TT-322Duct SensorsPart code DescriptionActive OutputTT-322-CVO 4-20mA/0-10Vdc selectable output,Output ranges:–10 to +40°C (14 to 104°F) or–10 to +110°C (14 to 230°F) (selectable)TT-322-CVO-C 4-20mA/0-10Vdc selectable output(custom temp. scaling), Calibration tocustomer specification in the range of–10 to +90°C (14 to 194°F)Suffix (add to part code)-250 250mm probe lengthAccessoryTT-DFP Duct flange plateData sheets: TT-322.pdf ∙ TT-CVO.pdfNote: Custom lengths available.The TT-322 direct output, temperature sensorused to measure air temperature in ducts.Units contain either a high quality thermistor,nickel or platinum sensing element. The sensingelement is fitted into a stainless steel probe.A flange plate is available for adjustment ofpenetration depth (order as TT-DFP).SPECIFICATIONOutput types:Thermistor ResistiveCurrent 4 to 20mAVoltage 0 to 10VdcProbe: Material Stainless steel 304Dimensions 150mm (5.91”) or 250mm (9.84”) x6mm (0.24”) dia.Housing: Material ABS (flame retardant)Dimensions 74 x 70 x 50mm (2.91 x 2.76 x 1.97”)Ambient range:Protection:Weight:–10 to +90°C (14 to 194°F)IP65160g (0.35 lb)Part code DescriptionPassive OutputTT-322-A 10K3A1, Trend, Seachange, Cylon, DistechTT-322-B 10K4A1, Andover, Delta ControlsTT-322-C 20K6A1, HoneywellTT-322-D PT100A, SerckTT-322-E PT1000A, CylonTT-322-F Ni1000A, SauterTT-322-G Ni1000A/TCR (LAN1), SiemensTT-322-H SAT1, SatchwellTT-322-K STA1, Landis & StaefaTT-322-L TAC1, TACTT-322-M 2.2K3A1, Johnson ControlsTT-322-N 3K3A1, AlertonTT-322-P 30K6A1, DraytonTT-322-Q 50K6A1, AmbiflexTT-322-R 100K6A1, York >40°CTT-322-S SAT2, SatchwellTT-322-T SAT3, SatchwellTT-322-W SIE1, SiebeTT-322-Y STA2, Landis & StaefaTT-322-Z 10K NTC, CarelVolume Price Breaks are applicableUnit Price (10-19 and 20+)TT-322-A 10K3A1 Please see price listTT-322-B 10K4A1TT-322-C 20K6A1TT-322-E PT1000ATT-322-G Ni1000A/TCRTT-322-H SAT1TT-322-K STA1TT-322-L TAC1TT-626True Duct Averaging Sensors<strong>Sontay</strong>’s true duct averaging sensor containsa PT100B element, which measures at pointalong the full length of the copper tube.SPECIFICATIONOutput types: PT100B ResistiveCurrent 4 to 20mAVoltage 0 to 10VdcProbe: Material CopperDimensions 2050mm (6.73 ft)(includes 50mm (1.97”) collar) x ¼” dia.Housing: Material ABS (flame retardant)Dimensions 116 x 106 x 52mm (4.57 x 4.17 x 2.05”)Ambient range:–10 to +90°C (14 to 194°F)Protection:IP65Weight:420g (0.93 lb)Part code DescriptionPassive OutputTT-626-PT100B PT100B Thermistor OutputActive OutputTT-626-CVO 4-20mA/0-10Vdc selectable outputOutput ranges:–10 to +40°C (14 to 104°F) or–10 to +110°C (14 to 230°F) (selectable)TT-626-CVO-C 4-20mA/0-10Vdc selectable output(custom temp. scaling), Calibration tocustomer specification in the range of–10 to +90°C (14 to 194°F)Data sheets: TT-626.pdf ∙ TT-CVO.pdfAir & Water Flow Air Quality & Gas Detection Controllers Input / Output Modules Water & Energy Metering Peripherals54www.sontay.com · Email sales@sontay.com
