General InformationClogged Filter Switch (Optional)The unit mounted clogged filter switch monitors the pressuredifferential across the return air filters. It is mounted inthe filter section and is connected to the RTOM. A diagnosticSERVICE signal is sent to the remote panel if the pressuredifferential across the filters is at least 0.5" w.c. The contactswill automatically open when the pressure differentialacross the filters decreases to approximately 0.4" w.c. Theclogged filter output is energized when the supply fan is operatingand the clogged filter switch has been closed for atleast 2 minutes. The system will continue to operate regardlessof the status of the filter switch.Compressor Disable (CPR1/2)This input incorporates the low pressure control (LPC) ofeach refrigeration circuit and can be activated by opening afield supplied contact installed on the LTB.If this circuit is open before the compressor is started, thecompressor will not be allowed to operate. Anytime this circuitis opened for 1 continuous second during compressoroperation, the compressor for that circuit is immediatelyturned “Off”. The compressor will not be allowed to restartfor a minimum of 3 minutes should the contacts close.If four consecutive open conditions occur during the firstthree minutes of operation, the compressor for that circuitwill be locked out, a diagnostic communicated to the remotepanel (if installed), and a manual reset will be required torestart the compressor.Low Pressure ControlReliaTel ControlWhen the LPC is opened for 1 continuous second, the compressorfor that circuit is turned off immediately. The compressorwill not be allowed to restart for a minimum of 3minutes.If four consecutive open conditions occur during the firstthree minutes of operation, the compressor will be lockedout, a diagnostic communicated to ICS TM if applicable, and amanual reset will be required to restart the compressor.Electromechanical ControlWhen the LPC is opened, the compressor for that circuit isturned off immediately. The compressor will restart when theLPC closes.High Pressure Control (Optional)ReliaTel ControlThe high pressure controls are wired in series between thecompressor outputs on the RTRM and the compressorcontactor coils. If the high pressure control switch opens, theRTRM senses a lack of current while calling for cooling andlocks the compressor out.On dual circuit units, if the high pressure control opens, thecompressor on the affected circuit is locked out. A manualreset for the affected circuit is required.Electromechanical ControlWhen the HPC is opened, the compressor for that circuit isturned off immediately. The compressor will restart when theHPC closes.Power Exhaust Control (Optional)ReliaTel ControlThe power exhaust fan is started whenever the position ofthe economizer dampers meets or exceed the power exhaustsetpoint when the indoor fan is on.With the optional ventilation override accessory, the powerexhaust fan is independent of the indoor fan.The setpoint panel is located in the return air section and isfactory set at 25%.Electromechanical ControlThe power exhaust fan is started whenever the indoor fan ison and the adjustable damper limit switch DLS is closed.Lead/Lag Control (Dual Circuit Only)ReliaTel Control OnlyLead/Lag is a selectable input located on the RTRM. TheRTRM is configured from the factory with the Lead/Lagcontrol disabled. To activate the Lead/Lag function, simplycut the wire connected to J3-8 at the RTRM. When it isactivated, each time the designated lead compressor is shutoff due to the load being satisfied, the lead compressor orrefrigeration circuit switches. When the RTRM is poweredup, i.e. after a power failure, the control will default to thenumber one circuit compressor.Zone Sensor Module (ZSM) (BAYSENS006B)This electronic sensor features three system switch settings(Heat, Cool, and Off) and two fan settings (Onand Auto). It is a manual changeover control with singlesetpoint. (Cooling Setpoint Only)Zone Sensor Module (ZSM) (BAYSENS008B)This electronic sensor features four system switch settings(Heat, Cool, Auto, and Off) and two fan settings (On andAuto). It is a manual or auto changeover control with dualsetpoint capability. It can be used with a remote zone temperaturesensor BAYSENS017B.Zone Sensor (BAYSENS010B)This electronic sensor features four system switch settings(Heat, Cool, Auto, and Off) and two fan settings (On andAuto) with four system status LED’s. It is a manual or autochangeover control with dual setpoint capability. It can beused with a remote zone temperature sensorBAYSENS017B.Wall Mounted Relative Humidity Sensor (BAYSENS036A)Field installed, wall mounted humidity sensor is used tocontrol activation of the hot gas reheat dehumidificationoption. Humidity set points can be selected for relativehumidity levels between 40% and 60% by adjusting theDEHUMID setting on the ReliaTel Options Module. Seepage 24.Duct Mounted Relative Humidity Sensor(BAYSENS037A)Field installed, duct mounted humidity sensor is used tocontrol activation of the hot gas reheat dehumidificationoption. Humidity set points can be selected for relativehumidity levels between 40% and 60% by adjusting theDEHUMID setting on the ReliaTel Options Module. Seepage 24.6
