25.12.2012 Views

Alia BOQ-Combined-Final_18Jun09 - UNDP

Alia BOQ-Combined-Final_18Jun09 - UNDP

Alia BOQ-Combined-Final_18Jun09 - UNDP

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Bill of Quantities<br />

Part 1<br />

Construction of Remaining Area of the Second Floor of the North<br />

Wing at Hebron Hospital<br />

June 2009


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

Section I - Civil Works<br />

1 Preparation Works<br />

The contractor shall visit the proposed site to<br />

familiarize himself with the required scope of work<br />

and the existing site conditions. Unit price shall<br />

include costs of the needed material and the<br />

workmanship which are required to complete the<br />

work. The price shall include costs for making the<br />

necessary temporary works to ensure the safety of<br />

the visitors of the functioning hospital and to<br />

protect the finished works rendered in the existing<br />

hospital. Price shall also include cost of hauling<br />

away the demolished material. The contractor shall<br />

preserve, protect and make the necessary works to<br />

maintain the existing electro-mechanical system to<br />

serve the functioning hospital.<br />

1.1 Carefully demolish the concrete covering steel<br />

reinforcement of the columns starters. The work<br />

includes demolishing portions of concrete<br />

parapets, walls, slabs... etc., and cleaning of steel<br />

rebars with a steel brush to remove any concrete<br />

paste, rust, stains, etc. necessary for making<br />

proper bonding and connections of the existing<br />

structural elements to the new proposed<br />

constructions. All as directed by the engineer and<br />

as shown on the drawings.<br />

1.2 Demolish and remove portion of the existing block<br />

wall between the existing corridor and the new<br />

constructed one as shown on the drawings.<br />

1.3 Dismantle, repair, paint and re-install of staircase<br />

steel door (210cm x 120cm) at the existing roof<br />

level to the roof of the new construction.<br />

1.4 Demolish and haul away the existing sloped light<br />

weight concrete layer on the existing roof<br />

according to the engineer instruction.<br />

Total of Preparation Works carried to summary:<br />

JOB 1<br />

M2 15<br />

JOB 1<br />

M2 450<br />

1


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

2 Concrete Works:<br />

Unit rates of concrete works includes supplying<br />

and casting of a ready mixed concrete. The price<br />

shall include all costs of material and workmanship<br />

for preparing the formwork, shuttering, fixing of<br />

steel reinforcement, vibration, curing making<br />

grooves and sleeves ..etc.<br />

2.1 Supply and cast concrete B300 for columns of<br />

various cross sections .<br />

2.2 Supply & cast concrete B300 for 46cm thick<br />

ribbed slabs, price includes cost of the required<br />

light weight polyester blocks "ETOLITE", and drop<br />

beams as shown on drawings.<br />

M3 27<br />

M2 235<br />

2.3 Ditto, but for 56cm thick ribbed slabs. M2 220<br />

2.4 Supply and cast of B300 for staircase flights,<br />

landings and steps .<br />

2.5 Supply and cast concrete B300 for walls 20-35cm<br />

thick.<br />

M3 9<br />

M3 17<br />

2.6 Supply and cast concrete B300 for roof parapet. M3 20<br />

2.7 Supply and cast concrete B300 for suspended<br />

solid slabs of various thickness<br />

2.8 Supply and cast concrete B300 for machine<br />

foundations including vibration insulation rubber<br />

pads... etc, as approved by the engineer.<br />

2.9 Supply of deformed high yield steel rebar<br />

reinforcement of various diameters, characteristic<br />

strength FY=4200kg/cm2 for concrete<br />

reinforcement, as shown on drawings and<br />

according to specifications. The steel<br />

