<strong>Mod</strong>.<strong>1043</strong>(DS<strong>1043</strong>-078)LBT7882SMOKE AND HEAT DETECTOR<strong>Ref</strong>. <strong>1043</strong>/<strong>231</strong> – <strong>1043</strong>/<strong>232</strong>


DESCRIPTIONThe operating principle of the optical-temperaturedetectors <strong>Ref</strong>. <strong>1043</strong>/<strong>231</strong> and <strong>Ref</strong>.<strong>1043</strong>/<strong>232</strong> isbased on analysis of the spreading of light causedby the particles of smoke present in the air and ona temperature sensor with an alarm threshold at55°.The detector acts as automatic gain control; amicrocontroller calculates the compensation of thereading to maintain constant sensitivity over time,correcting any increased level due to the deposit ofdust inside the analysis cell. A red led indicates thefollowing detector conditions: during normaloperation it flashes briefly every 4 seconds; in theevent of a fault or maintenance it flashes for half asecond once a second; in the event of an alarm,the indicator glows steadily.The detector <strong>Ref</strong>.<strong>1043</strong>/<strong>232</strong> has a base with relaywith NC and NO contacts for activating externaldevices in the event of an alarm..ASSEMBLY AND INSTALLATIONINSTRUCTIONSInstall the ceiling detector using 2 bolts.The detector is connected to the base making thereference arrows coincide.After installation and before testing, remove thedust cover from the detector.<strong>Ref</strong>erencearrowTRADIZIONALEALIM. ALLARMEABCN1CON RELEINOUTSCRNA NC COMCN2INDICATOR LEDSBrief flash every foursecondsGlowing steadily½ second flash once asecondnormal operationalarmmaintenance or faultCONNECTION TERMINALSTerminals Description– Power negative+IN Power positive input+OUT Power positive outputSCR (*) Do not useNO (*) Alarm relay NO contactNC (*) Alarm relay NC contactCOM (*) Alarm relay common(*) Only on detector <strong>Ref</strong>.<strong>1043</strong>/<strong>232</strong>NOTE: if only one detector is installed, or if it is thelast device on the line, connect the line endresistance between the +OUT and terminals.In a fire alarm system the position of jumper CN1must be the following:<strong>Ref</strong>.<strong>1043</strong>/<strong>231</strong>: position B<strong>Ref</strong>.<strong>1043</strong>/<strong>232</strong>: position A2 (DS<strong>1043</strong>-078)


Fig.1 Connection of two or more optical-temperature detectors <strong>Ref</strong>.<strong>1043</strong>/<strong>231</strong> (or -/<strong>232</strong>) to aconventional control unitA BCN1<strong>1043</strong>/<strong>231</strong> oA BA 24V 10 mA <strong>1043</strong>/<strong>232</strong>A 24V 10 mAB 24V 25 mA CN1B 24V 25 mA<strong>1043</strong>/221 <strong>1043</strong>/<strong>231</strong> <strong>1043</strong>/221o<strong>1043</strong>/<strong>232</strong>IN OUT SCR NANC COMINOUT SCR NANC COM- LINEACENTRALECONTROL UNIT+ LINEACN2Connect the line end resistance on the last detectorCN2LINE RESISTENZA ENDRESISTANCE FINE LINEA 3K33k3A BCN1<strong>1043</strong>/<strong>231</strong> oA BA 24V 10 mA <strong>1043</strong>/<strong>232</strong>A 24V 10 mACN1B 24V 25 mA B 24V 25 mA<strong>1043</strong>/<strong>231</strong> o<strong>1043</strong>/<strong>232</strong>INA 24V 25 mA A 24V 25 mAB 12V 16 mAB 12V 16 mAOUT SCR NANC COMINOUT SCR NANC COM- LINEACONTROLCENTRALEUNIT+ LINEACN2LINE RESISTENZA END RESISTANCE FINE LINEADO NOT connect the detectors in parallel with one another or on the lineCN2Fig 2 Connection of an outside optical repeater to an optical temperature detector <strong>Ref</strong>.<strong>1043</strong>/<strong>232</strong>A BCN1<strong>1043</strong>/<strong>232</strong> <strong>1043</strong>/222A 24V 25 mAB 12V 16 mAIN OUT SCR NA NC COM- LINEACONTROL CENTRALEUNIT+ LINEALINE+24VLINE RESISTENZA ENDRESISTANCEFINE LINEA3K3 3k3FROM DALLA CENTRALE CONTROL OTO UNIT FORADDITIONAL ALIMENTATORE POWER SUPPLEMENTARECN2+OUTSIDER FUORI PORTA REPEATER<strong>1043</strong>/035-To turn off outside repeater cut off the supply for at least 1 second.(DS<strong>1043</strong>-078) 3


TEST PROCEDURESInsert the white plastic rod provided a couple ofcentimetres inside the hole at the centre of thedetector top; check that the alarm led turns on. Itis turned off briefly cutting off the power.Note! Frequent cleaning is recommended inparticularly dusty environmentsTECHNICAL SPECIFICATIONSAll models:Stand-by intake:75 µA meanResponse time:3 sAlarm temperature range: 55° +/-5%Alarm threshold (smoke): m=0.16dBm +/-20%Max. air speed:1m/sWorking temperature range: 0° ÷ 70° CMax. relative humidity: 92%Weight: 210Dimensions:Ø115 x 45 mm<strong>1043</strong>/<strong>231</strong> only:Power voltage:11÷29VdcUptake in the case of alarm(*): 25mA @ 24Vdc10mA @ 24VdcRelay Output:not available<strong>1043</strong>/<strong>232</strong> only:Power voltage:20÷29VdcOr 11÷15VdcUptake in the case of alarm(*): 25mA @ 24Vdc16mA @ 12VdcRelay Output:NO-NC 1A @ 30Vdc(*) Important: intake during an alarm variesdepending on the position of jumper CN1.Before changing the position of the jumpercheck the alarm threshold of the control unit towhich the device is connected.(DS<strong>1043</strong>-078)LBT7882BRANCHES20151 MILANO - Via Gallarate 218Tel. 02.380.111.75 - Fax 02.380.111.8000043 CIAMPINO (ROMA) Via L.Einaudi 17/19ATel. 06.791.07.30 - Fax 06.791.48.9780013 CASALNUOVO (NAPOLI)URMET DOMUS S.p.A.10154 TORINO (ITALY)VIA BOLOGNA 188/CTel. 011.24.00.000 (RIC. AUT.)Fax 011.24.00.300 – 323Call Center 011.23.39.801Via Nazionale delle Puglie 32 Tel. 081.193.661.20 - Fax 081.193.661.04(DS<strong>1043</strong>-078)30030 VIGONOVO (VENEZIA) - Via del Lavoro 71 http://www.urmetdomus.comTel. 049.738.63.00 r.a. - Fax 049.738.63.11e-mail: info@urmetdomus.it