Transport and Storage<strong>GEA</strong> <strong>CAIRplus</strong>4.3 StorageNOTEObserve the permissible storage conditions when storing the unit. Only removethe original packaging just before the installation starts.Protect the unit before commissioning against building dust and dirt as well asdamage.Suitable measures must be taken to protect units delivered without packagingagainst building dust and dirt prior to commissioning. Care must be taken toensure that condensation cannot form below packaging supplied by others (byensuring the correct distance between the packaging and the casing).• Always place units on an even surface during storage or intermediate storage.• Protect units from bumps and knocks which may damage the casing andprojecting components.• If commissioning is not carried out within three months of the delivery the beltdrive must be slackened.• Turn the motor axle and fan through at least 2 revolutions every 3 months.Permitted storage conditions / air conditions for non-installed units.Air temperatureAir humidity-10°C to +50°<strong>CS</strong>tore units in a dry, non-condensing environment22 PR-2009-0096-GB • Subject to modifications • Status 07/2010