reinforcement should be stored in a proper location<br />

on site as instructed by the engineer.<br />

Total of Concrete Works carried to civil<br />

summary:<br />

M3 5<br />

M3 1<br />

TON 28<br />

2


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

3 Block Works:<br />

Supply and construct hollow concrete block walls<br />

using cement and sand mortar (1:4) . The price<br />

includes cost of cutting, bonding, control and<br />

expansion joints, vertical concrete bond beams to<br />

columns or walls including steel reinforcement (of<br />

4 steel bars 12mm dia and 8mm stirrups@ 20cm<br />

c/c). All as shown on the drawings, the<br />

specifications and as directed by the engineer.<br />

3.1 Ditto, for constructing 10cm hollow concrete block<br />

walls<br />

M2 650<br />

3.2 Ditto, but 15 cm hollow concrete block . M2 220<br />

3.3 Ditto, but 20 cm hollow concrete block . M2 310<br />

3.4 Casting horizontal B300 concrete lintels or girdles<br />

above block works 20 or 10 cm thick. The price<br />

shall include the cost of steel reinforcement of<br />

4steel bars 12mm dia and 8mm stirrups@ 20cm<br />

c/c. All in accordance with the engineer's<br />

instructions, all as shown on the drawings.<br />

Total of Block Works Carried to Summary:<br />

M3 10<br />

3


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

4 Sealing Works:<br />

4.1 Supply and cast light weight sloping foam concrete<br />

layer, of density 1400kg/M3and compressive<br />

strength of 40kg/cm2, on the roof having<br />

minimum thickness of 5cm and to the required<br />

slope. Unit rate includes performing 2 cm cement<br />

screed layer and 12x12 cm cement fillet at the<br />

parapet above the light weight concrete layer to<br />

receive the water proofing membrane.<br />

4.2 Supply and install one layer of water proofing<br />

membrane 5mm thick, covered with white gravel,<br />

"Pazkar"or equally approved. The unit price shall<br />

include cost of a prime coat GS474 at a rate of<br />

0.25 kg /m2 including all the necessary material<br />

and workmanship, as specified.<br />

4.3 Supply and install sealant cover at groove" NP1 or<br />

equally approved" at roof parapet, as shown in<br />

drawings.<br />

4.4 Supply and apply three coats of hot asphalt layers<br />

(25/75) at rate of 500g/m2 for each layer,<br />

reinforced by two layers of fiberglass, and a prime<br />

coat GS474. All according to the manufacturer<br />

instructions and to the engineer's approval.<br />

4.5 Insulation of exterior walls with two layers of<br />

BONZAL sealant or equally approved. The price<br />

also include preparing the surface and applying<br />

one layer of cement and sand(2:1) plaster to<br />

receive the sealant coat.<br />

4.6 Thermal insulation of exterior walls with high<br />

density extruded polystyrene boards RANDOPAN<br />

or equally approved, 3cm thick<br />

4.7 Circular strip with foamed rubber and caulking with<br />

elastic compound for vertical and horizontal seams<br />

.<br />

4.8 Supply and install aluminum clip strip for covering<br />

vertical and horizontal expansion joints .<br />

4.9 Supply and install 2 cm extruded polystyrene for<br />

expansion joints (24 kg/m3).<br />

Total of Water Proofing carried to summary:<br />

M2 480<br />

M2 540<br />

MR 90<br />

M2 80<br />

M2 340<br />

M2 340<br />

MR 30<br />

MR 13<br />

M2 85<br />

4


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

5 Carpentry and Metal Works:<br />

All door frames of the required widths (metal or<br />

wood) shall be of formed galvanized sheet metal<br />

2mm thick. The frames shall be held in place with<br />

standard concrete filling. Door frames shall be<br />

painted using a prime coat brown unseal ZN, under<br />

coat, and the finishing coat.<br />

Wooden door leaf shall be 45mm thick with 70%<br />

