Divisione Nucleare<br />

Progetto<br />

Project<br />

PDS-XADS<br />

<strong>AnsaldoEnergia</strong><br />

Identificativo<br />

Document no.<br />

XADS 20 TRIX 009<br />

Rev.<br />

Rev.<br />

1<br />

Cl. ris.<br />

class<br />

Pagina<br />

Page<br />

25<br />

cold leg temperature. The serial arrangement of the Air Coolers allows to fully exploiting<br />

their heat transfer capability, and provides wider control flexibility.<br />

The Air Coolers (see Figure 3.2-10) are provided with motor-operated variable speed fans,<br />

in order to select the desired heat removal rate during each plant operating condition. At low<br />

heat load, the air can flow on natural circulation and the flow rate can be controlled by<br />

means of movable dampers. The air exhausts are then discharged to the external<br />

atmosphere through a battery of stacks.<br />

The Expansion Tank is installed after the ACs upstream of the IHXs. This tank holds the oil<br />

volume fluctuations due to possible operating temperatures fluctuations and oil swelling<br />

from 60°C to 320°C.<br />

The recirculation pump, installed on the hot leg downstream of the IHXs, is sized to deliver<br />

100% of the required loop flow rate. Each pump is connectable to the on-site power<br />

generation bus (Diesel Generator) to be automatically actuated in case of a Loss of Off-Site<br />

Power. Separate power buses, belonging to the Non-Class normally feed 1E AC Power<br />

Systems (NACS the SCS pumps, loop 1 and 2, 1E AC Power Systems (NACS). This<br />

redundancy ensures a defense-in-depth capability against the possibility of a reactor<br />

shutdown.<br />

On high radioactivity signal from one SCS loop the corresponding recirculation pump is<br />

automatically stopped in order to terminate contaminated material recirculation; beside, the<br />

ACs air path is intercepted in order to terminate the natural recirculation. The reactor shall<br />

be shut down and the other available SCS loop shall be used to drive the plant to a<br />

controlled state.<br />

On low RCS temperature signal a total air coolers shutdown is automatically initiated in<br />

order to limit primary coolant temperature decrease, to try to maintain just above the LBE<br />

freezing point.<br />

A safety-relief valve protects the SCS from the potential overpressure caused by secondary<br />

coolant thermal expansion.<br />

Before start up phase’s gas pockets shall be eliminated through adequate vent lines, on the<br />

upper parts of the secondary circuit, connected to the Expansion Tank.<br />

The Expansion Tank and all the main loop piping are thermally insulated. This sections; one<br />

for each SCS loop, include the equipment necessary for filling/draining of each loop. These<br />

sections are also utilized for a continuous feed and bleed to perform the required oil<br />

purification. More specifically an oil drain line is provided to connect each loop to a<br />

dedicated Storage Tank capable of containing all the drainable coolant oil.<br />

DNU 020/1