pump operation <strong>and</strong> flowswitch.*1 Control mode: Boiler/burner fully operational (fault code must be verified <strong>and</strong> reset).Burner in fault mode: Boiler control requires manual reset before burner can resume operation.Burner blocked: If fault cause is corrected, burner resumes operation.5414 553 v1.450