23.12.2012 Views

electrical data - Mitsubishi Heavy Industries

electrical data - Mitsubishi Heavy Industries

electrical data - Mitsubishi Heavy Industries

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Range of usage & limitations (SRK208, 288, 388, 458, 408, 561 HENF-A)<br />

(1) Inlet air temperature<br />

(a) Cooling operation (b) Heating operating<br />

Outdoor air temp. ºC D. B.<br />

Note: The chart is the result from the continuous<br />

operation under constant air temperature<br />

conditions, however, excludes the<br />

initial pull-down stage.<br />

(2) Total one way piping length and vertical height difference.<br />

(3) Voltage application<br />

Item<br />

Applicable temp.<br />

range<br />

JIS-Cooling<br />

Indoor air temp. ºC W. B.<br />

Item<br />

Models<br />

All models<br />

Total one way piping length (m) 15<br />

Vertical height Outdoor unit is higher 5<br />

difference (m)<br />

Outdoor unit is lower 5<br />

Models<br />

Indoor air temp. ºC D. B.<br />

All models (except SRK458HENF-W model)<br />

Minimum (V) 198<br />

Maximum (V) 264<br />

SRK458HENF-W (V) Min 187 Max 264<br />

Applicable temp. range<br />

JIS-Heating<br />

Outdoor air temp. ºC W. B.<br />

SRK-H<br />

Note: The chart is the result from the continuous<br />

operation under constant air temperature conditions,<br />

however, excludes the initial pulldown<br />

stage and any possible defrost cycles.<br />

13

Hooray! Your file is uploaded and ready to be published.

Saved successfully!