13.07.2015 Views

ZUCCHINI LMP 001-079_EN.indd - Legrand

ZUCCHINI LMP 001-079_EN.indd - Legrand

ZUCCHINI LMP 001-079_EN.indd - Legrand

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Determination of the operatingcurrent of a busbarIn order to determine the current whereby it is necessary to choose the busbar,the following planning data must be known:• type of load inputs: three-phase or single-phase;• type of circuit input: from one end, from both ends, central input, etc.;• nominal input voltage;• number, power and cos of loads which are to be fed by the busbar;• load diversity factor;• load use nominal factor;• assumed short circuit current at the input point;• room temperature;• type of busbar installation (edgewise, flat, vertical).VOLTAGE DROPv% = bdefinedI bVnLv%PTOT • • • dkI b=[A]3 • Ue • cos mediumb =2b =1ex: MR 160I b=15 20 25 30 35 40 45 50 55 601.15 1.12 1.08 1.05 1.025 1 0.975 0.95 0.93 0.89I nt I bI nt= k 1• I nWhen using a three-phase power supply, the operating current is determinedby the following formula:where:I boperating current [A]; load diversity factor [.]; load use factor [.];d feed factor [.];P TOTsum of the total active power of installed loads [W];Ue operating voltage [V];cos mediumaverage load power factor [.];The “d” input factor has a value of 1 when the busbar is fed from one end only.The value is 1/2 if fed from the centre or if it is fed from each end.Once the operating current has been determined, choose the busbar with a ratedcurrent immediately higher than the one calculated.All Zucchini products have been designed and tested for an average roomtemperature of 40 °C; should they be installed in rooms with average dailytemperatures different from 40 °C the rated current of the busbar should bemultiplied by a k1 factor that is greater than the unit for temperatures lower than40°C and lower than the unit if the room temperature is higher than 40°C.Roomtemperature [°C]k 1thermal correctionfactor [.]Finally, the following should be considered for the most appropriate busbarchoice:where I ntrepresents the maximum current loaded by a busbar for an indefinitetime at the specified room temperature.JOULE EFFECT LOSSESLosses due to the Joule effect are essentially caused by the electrical resistanceof the busbar. Lost energy is transformed into heat and contributes to theheating of the conduit.If the length of the line is particularly long (>100m) it is necessary to check thevoltage drop (hereinafter specified as v.d.). If the installation is a three phasesystem and the power factor is not lower than cos = 0.7 the v.d. may be calculatedwith the coefficients of the voltage drop specified in the technical data table.k . I b . LVn. 100= the current that supplies the busbar [A]= the voltage power supply of the busbar [V]= the length of the busbar [m]= the voltage drop percentageb = the distribution factor of the current [.]= corresponding voltage drop factora cos [V/m/A] (see technical data table)The current distribution factor “b” depends on how the circuit is fed and on thedistribution of the electric loads along the busbar:supplies at one end and loadat the end of the linesupplies at one end and withload evenly distributedb =0.5 supplies at both ends and withload evenly distributedb =0.5 central supply with loadsat both endsb =0.25 central supply with loaddistributed evenly80A operating currentb=1 supply from one endk=0.608 see technical data tableCos = 0.85L= 100m line lengthVn= 400V operating voltageI bLI bI bLI bLI bI b2 Lv% = bk . I b . LVn . 10 3SHORT-CIRCUIT CURR<strong>EN</strong>TThe short circuit current value I CW that can be supported by our busbar trunking systemsallows for both electrodynamic stress and thermal energy dissipated during the fault.The busbars must be able to sustain the short circuit current for the entire durationof the fault - i.e. for the time required for the protective device (circ. breacker) to startoperating, cutting off the metal continuity and extinguishing the electric arc.I b. 100 =0.608 . 80 . 100400 . 10 3 . 100 = 1.22%I b2Three-phase ratingSingle phase ratingP = 3 • R t• I b2• 10 -3 [W/m]P = 2 • R t• I b2• 10 -3 [W/m]TECHNICAL INFORMATION135TECHNICALINFORMATIONLOW-MEDIUM POWER G<strong>EN</strong>ERAL CATALOGUE

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!