02.96 Technical data14.1 Power reduction at increased coolant temperatureThe rated current must be reduced according to Figure 14.2 for cooling medium temperatures exceeding 40°C.Cooling medium temperatures > 50°C are not permissible.permissible rated currentin %100908075706010 20 30 40 50Coolant temperaturein °CFigure 14.2 Maximum permitted rated current depending on coolant temperature14.2 Power reduction at altitudes > 1000m above MSLThe rated current must be reduced as shown in Figure 14.3 in the event of installation altitudes > 1000 m abovemean sea level. Installation altitudes > 2000 m above MSL (please enquire)permissible rated currentin %permissible rated voltagein %10010090908080707060600 1000 2000 3000 4000Installation altitudein m above sea level0 1000 2000 3000 4000Installation altitudein m above sea levelFigure 14.3Maximum values for rated current and rated voltage depending on installation altitudeSiemens AG 6SE7087-6AE85-0AA0 ENGLISH 14-5<strong>Common</strong> Rectifier Operating instructions