fill, plywood facing on each side shall be 6mm<br />

thick, the door panels frames shall be of hard wood<br />

45*100mm.The doors shall be coated with "PVC"<br />

on both sides similar to the existing doors on the<br />

same floor or oil-based paint. Price shall include<br />

cost of the protection plates, hinges, closing<br />

mechanism, door stops, and all needed<br />

accessories. All as per drawings and the<br />

specifications.<br />

Supply and install heavy duty hinges (three 4"<br />

hinges for each door), locks and cylinders are<br />

"Yardini" or equally approved. Doors shall have 3<br />

original sub-master keys and 2 general master<br />

keys.<br />

Door handles shall be steel handles similar to<br />

those installed on the existing doors at the same<br />

floor or as approved by the engineer<br />

The "pvc" shall be 2mm thick "Tarkett Commercial<br />

" # 227 NCS 4010- B90G or equivalent applied on<br />

both sides of door panels.<br />

The thickness of the sheet metal of the fire doors<br />

shall be 1.5mm insulated with rock wool 50mm<br />

thick and density of 80-90kg/m3. The door shall<br />

include the emergency door-opening handle,<br />

fireproof locks, and hydraulic door closers made in<br />

Germany.<br />

All wooden door panels shall be furnish by oak<br />

wood frames and should be painted with 3 coats of<br />

lacquer paint.<br />

All wooden and metal door panels shall be painted<br />

with 2 coats of butty, one coat of under coat and 3<br />

coats of oil base paint.<br />

All exposed edges, louvers and door frames are<br />

oak wood and should be painted with 3 coats of<br />

lacquer paint.<br />

Rate for smoke proof doors include 100% filling,<br />

sealing strips around door panel including bottom<br />

of panel.<br />

5


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

5.1 A-Carpentry<br />

Fabricate supply and install the following wooden<br />

doors complete with all necessary fixing<br />

accessories, glazing, hinges, louvers, grills,<br />

hydraulic closures, hardware and ironmongery. All<br />

in accordance with the drawings and<br />

specifications.<br />

5.1.1 Single sealed door with fixed wooden slats<br />

120x210 cm, type N-24<br />

UNIT 12<br />

5.1.2 Single sealed door 90x210 cm, type N-45 in the list UNIT 1<br />

5.1.3 Ditto, but with a wooden louver UNIT 3<br />

5.1.4 Wooden single door 80x210 cm, type N-62in the<br />

list<br />

5.1.5 Single door + window 80x210 cm, type N-63 in the<br />

list<br />

UNIT 1<br />

UNIT 11<br />

5.1.6 Four doors closet 240x200x40 cm, type N-85 UNIT 1<br />

5.2 B. Metal Works<br />

5.2.1 Ladder anchored to the wall, type M-21 in the list UNIT 1<br />

5.2.2 Metal door , 200x40cm bent sheet 2mm thick, M-<br />

26<br />

UNIT 1<br />

5.2.3 Sheet metal door 35X200 cm type M-27 in the list UNIT 6<br />

5.2.4 Fabricate, supply and install steel cover for the<br />

main mechanical shaft at existing roof, covered<br />

with corrugated white color galvanized sheets of<br />

0.06 mm thick as per the drawings and Engineer<br />

instructions. Price to include preparing the shop<br />

drawings for approval and painting the steel of<br />

three coats of oil paint on one coat of primer.<br />

5.2.5 Fabricate, supply and install steel Fire Escape<br />

Stairs. The price shall include preparing the shop<br />

drawings for approval, steel handrail for the stairs,<br />

painting works, fastening the stairs at both ends,<br />

civil works and foundations, and all other works<br />

that might be needed as per the drawings and the<br />

Engineer instruction.<br />

5.2.6 Supply and install a staircase steel door (210cm x<br />

120cm) similar to the door installed at the existing<br />

roof level.<br />

Total of Carpentry and metal works….. carried<br />

