Diagnostic help<br />

Symptoms<br />

No indicators light up on the front<br />

Setting refused by the system<br />

The system does not communicate<br />

Probable causes<br />

Check that voltage is present on the terminals<br />

(C3-C4)<br />

Check setting consistency<br />

(see Table in "Setting the relay" chapter)<br />

Check INTERNAL BUS addressing (see DC150<br />

manual). Check the terminal connections.<br />

Error messages<br />

<strong>5100512174</strong>-<strong>03</strong><br />

Anomalies can be detected by the system automatically. Depending on the case, an<br />

alarm may be tripped. A message appears on the display to indicate the type of<br />

problem detected.<br />

Messages<br />

displayed<br />

"TOR"<br />

"Er0" and "Er1"<br />

"Er2""<br />

"SAT"<br />

Probable causes Consequences Action<br />

A break in the link between a<br />

toroid and the RMH relay has<br />

been detected<br />

A problem has been detected<br />

during a test sequence<br />

A problem has been detected<br />

concerning the connection<br />

between the RMH and the<br />

RM12T<br />

Leakage current greater<br />

than 60 A<br />

Alarm trip<br />

Alarm trip<br />

Alarm trip<br />

None<br />

"Adr" Power-up b no internal bus<br />

connection:<br />

message disappears<br />

after 30 seconds<br />

b internal bus<br />

connection: "Adr"<br />

displayed + number<br />

of the channel to be<br />

addressed<br />

Released for Manufacturing<br />

Printed on 2013/01/09<br />

Check wiring<br />

Contact your<br />

Schneider<br />

branch office<br />

Check the<br />

RM12T wiring<br />

and power<br />

supply.<br />

Addressing<br />

(see DC150<br />

manual)<br />

68/69