Flexible connectivity to automation networksOur fieldbus adapter modules enable communication between<strong>drives</strong>, systems, devices and software. Our <strong>industrial</strong> <strong>drives</strong>are compatible with a wide range of fieldbus protocols.The plug-in fieldbus adapter module can easily be mountedinside the drive. Other benefits include reduced wiring costswhen compared with traditional input/output connections.Fieldbus systems are also less complex than conventionalsystems, resulting in less overall maintenance.Multiple fieldbus connections for flexible control<strong>ACS880</strong> supports two fieldbus connections simultaneously.The user has flexibility of choice for control modes by beingable to select one protocol for control and one for monitoring.Drive monitoringA set of drive parameters and/or actual signals, such astorque, speed, current, etc., can be selected for cyclic datatransfer, providing fast data access.Drive diagnosticsAccurate and reliable diagnostic information can be obtainedthrough the alarm, limit and fault words.Drive parameter handlingThe Ethernet fieldbus adapter module allows users to buildan Ethernet network for drive monitoring and diagnostic andparameter handling purposes.CablingSubstituting the large amount of conventional drive controlcabling and wiring with a <strong>single</strong> cable reduces costs andincreases system reliability and flexibility.DesignThe use of fieldbus control reduces engineering time atinstallation due to the modular structure of the hardware andsoftware and the simplicity of the connections to the <strong>drives</strong>.Commissioning and assemblyThe modular machine configuration allows pre-commissioningof <strong>single</strong> machine sections and provides easy and fastassembly of the complete installation.Universal communication with <strong>ABB</strong> fieldbus adaptersThe <strong>ACS880</strong> supports the following fieldbus protocols:Fieldbus adapter modulesOption Option code Fieldbus protocolFPBA-01 +K454 PROFIBUS DP, DPV0/DPV1FCAN-01 +K457 CANopen ®FDNA-01 +K451 DeviceNetFENA-11 +K473 1 port EtherNet/IP, Modbus TCP,PROFINET IO, PROFIsafe 1)FENA-21 +K475 2 port EtherNet/IP, Modbus TCP,PROFINET IO, PROFIsafe 1)FECA-01 +K469 EtherCAT ®FSCA-01 +K458 Modbus RTUFEPL-02 +K470 PowerLinkFCNA-01 +K462 ControlNet TM1)For the PROFIsafe to work PROFINET fieldbus adapter module(FENA-11/-21) and the safety functions module (FSO-11) are required.<strong>ACS880</strong> drive with fieldbus adapters and feedbackinterface module24 <strong>ABB</strong> <strong>industrial</strong> <strong>drives</strong> <strong>ACS880</strong> <strong>single</strong> <strong>drives</strong> | Catalog
Input/output extension modules for increased connectivityStandard input and output can be extended by using optionalanalog and digital input/output extension modules. Themodules are easily installed in the extension slots located onthe control unit.Analog and digital input/output extension modulesOption Option code ConnectionsFIO-01 +L501 4×DI/O, 2×ROFIO-11 +L500 3×AI (mA/V), 1×AO (mA), 2×DI/OFAIO-01 +L525 2×AI(mA/V), 2×AO(mA)Speed feedback interfaces for precise process control<strong>ACS880</strong> <strong>drives</strong> can be connected to various feedbackdevices, such as HTL pulse encoder, TTL pulse encoder,absolute encoder and resolver. The optional feedback moduleis installed in the option slot on the drive. It is possible to usetwo feedback modules at the same time, either of the sametype or different type.I/O option extension adapterFor additional I/O option slots the FEA-03 is suitable for thisuse. An analog and digital input/output extension and speedfeedback interface can be installed on the FEA-03. Twoextension modules can be installed on each I/O extensionslot. The connection to the control unit is via an fiber optic linkand the adapter can be mounted on an DIN rail (35 x 7.5 mm).Feedback interface modulesOption Option code ConnectionsFEN-01 +L517 2 inputs (TTL pulse encoder), 1 outputFEN-11 +L518 2 inputs (SinCos absolute, TTL pulseencoder), 1 outputFEN-21 +L516 2 inputs (Resolver, TTL pulse encoder),1 outputFEN-31 +L502 1 input (HTL pulse encoder), 1 outputI/O extension adapterOption Option code ConnectionsFEA-03 1) +L515 2×F-type option extension slots1)Please check availability from your local <strong>ABB</strong>.DDCS communication option modulesThe FDCO-0X optical DDCS communication options are addonmodules on the <strong>ACS880</strong> <strong>industrial</strong> <strong>drives</strong> control board.The modules include connectors for two fiber optic DDCSchannels. The FDCO-0X modules make it possible to performmaster-follower and AC800 M communication.Option Option code ConnectionsFDCO-01 +L503 Optical DDCS (10 Mbd/10 Mbd)FDCO-02 +L508 Optical DDCS (5 Mbd/10 Mbd)Remote monitoring access worldwideThe remote monitoring tool, NETA-21, gives easy access tothe drive via the Internet or local Ethernet network. NETA-21comes with a built-in web server. Being compatible withstandard web browsers, it ensures easy access to a webbaseduser interface. Through the interface the user canconfigure drive parameters, monitor drive log data, and followup load levels, run time, energy consumption, I/O data andbearing temperature of the motor connected to the drive.The user can access the remote monitoring tool web pageusing 3G modem from anywhere with a standard PC, tabletor a mobile phone. The remote monitoring tool helps toreduce cost when personnel are able to monitor or performmaintenance for unmanned or manned applications in a rangeof industries. It is also very useful when more than one userwants to access the drive from several locations.Enhanced monitoring functionsThe remote monitoring tool supports process and drivedata logging. Values of process variables or <strong>drives</strong> actualvalues can be logged to NETA-21´s SD memory card whichis situated in the remote monitoring tool or sent forward toa centralized database. NETA-21 does not need an externaldatabase as the remote monitoring tool is able to storevaluable data of the drive during its entire lifetime.Unmanned monitoring of processes or devices is ensured bythe built-in alarm functions that notify maintenance personnelif a safety level is reached. Alarmhistory with true time stamps arestored internally to the memorycard as well as technical data,which is provided by the drive fortroubleshooting purposes. Truetime stamps are also used with<strong>drives</strong> that do not have a real timeclock as standard for ensuringevents of all connected <strong>drives</strong>.NETA-21Catalog | <strong>ABB</strong> <strong>industrial</strong> <strong>drives</strong> <strong>ACS880</strong> <strong>single</strong> <strong>drives</strong> 25