to summary:<br />

Job 1<br />

Job 1<br />

No. 1<br />

6


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

6 Stainless Steel Works<br />

6.1 Sink and work area ,255 /60/90cm, type M-51 in<br />

the list<br />

6.2 Sink and work area ,215 /60/90cm ,type M-53* in<br />

the list<br />

UNIT 1<br />

UNIT 1<br />

6.3 Sink and work area 302/60cm ,type M-61*in the list UNIT 1<br />

6.4 Handholds for toilets for invalids, 270 cm long type<br />

M-64 in the list<br />

UNIT 28<br />

6.5 Support handles in toilets, type M-65 in the list UNIT 10<br />

6.6 Corner guard for the walls, to height 210cm ,type<br />

M-68 in the list<br />

6.7 Corner guard for the walls, 10-25cm thick, type M-<br />

69 in the list<br />

Total of Stainless Steel works….. carried to<br />

summary:<br />

7 Plastering Works:<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses<br />

of all requirements stipulated in the preambles,<br />

drawings and technical specification of the<br />

contract.<br />

7.1 Three layers of internal plastering for ceiling, walls,<br />

columns, drop beams..ets composed of a bond<br />

coat, base coat 1:4, and finish coat 1:5 as<br />

specified.<br />

7.2 External plastering for parapet, walls and wherever<br />

needed composed of 3 coats a bond coat 1:1,<br />

base coat 1:4 and finish coat 1:2 with waterproof<br />

liquid all as specified.<br />

7.3 One layer of cement plastering (Glanse) to ceiling<br />

and wall above suspended ceiling level and where<br />

ever instructed by the Engineer.<br />

Total of Plastering Works carried to Summary:<br />

UNIT 35<br />

UNIT 2<br />

M2 1320<br />

M2 90<br />

M2 400<br />

7


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

8 Flooring and Covering Works:<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses<br />

of all requirements stipulated in the preambles,<br />

drawings and technical specification of the<br />

contract.<br />

8.1 Supply and install 30x30cm terrazzo tiles similar to<br />

the floor tiles at the 2nd floor. Rate includes the<br />

supply and installation of 3 cm mortar, cement<br />

sand fill blew tiles, grouting as made by Mrfix or<br />

equally approved and polishing all in accordance<br />

with the specifications and applicable Standards.<br />

M2 290<br />

8.2 Ditto but 30 x 10 x 1 cm terrazzo tiles skirting. MR 260<br />

8.3 Supply and install 3 cm local marble (Abo<br />

alkhabaz) or equally approved thresholds 15-25<br />

cm wide, including aluminum strips<br />

8.4 Supply and install 20x20x0.8cm ceramic tile class<br />

(A) "Negev" model 9001 similar to the tile installed<br />

in existing part of the same floor. The tiles shall be<br />

laid and fixed to the walls by Mr fix bonding agents<br />

or equally approved, as specified. Price includes<br />

cost of surface preparation to receive tiles, which<br />

shall include two coats of cement plaster (scratch<br />

and float coat) and the approved adhesive<br />

materials and grouting.<br />

8.5 Ditto but installation (no supply) of green color<br />

ceramic tiles (20x20x0.8cm).<br />

8.6 Supply and install non-slip 20x20*.8cm ceramic<br />

tiles, "Negev" or equivalent class (A) for bathrooms<br />

flooring, as specified and approved by the<br />

Engineer. The price includes the mortar (1:3) the<br />

sand cement fill. The color of the tiles shall be as<br />

chosen by the Engineer.<br />

8.7 Installation of the granite porcelain tiles<br />

(30x30*.8cm), for flooring. The price to include the<br />

mortar (1:3)and the sand cement fill. (materials<br />

are available in Hospital storage)<br />

8.8 Supply and install 3cm thick local marble<br />

"Sourmaen" for stair threads 155*34*3 cm polished<br />

one face & edge . The threads should be bedded<br />

on 3cm mortar (1:3). The rate also includes cost of<br />

