18.04.2016 Views

isolated current voltage transducers

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Glossary A-Z<br />

Open loop <strong>current</strong> <strong>transducers</strong> (§ 3.1)<br />

Current <strong>transducers</strong> where the output signal is an image of the<br />

magnetic field created by the primary <strong>current</strong> to be measured. It<br />

generally uses a magnetic circuit which focuses the field on a field<br />

sensing element, e.g. made of a Hall generator. The output signal is<br />

a direct amplification of the Hall signal, giving a true image of the<br />

measured <strong>current</strong> if the system is designed for a linear behavior.<br />

Primary<br />

The input, driving or measured side of a circuit and the components<br />

related to that side of the circuit. Galvanic isolation is provided<br />

between the primary and the secondary side. For example, the<br />

primary winding carries the primary <strong>current</strong>. See also Secondary.<br />

PWB (printed wiring board)<br />

Often referred to as a „PCB“ or printed circuit, or PWB depending<br />

on the geographic location.<br />

Ratiometric<br />

The output (offset and/or transfer function) is directly proportional to<br />

the supply or a reference <strong>voltage</strong>. See also Offset and Transfer<br />

function.<br />

Reaction time<br />

The delay between the measured signal reaching 10% of final value<br />

and the output signal reaching 10% of final value. See also<br />

Response time, and Rise time (Figure 8).<br />

Recovery time<br />

The time required to ‘recover’ and resume normal operation after an<br />

event that interrupts operation, such as saturation. Not to be<br />

confused with Settling time.<br />

Remanence<br />

After traversing a hysteresis loop the output will not return to zero<br />

when the input is at zero. The amount remaining at the output is the<br />

remanence and, in essence, creates an additional output offset.<br />

See also Magnetic offset and Hysteresis.<br />

It is minimized by design in LEM <strong>transducers</strong> and is often resulting<br />

from a non-expected primary <strong>current</strong> overload. The magnetic offset<br />

defines the offset on the transducer output signal, positive or<br />

negative depending on the direction of the <strong>current</strong> overload.<br />

Response time<br />

The time difference between the driving signal reaching 90% of its<br />

final value and the measured signal reaching 90% of its final value.<br />

This is a combination of delay time, driving signal rise time, and<br />

measured signal rise time. See also Reaction time and Rise time<br />

(Figure 8).<br />

Rise time<br />

The time difference between a signal reaching 10% and 90% of its<br />

final value. See also Delay time, Reaction time, and Response time<br />

difference (Figure 8).<br />

Saturable inductor<br />

An inductor designed to operate into its saturation region. The<br />

inductance value varies from a high value at low <strong>current</strong>s (based on<br />

the permeability of the core) to a low value at high <strong>current</strong>s (the<br />

core permeability becomes unity when saturated). (Figure 25).<br />

Secondary<br />

The output, driven or measurement side of an <strong>isolated</strong> circuit and<br />

the components related to that side of the circuit. Isolation is<br />

provided between primary and secondary side components. For<br />

example, the secondary supply provides secondary compensation<br />

<strong>current</strong>. See also Primary.<br />

Settling time<br />

The amount of time required to ‘settle’ to within a defined tolerance<br />

after a disturbance, such as dv/dt. Not to be confused with<br />

Recovery time.<br />

Standard Fluxgate<br />

A LEM definition, Standard Fluxgate <strong>transducers</strong> operate on the<br />

closed loop principle and provide the most „standard“ performance<br />

in term of accuracy or bandwidth. Non-standard Fluxgate<br />

<strong>transducers</strong> include the more efficient IT or C-types, or the less<br />

dynamic „low frequency“ Fluxgates. See also C-type, IT-type,<br />

Fluxgate, Low frequency Fluxgate and § 4.<br />

Transfer function<br />

The ratio of output signal to input signal. For example, if a 100A<br />

input creates a 1V output the transfer function is 1V / 100A or 1mV /<br />

100mA. The output of a ratiometric device is dependent on the<br />

supply <strong>voltage</strong>, so VS will be part of the transfer function.<br />

Turns ratio<br />

The ratio of primary turns to secondary turns in a transformer. With<br />

closed loop <strong>current</strong> <strong>transducers</strong>, the turns ratio typically assumes a<br />

single primary turn. For example, 1:1000 implies 1000 secondary<br />

turns and a secondary <strong>current</strong> of 1mA with a single primary turn<br />

carrying 1A.<br />

47

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!