General InformationProgrammable Zone Sensor - (BAYSENS019B)This 7 day programmable sensor features 2, 3 or 4 periodsfor Occupied or Unoccupied programming per day. If thepower is interrupted, the program is retained in permanentmemory. If power is off for an extended period of time, onlythe clock and day may have to be reset.The Zone Sensor allows selection of 2, 3 or 4 system modes(Heat, Cool, Auto, and Off), two fan modes (On and Auto). Ithas dual temperature selection with programmable start timecapability.The occupied cooling set point ranges between 45 and 98degrees Fahrenheit. The heating set point ranges between43 and 96 degrees Fahrenheit.A liquid crystal display (LCD) displays zone temperature,temperature set points, day of the week, time, and operationalmode symbols.The Option Menu is used to enable or disable applicablefunctions, i.e.; Morning Warm-up, Economizer minimum positionoverride during unoccupied status, Fahrenheit or Centigrade,Supply air tempering, Remote zone temperature sensor,12/24 hour time display, Smart fan, and Computed recovery.During an occupied period, an auxiliary relay rated for 1.25amps @ 30 volts AC with one set of single pole double throwcontacts is activated.Status Inputs (4 Wires Optional)The ZSM can be wired to receive four (4) operating statussignals from the RTRM (HEAT, COOL, SYSTEM “ON”, SER-VICE).Four (4) wires from the RTRM should be connected tothe appropriate terminals (7, 8, 9 & 10) on the ZSM.Remote Zone Sensor (BAYSENS013B)This electronic sensor features remote zone sensing andtimed override with override cancellation. It is used with aTrane Integrated Comfort TM building management system.Remote Zone Sensor (BAYSENS014B)This electronic sensor features single setpoint capability andtimed override with override cancellation. It is used with aTrane Integrated Comfort TM building management system.Remote Zone Sensor (BAYSENS016A)This bullet type temperature sensor can be used for; outsideair (ambient) sensing, return air temperature sensing, supplyair temperature sensing, remote temperature sensing (uncovered.Wiring procedures vary according to the particularapplication and equipment involved. Refer to the unit’s wiringdiagrams for proper connections.BAYSTAT036ASingle Stage - 1 Heat/1 CoolBAYSTAT037AMulti Stage - 2 Heat/2 Cool - Can be Used for EconomizerOperationBAYSENS025ARemote sensor for BAYSTAT036A and BAYSTAT037AHigh Temperature Sensor (BAYFRST001A)This sensor connects to the RTRM Emergency Stop Inputon the LTB and provides high limit “shutdown” of the unit.The sensor is used to detect high temperatures due to firein the air conditioning or ventilation ducts. The sensor isdesigned to mount directly to the sheet metal duct. Each kitcontains two sensors. The return air duct sensor(X1310004001) is set to open at 135 F. The supply air ductsensor (X1310004002) is set to open at 240 F. The controlcan be reset after the temperature has been lowered approximately25 F below the cutout setpoint.Evaporator Frost Control(ReliaTel Option)This input incorporates the Frostat control (FOS)mounted in the indoor coil circuit and can be activated byclosing a field supplied contact installed in parallel withthe FOS.If this circuit is open before the compressor is started, thecompressor will not be allowed to operate. Anytime thiscircuit is opened for 1 continuous second during compressoroperation, the compressor for that circuit is immediatelyturned “Off”. The compressor will not be allowed torestart for a minimum of 3 minutes should the FOS close.(Electro Mechanical Option)This input incorporates the Frostat control (FOS)mounted in the indoor coil circuit and can be activated byopening a field supplied contact installed in series with theFOS.If this circuit is open before the compressor is started, thecompressor will not be allowed to operate. Anytime thiscircuit is opened during compressor operation, the compressorfor that circuit is immediately turned “Off”. Thecompressor will restart when the FOS closes.Remote Zone Sensor (BAYSENS017B)This electronic sensor can be used with BAYSENS006B,008B, 010B, 019B Remote Panels. When this sensor is wiredto a BAYSENS019B Remote Panel, wiring must be 18 AWGShielded Twisted Pair (Belden 8760 or equivalent). Refer toThe specific Remote Panel for wiring details.Electro Mechanical ControlThe unit must have a Thermostat to operate.7