risers 155*13.66*2 cm and the water stop at each<br />

thread and where required<br />

8.9 Ditto but,10cm high,1cm thick for stair case skirting<br />

(triangle).<br />

M.R 22<br />

M2 470<br />

M2 17<br />

M2 40<br />

M2 115<br />

No 24<br />

MR 12<br />

8.10 Supply and install stainless steel toilet paper<br />

holders, mounted on the wall.<br />

UNIT 40<br />

8.11 Ditto but soap dishes . UNIT 40<br />

8.12 Liquid soap dispenser, model Visio soap AM or<br />

equivalent.<br />

UNIT 20<br />

8.13 Crystal mirrors, 60/45 cm. 4mm thick. UNIT 50<br />

8.14 Total of Flooring and Covering Works carried to<br />

Summary:<br />

8


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

9 Painting Works:<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses<br />

of all requirements stipulated in the preambles,<br />

drawings and technical specification of the<br />

contract.<br />

The contractor should allow in his pricing that the<br />

engineer will use as many different colors or<br />

combination of colors to meet an approved color<br />

scheme.<br />

All painting material shall be made by Tambour or<br />

equally approved<br />

9.1 Supply and apply policed paint for plastered walls<br />

and ceiling composed of one coat of primer fill<br />

and three coats of policed.<br />

9.2 Supply and apply emulsion paint for plastered<br />

walls composed of one coat of primer fill two coats<br />

putty and 3 coats of emulsion.<br />

9.3 Supply and apply oil paint for plastered walls<br />

areas composed of primer fill , two coats of putty<br />

,one coat of under coat and 3 coats of " Polyour".<br />

9.4 Painting of wall with "Acrinol" for mildew and<br />

fungus protector<br />

9.5 Painting of interior walls with a fine texture coating<br />

Tamburtext or equivalent.<br />

9.6 Painting of bare exterior concrete with Temglass,<br />

price includes preparation of the surface .<br />

Total of Painting Works carried to Summary:<br />

M2 320<br />

M2 30<br />

M2 1000<br />

M2 50<br />

M2 230<br />

M2 85<br />

9


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

10 Aluminum Works:<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses<br />

of all requirements stipulated in the preambles,<br />

drawings and technical specification of the<br />

contract.<br />

Fabricate supply and install the following<br />

aluminum doors & windows complete with<br />

vacuumed double glazing, silicone, handles and<br />

locks , all as shown in drawings and the<br />

specifications. The type, grade and colors shall<br />

match those installed in the existing part of the<br />

same floor. Shop drawings must be submitted by<br />

the contractor for the Engineer's approval. All<br />

windows and doors profiles shall be "Gonzales"<br />

product or equally approved. The unit rate shall<br />

include cost of the roller and Aluminum shutters as<br />

shown on drawings and specifications.<br />

All aluminum windows shall be 2 1/2 tracks for<br />

horizontal and vertical partitions, with screen mesh,<br />

glazing, weather strips shall be Neoprene or<br />

EPDM.<br />

10.1 Two-pane sliding window, 180/104 cm, type 20-AL<br />

in the list<br />

10.2 Window with lower part fixed, including roller<br />

shade, 180/156cm type 33AL<br />

10.3 Rail for curtain around hospital bed, 180 + 240 cm<br />

long, type 50-AL in the list.<br />

10.4 Aluminum fixed window 60x338 cm divided into<br />

four equally parts with 6mm antisun glass, type<br />

61AL in the list<br />

10.5 Screen mesh 90x90 cm for existing windows at<br />

same floor.<br />

10.6 Screen mesh 60x90 cm for existing windows at<br />

same floor.<br />

Total of Aluminum works carried to summary:<br />

UNIT 7<br />

UNIT 8<br />

UNIT 82<br />

UNIT 1<br />

UNIT 41<br />

UNIT 6<br />

10


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

