and otheres:www.comat.ch3Three-phase Monitoring RelaySSU34 (50Hz)SSU36 (60Hz)DO NOT connect simultaneously: neutral conductor N and bridge L3-L!NoderorL3L2L1L< >UMIN MAX∆ U, ϕ, ƒPHASESEQUENCE123t del0,2-5sfailredSSU34/36gnokalokalarmµ 5A 250VA1250VA/...150W4 5 6 3 7 8In case of power failure the alarm is activated without delay!MAINS MONITORINGSSU34, SSU36E The SSU34(50Hz) and the SSU36(60Hz) provide comprehensive monitoring ofthree-phase mains supplies with or without neutral.The following mains faults are moni-tored:Error signal 1 U (V , V ):Exceeding or dropping below the set voltage values Umin/Umax for L1-N orL1-L3,L (no differential voltage, phase position or frequency fault).Error signal 2 ∆U, ∆ϕ, ∆ƒ:One or more of the three voltages, phase positions, or the mains frequency are divergingfrom the required value. Depending on the nature of their occurrence ∆-errors are evaluated cumulatively.Error signal 3 :Connection polarity reversal (wrong phase-sequence). Any error is signalled bythe red LED "fail" and is reported after expiry of the set alarm-delay time (tdel0,2...5s) (for error signal 3 undelayed) via 5-6 and 7-8.In the correct status (ok) the green LED is illuminated (5-6 and 7-8 open, 5-4and 7-2 closed).Monitoring Relays4U1Overvoltage>(Umax)Undervoltage