Table 3: Supported Baud Rates<br />
Baud Rate Integer Value<br />
19.2 kbps (Default) 0<br />
1.2 kbps 1<br />
2.4 kbps 2<br />
4.8 kbps 3<br />
9.6 kbps 4<br />
14.4 kbps 5<br />
19.2 kbps 6<br />
28.8 kbps 7<br />
38.4 kbps 8<br />
57.6 kbps 9<br />
76.8 kbps 10<br />
115.2 kbps 11<br />
230.4 kbps 12<br />
3.4 <strong>Modbus</strong> Parity<br />
Register Address: 43024<br />
Default Value: 0 (Odd)<br />
Supported Values: Odd, None and Even.<br />
Units: N/A<br />
The parity specifies the parity between the <strong>Modbus</strong> master and the <strong>Modbus</strong> Adapter. Read register<br />
43024 to obtain the current parity. Write to the same register to change it using the integer values in the<br />
following table.<br />
Table 4: Parity<br />
Parity Integer Value<br />
Odd (Default) 0<br />
None 1<br />
Odd 2<br />
Even 3<br />
<strong>Thermo</strong> <strong>Scientific</strong> AquaSensors DataStick <strong>Modbus</strong> Communications User Guide 7