1. DESIGN METHODS1-1. System Overview1-1-1. Outdoor UnitsCorresponding HPInverter unit4HP 5HP 6HPModel nameHeat pump (50Hz)Heat pump (60Hz)<strong>MCY</strong>-<strong>MAP0401HT</strong> <strong>MCY</strong>-<strong>MAP0501HT</strong> <strong>MCY</strong>-<strong>MAP0601HT</strong><strong>MCY</strong>-<strong>MAP0401HT</strong>2D <strong>MCY</strong>-<strong>MAP0501HT</strong>2D <strong>MCY</strong>-<strong>MAP0601HT</strong>2DCooling capacity (kW) ∗1Heating capacity (kW) ∗1No.of connectable indoor units12.1 14.0 15.512.5 16.0 18.06 8 9∗1 Rated conditionsCooling:Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DBHeating:Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WBAllocation standard of model name<strong>MCY</strong>- M APH T 2DNo mark : Power supply specification, 1Ø/220/230/240V (50Hz)2D : Power supply specification, 1Ø/220V, 60HzT : Inverter unitH : Heat pumpDevelopment numberCapacity rank HP × 10R410AM : Individual unitMulti Compact type10