9. FAULT FINDINGELECTRICITY SAFETY - Before making any electrical checks, switch off mains supply to boiler.FAULT POSSIBLE CAUSE ACTIONBURNER WILL NOT START Control box locked out Press reset button on front of burner.N.B. ONLY TRY TWICELimit-stat trippedBoiler thermostat or other system<strong>co</strong>ntrols satisfiedFuse blownCheck for live supply <strong>co</strong>ntinuity upto burnerMotor or pump seizedPress reset button under <strong>co</strong>ntrol panel andcheck function of boiler <strong>co</strong>ntrol thermostat.Ensure all <strong>co</strong>ntrols are calling for heat.Fit new 5 amp fuse, if it blows again, checkfor short circuit in wiring.If live supply <strong>co</strong>nfirmed, change <strong>co</strong>ntrol boxCheck for rotation and replace asnecessary.BURNER STARTS No oil supply Check oil level in tank and feed to burner.BUT FLAME NOTESTABLIS<strong>HE</strong>D Photo-cell not seeing flame Clean photo-cell and ensure it is fullyplugged in.Air trapped in pumpSolenoid valve faultyNozzle blockedElectrodes in<strong>co</strong>rrectly setBleed off air through pressure gaugetapping.Check <strong>co</strong>il for <strong>co</strong>ntinuity andreplace if faulty.Replace nozzle with one of samespecification.Reset gap and positionelectrodes as shown in Burner diagram.Electrode insulator crackedIgnition transformer and H.T.<strong>co</strong>ntactsLow oil pressureCheck and replace if insulator cracked orcrazed.Check for spark and <strong>co</strong>ndition of H.T.<strong>co</strong>ntacts. Replace as necessary.Check pump pressure and adjust to<strong>co</strong>rrect setting.FLAME ESTABLIS<strong>HE</strong>D <strong>Oil</strong> <strong>co</strong>ntaminated with water Run off oil at burner until free ofBUT BURNER LOCKSwater and drain <strong>co</strong>ndensation from tankOUT AFTER FEW SECONDS<strong>Oil</strong> filter partially blockedWash filter clean with kerosene.Photo-cell fault<strong>Oil</strong> pressure lowClean photo-cell and ensureit is fully plugged in. Replace if faulty.Check pump pressure and adjustto <strong>co</strong>rrect setting.22

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!