12120 OWNER'S MANUALMINIMUM CONTROL UNIT CONFIGURATIONPower SupplyA 3A, 24V nominal power supply provides all operating power to the control unit for both standby andalarm conditions. Sufficient battery charging capability is available to charge sealed lead-acid batterieswithin code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries onlyup to 7 AH. The back-up battery is 24V, maintained by floating on the power supply. The power supply isphysically contiguous with the main board.Addressable Device CircuitThe 12120 control unit has one addressable device circuit, that is programmed for connection to <strong>Faraday</strong>or <strong>System</strong> Sensor addressable devices.<strong>Faraday</strong> Addressable Devices:The addressable device circuit drives up to 60 addressable devices, detectors and/or modules.<strong>System</strong> Sensor Addressable Devices:The addressable device circuit drives up to 99 addressable sensors and 99 addressablemodules.Notification Appliance CircuitsThe 12120 control unit has four independent notification appliance circuits (NACs). Each circuit can beselected to give continuous output or one of eight sounding patterns available in the control unit. There isalso a system coder capable of zone coded operation. All of the NACs are power limited and can bewired for Class A (Style Z) or Class B (Style Y) operation.RS485 Communications CircuitThe 12120 control unit has a RS485 Communications Circuit that will drive up to 16 remote LCDannunciators and 8 Serial Relay <strong>Unit</strong>s and Serial Annunciator <strong>Unit</strong>s on the RS485 communication line.Status RelaysThree dry relay contacts are provided. These contacts are dedicated to alarm, trouble and supervisoryindications. The relay contacts are form C and are rated 1A @ 28VDC resistive.OPTIONAL CONTROL UNIT CONFIGURATIONA maximum control unit configuration can include all of the minimum configuration items plus additions asnoted below. Details of these accessories are given in Appendix D.City Tie BoardThe <strong>Faraday</strong> 12101 city tie board provides local energy and polarity reversal connections. The polarityreversal connections provide a trouble circuit and an alarm circuit with optional trouble output.RS232 Communication BoardThe <strong>Faraday</strong> 12103 RS232 communication board will allow event data to a serial printer or terminal.DACT BoardThe <strong>Faraday</strong> 12105 Digital <strong>Alarm</strong> Communication Transmitter board will send control unit status data to aremote receiving station.P/N 447192 Issue I (preliminary 10/31/2001)II-2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!