11 Stone Works:<br />

The contractor shall, when pricing this bill, take into<br />

consideration the costs and expenses of all<br />

requirements stipulated in the preambles,<br />

drawings, details, and technical specification of the<br />

contract.<br />

11.1 Supply and install 5 cm thick 25 cm wide Taltish<br />

stone courses, first quality KHALET ENJASSA<br />

similar to the existing at the Northern Wing, as<br />

shown on drawings. The price also includes 15 cm<br />

thick B200 concrete backing and #8 mm steel<br />

mesh and anchoring as shown on drawings. Unit<br />

price shall also include cost of corner stones, stone<br />

grouting and pointing with white cement.<br />

11.2 Window sills of stone panels (Matabeh) 43 cm<br />

wide 8cm thick as shown on drawings.<br />

M2 300<br />

MR 30<br />

11.3 Ditto, but 38 cm wide. MR 2<br />

11.4 Window jamb with stone panels (Matabeh) 30 cm<br />

wide, 5cm thick.<br />

MR 45<br />

11.5 Ditto, but 25 cm wide. MR 8<br />

11.6 Window lintels with stone panels 30 cm wide, 5cm<br />

thick.<br />

11.7 Window lintel with stone panels 25 cm wide, 5cm<br />

thick.<br />

11.8 45cm wide stone coping 6cm thick, "mesamsem"<br />

finish<br />

Total of Stone Works carried to civil summary:<br />

MR 30<br />

MR 2<br />

MR 95<br />

11


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

12 Suspended ceiling:<br />

The contractor shall, when pricing this bill, take into<br />

consideration the costs or expenses of all<br />

requirements stipulated in the preambles,<br />

drawings and technical specification of the<br />

contract.<br />

12.1 Supply and install non perforated acoustical<br />

ceiling made of formed galvanized sheet metal<br />

trays for bathrooms and wet areas. The metal tray<br />

should be of 0.8 mm thick 45 mm high painted<br />

with polyester epoxy paint<br />

12.2 Ditto, but perforated sheets with perforation<br />

diameter 3.0mm (11% perforation). The trays<br />

should be covered with continuous and uniform<br />

manner of rock wool mats 25 mm thick of<br />

25kg/m3 density. The rock wool mats shall be<br />

wrapped by inflammable polyethylene sacks, (in<br />

accordance with the Safety Regulations and<br />

Standard).<br />

12.3 Ditto, but 60*60cm squared perforated sheets trays<br />

with perforation diameter 1.5mm (22% perforation)<br />

covered with approved acoustic material,(soundex)<br />

or equally approved<br />

12.4 Supply and install vertical & horizontal gypsum<br />

boards 12mm thick for decorative ceilings and<br />

where required.<br />

12.5 Galvanized sheet metal trays 0.6 mm thick for<br />

closing vertical walls.<br />

Total of Suspended Ceiling Works carried to<br />

Summary:<br />

M2 40<br />

M2 150<br />

M2 15<br />

M2 25<br />

M2 17<br />

12


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

13 Fixed Furniture:<br />

Fabricate, supply and install the following units, as<br />

in drawings with all fixing accessories, drawers,<br />

shelves, hardware, and iron monger with a master<br />

key .All furniture shall be made of plywood and<br />

carpenters' board 20mm maid by Etz<br />

Lavood,Sepen or equal. All edges shall be<br />

protected by oak wood strip, all in accordance with<br />

the drawings and specifications.<br />

13.1 Maternity nurses' counter, dimensions of<br />

300/60/110 cm, type N107<br />

13.2 Bottom closet with stainless steel surface + upper<br />

closet, with general dimension of<br />

255/35/60cm+255/58/90 cm, type N109 in the list.<br />

13.3 Bottom closet with stainless steel surface + upper<br />

closet, with general dimension of<br />

300/35/60cm+300/58/90cm, type N119 in the list.<br />

13.4 Bottom closet with stainless steel surface + upper<br />

closet, with general dimension of 210/35/60<br />

