12.07.2015 Views

Effect of Automatic Sprinkler Protection on Smoke Control Systems

Effect of Automatic Sprinkler Protection on Smoke Control Systems

Effect of Automatic Sprinkler Protection on Smoke Control Systems

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1An uncertainty analysis, applied to the measurements andequati<strong>on</strong>s used to calculate the heat release rate from oxygenc<strong>on</strong>sumpti<strong>on</strong> measurements, indicated that there is an uncertainty<str<strong>on</strong>g>of</str<strong>on</strong>g> 12% in the computed heat release rates. The presence' <str<strong>on</strong>g>of</str<strong>on</strong>g>significant amounts <str<strong>on</strong>g>of</str<strong>on</strong>g> water in the products <str<strong>on</strong>g>of</str<strong>on</strong>g> combusti<strong>on</strong>increased the uncertainty in the oxygen c<strong>on</strong>sumpti<strong>on</strong> calculati<strong>on</strong>s.The mass loss rate <str<strong>on</strong>g>of</str<strong>on</strong>g> the burning cribs was measured with anaccuracy <str<strong>on</strong>g>of</str<strong>on</strong>g> ±2%, although the combined effects <str<strong>on</strong>g>of</str<strong>on</strong>g> mass loss dueto burning and evaporati<strong>on</strong> and mass gain due to the c<strong>on</strong>stantspray <str<strong>on</strong>g>of</str<strong>on</strong>g> sprinkler water <strong>on</strong>to the crib complicated interpretati<strong>on</strong><str<strong>on</strong>g>of</str<strong>on</strong>g> the mass loss measurements. The overall uncertainty in the heatrelease rates was estimated to approach 1 S%.ASHRAE Transacti<strong>on</strong>s: Research]"'~0:<str<strong>on</strong>g>Sprinkler</str<strong>on</strong>g> spray density, Lprnlm 20 2 3 4 5 6 7 8' ..'22002000 ~ UnsprinkleredOne-storey Test Room Results 20001800' 1200 lb (545 kg) wood cribs' - 18001600 f-' ' ,,#"Envelope- 16001400'50 % ltducti<strong>on</strong>I ' ' 'Unshielded -400I ·=- {""\""'L 400200 f- # 'Figure 3""1400600,.2000 ' • ' 00.00 0.05 0.10 0.15 0.20<str<strong>on</strong>g>Sprinkler</str<strong>on</strong>g> spray densily, USgpmtft'• Nore: HRR at a given density depends <strong>on</strong> staa:e <str<strong>on</strong>g>of</str<strong>on</strong>g> fire developmentprior to applicati<strong>on</strong> <str<strong>on</strong>g>of</str<strong>on</strong>g> water spray, See discussi<strong>on</strong> in tcxL01200'1100 f-',1000tests between the computed heat release rate based <strong>on</strong>oxygen calorimetry and that determined using the measurements<str<strong>on</strong>g>of</str<strong>on</strong>g> mass loss, the same factor was used to determinethe heat release rate <str<strong>on</strong>g>of</str<strong>on</strong>g> the wood cribs in the Tower tests. 1Tests were c<strong>on</strong>ducted with no sprinklers, with sprinklersand shielding, and with sprinklers and no shielding. Inthe oO:e test without sprinklers, which was c<strong>on</strong>ducted in the<strong>on</strong>e-story room, the fire in the I ,200-lb (545-kg) cribattained an HRR <str<strong>on</strong>g>of</str<strong>on</strong>g> more than 1,900 Btu/s (2,000 kW)under limited ventilati<strong>on</strong> c<strong>on</strong>diti<strong>on</strong>s <str<strong>on</strong>g>of</str<strong>on</strong>g> I ,000 cfm (0.42m 3 /s). By increasing the ventilati<strong>on</strong> rate to 1,500 cfm (0.63m3/s), the HRR increased to 3,000 kW. No unsprinkleredcase was tested in the Tower, but it is estimated fromburning rates observed during periods when the sp_rinklerspray was turned <str<strong>on</strong>g>of</str<strong>on</strong>g>f during the course <str<strong>on</strong>g>of</str<strong>on</strong>g> the test that the700-lb (318-kg) cribs would have had an HRR <str<strong>on</strong>g>of</str<strong>on</strong>g> 1,150Btu/s (1,213 kW) under unsprinklered c<strong>on</strong>diti<strong>on</strong>s.Several tests were c<strong>on</strong>ducted using fast-resp<strong>on</strong>sesprinklers (listed for <str<strong>on</strong>g>of</str<strong>on</strong>g>fice occupancies), which operated 30to 50 sec<strong>on</strong>ds faster than standard sprinklers. Normally,faster resp<strong>on</strong>se would he a significant advantage for firesuppressi<strong>on</strong> because the HRR <str<strong>on</strong>g>of</str<strong>on</strong>g> the fire is smaller earlierin the fire growth, hence the fire is easier to extinguish.The advantage was so<strong>on</strong> dissipated, however, for shieldedfires. After an initial slowing <str<strong>on</strong>g>of</str<strong>on</strong>g> the burning rate, withinseveral minutes the fire within the shielded area regrew tothe same size it achieved with standard sprinklers.Ten tests were c<strong>on</strong>ducted with shielded

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!