TT-331Outside Air SensorsVolume Price Breaks are applicableThe TT-331 range are direct output,temperature sensors for measuring outsideair temperature. Units contain either a highquality thermistor, Nickel or Platinum sensingelement. The sensors are housed in IP65 ratedenclosures. The TT-331 has a cap containingthe sensing element located externally inthe shadow of the lid to curb the effects ofsolar gain, but should always be situated in asheltered position on a north facing wall.SPECIFICATIONOutput types:Thermistor ResistiveCurrent 4 to 20mAVoltage 0 to 10VdcHousing material: ABS (flame retardant)Dimensions: 74 x 70 x 50mm (2.91 x 2.76 x 1.97”)Ambient range:–10 to +90°C (14 to 194°F)Protection:IP65Weight:160g (0.35 lb)Unit Price (5-9 and 10+)TT-331-A 10K3A1 Please see price listTT-331-B 10K4A1TT-331-C 20K6A1TT-331-D PT100ATT-331-E PT1000ATT-331-G Ni1000A/TCRTT-331-H SAT1TT-331-K STA1TT-331-L TAC1Part code DescriptionPassive OutputTT-331-A 10K3A1, Trend, Seachange, Cylon, DistechTT-331-B 10K4A1, Andover, Delta ControlsTT-331-C 20K6A1, HoneywellTT-331-D PT100A, SerckTT-331-E PT1000A, CylonTT-331-F Ni1000A, SauterTT-331-G Ni1000A/TCR (LAN1), SiemensTT-331-H SAT1, SatchwellTT-331-K STA1, Landis & StaefaTT-331-L TAC1, TACTT-331-M 2.2K3A1, Johnson ControlsTT-331-N 3K3A1, AlertonTT-331-P 30K6A1, DraytonTT-331-Q 50K6A1, AmbiflexTT-331-R 100K6A1, York >40°CTT-331-S SAT2, SatchwellTT-331-T SAT3, SatchwellTT-331-V SAT4, SatchwellTT-331-W SIE1, SiebeTT-331-Y STA2, Landis & StaefaTT-331-Z 10K NTC, CarelActive OutputTT-331-CVO 4-20mA/0-10Vdc selectable outputOutput ranges:–10 to +40°C (14 to 104°F) or–10 to +110°C (14 to 230°F) – selectableTT-331-CVO-C 4-20mA/0-10Vdc selectable output(custom temp. scaling), Calibration tocustomer specification in the range of–10 to +90°C (14 to 194°F)Data sheets: TT-331.pdf ∙ TT-CVO.pdfTT-332Outside Air Sensors with Radiation ShieldFor measuring outside air temperature the TT-332 contains either a high quality thermistor,nickel or platinum sensing element. Thesensors are housed in IP65 rated enclosures.The TT-332 has the element fitted into aPTFE radiation shield, designed to providefast response times to changes in outside airtemperature and to protect the element fromthe effects of direct sunlight.SPECIFICATIONOutput types:Thermistor ResistiveCurrent 4 to 20mAVoltage 0 to 10VdcHousing material: ABS (flame retardant)Dimensions: 74 x 70 x 50mm (2.91 x 2.76 x 1.97”)Ambient range:–10 to +90°C (14 to 194°F)Protection:IP65Weight:160g (0.35 lb)Part codeTT-332-CVOTT-332-CVO-CDescriptionActive Output4-20mA/0-10Vdc selectable outputOutput ranges:–10 to +40°C (14 to 104°F) or–10 to +110°C (14 to 230°F) – selectable4-20mA/0-10Vdc selectable output(custom temp. scaling), Calibration tocustomer specification in the range of–10 to +90°C (14 to 194°F)Part code DescriptionPassive OutputTT-332-A 10K3A1, Trend, Seachange, Cylon, DistechTT-332-B 10K4A1, Andover, Delta ControlsTT-332-C 20K6A1, HoneywellTT-332-D PT100A, SerckTT-332-E PT1000A, CylonTT-332-F Ni1000A, SauterTT-332-G Ni1000A/TCR (LAN1), SiemensTT-332-H SAT1, SatchwellTT-332-K STA1, Landis & StaefaTT-332-L TAC1, TACTT-332-M 2.2K3A1, Johnson ControlsTT-332-N 3K3A1, AlertonTT-332-P 30K6A1, DraytonTT-332-Q 50K6A1, AmbiflexTT-332-R 100K6A1, York >40°CTT-332-S SAT2, SatchwellTT-332-T SAT3, SatchwellTT-332-V SAT4, SatchwellTT-332-W SIE1, SiebeTT-332-Y STA2, Landis & StaefaTT-332-Z 10K NTC, CarelData sheets – TT-332.pdf, TT-CVO.pdf& Interfaces Pressure Relative Humidity Wireless Devices Temperature Valves & ActuatorsUK Tel. +44 (0) 1732 861200 · Int. Tel. +44 (0) 1732 861225 · UK Fax +44 (0) 1732 861201 · Int. Fax +44 (0) 1732 86122655