(4) Troubleshooting procedure (If the air conditioner runs)Confirm the contents of the customer complaint.NOThe cause of the trouble canbe specifically identified.YESCheck the self-diagnosis display.See page 34.Eliminate the cause of the trouble and perform anoperation check.Is an error code displayed bythe self-diagnosis function?YESNOUsing the Service Mode, access the self-diagnosisdisplays generated in the past.See pages 35~38.YESIs there a history of selfdiagnosisdisplay items?NOUsing the Service Mode, access the stop history dueto protection control generated in the past.See pages 35~38.YESIs there a history of stops dueto protection control? (1)NOIdentify the faulty component by using the checkprocedure corresponding to the content of the trouble.Replace the faulty component, then perform anoperation check.The air conditioning system is operating normally.Note (1) Even in cases where only intermittent stop data are generated, the air conditioning system is normal. However, if the same protective operation recursrepeatedly (3 or more times), it will lead to customer complaints. Judge the conditions in comparison with the contents of the complaints.- 33 -