MW-UUltrasonic Flow SensorsUltrasonic heat sensors have no moving partswhich makes them almost wear free andnoiseless. They measure the flow by using thetransit time principle, one ultrasonic signal islaunched in the flow direction and one againstthe flow direction. The calculator uses thelatest innovative technology to calculate heatusage from heating systems. With its dynamicmeasuring cycle even the smallest energyconsumptions are reliably collected. The largemultifunction display permanently shows theheat consumption total; it is possible to scrollthrough the display to show all data.SPECIFICATIONNominal flow rate: Qp 0.6 to Qp 60m 3 /hMax. static pressure: Screwed 16 bar (232 psi)Flanged 25 bar (362 psi)Body materials: BrassTemperature range: Heating 10 to 130°C (50 to 266˚F)Cooling 10 to 50°C (50 to 122˚F)Maximum temp: 50°C (122˚F) for 2000 hTemperature diff: 3 to 120KSupply:3.6V Lithium batteryBattery life: 6 years (optional 11 year available upon request)Display:Multifunction 8-digit + characters LCDOutput pulse: 30Vdc max. @ 20mAPulse duration: 400m/s