cm+210/58/90 cm, type N122 in the list.<br />

UNIT 1<br />

UNIT 1<br />

UNIT 1<br />

UNIT 1<br />

13.5 Storage cabinet 180/55/260 type N -124 UNIT 2<br />

13.6 Storage cabinet, 90/60/180 cm, type N128 in the<br />

list.<br />

13.7 four-door closet, 220/60/180 cm, type N130 in the<br />

list.<br />

13.8 Storage cabinet , 110/55/180 cm, type N129 in the<br />

list.<br />

13.9 Wall guard wooden 25x3 cm with 20 cm PVC 2<br />

mm thick similar to the existing wall guard at the<br />

same floor.<br />

13.10 Fabricate supply and install staircase handrail<br />

including fixing accessories, matching the existing<br />

handrail and as shown on the drawings. The rate<br />

includes surface preparation, 2 coats anti rust<br />

primer "Tambour synthetic and three coats of<br />

Tambour superlac.<br />

13.11 Wall Signs:<br />

Supply & install Aluminum wall signs (plaques) with<br />

writing in Arabic and English with a special solventproof,<br />

weather and temperature resistant fixed on<br />

the door or the wall. The price include labor work<br />

and all fixing materials.<br />

UNIT 3<br />

UNIT 1<br />

UNIT 1<br />

MR 250<br />

MR 15<br />

13.11.1 Size 25x12 cm NO 25<br />

13.11.2 Size 40x15 cm NO 5<br />

Total of Fixed Furniture carried to Summary:<br />

13


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

Section II - Mechanical Works<br />

14 Cold and Hot Water Supply System:<br />

14.1 Supply and install "Schedule 40" galvanized 1/2"<br />

pipe running along exposed or are within partitions<br />

and are fastened to the building, (or penetrate<br />

them) like ceilings, walls, bottom of suspended<br />

floors, partitions, columns, ducts, tunnels, special<br />

horizontal shats for pipes. The price includes all<br />

fasteners, supports, brackets, arches, bends,<br />

elbows, sleeves, branches, unions, all other<br />

required fittings and valves, connection with<br />

existing system, and testing. The pipes are joined<br />

by threaded joints. All done according to<br />

specifications, drawings and the approval of the<br />

Engineer.<br />

M.R 80<br />

14.2 Ditto, for 3/4" pipe. M.R 90<br />

14.3 Ditto, for 1" pipe. M.R 100<br />

14.4 Ditto, for 1.25 pipe. M.R 40<br />

14.5 Ditto, for 1.5 pipe. M.R 40<br />

14.6 Ditto, for 2" pipe. M.R 160<br />

14.7 Ditto, for 3" pipe. M.R 20<br />

14.8 Ditto, for 4"pipe. M.R 6<br />

14.9 Supply and install hot water pipe insulation as per<br />

Vidoflex or equal, 13mm thick, for 1/2" dia pipe.<br />

M.R 40<br />

14.10 Ditto, for 3/4" pipe. M.R 50<br />

14.11 Ditto, for 1" pipe. M.R 40<br />

14.12 Supply and install insulation for exposed hot water<br />

1/2" pipe, with "Vidoflex" sleeves or equally<br />

approved, 13 mm thick, wrapped with plastic tape<br />

and secured with sheet metal strip and tagged for<br />

identification. Price includes insulation of bends,<br />

branches, valves , etc.<br />

M.R 70<br />

14.13 Ditto, for 3/4" pipe. M.R 70<br />

14.14 Ditto, for 1" pipe. M.R 40<br />

14.15 Ditto, for 1.25 pipe. M.R 40<br />

14.16 Ditto, for 1.5 pipe. M.R 30<br />

14.17 Supply and install insulation for exposed hot water<br />

2" pipe, with "Vidoflex" sleeves or equally<br />

approved, 19 mm thick, wrapped with plastic tape<br />

and secured with sheathed with sheet metal strip.<br />

Price includes insulation of bends, branches,... etc.<br />

M.R 20<br />

14.18 Ditto, for 3" pipe M.R 20<br />

14.19 Supply and install pex pipe 16mm with sleeve<br />

25mm by "Aquapex" or equivalent .The price shall<br />

include all copper fittings like elbows inside walls<br />

1/2", male and female adaptors, hangers, all<br />

needed accessories for connection between<br />

copper collectors to the point. All done according<br />

to specifications, drawings and the approval of the<br />

Engineer.<br />

M.R 750<br />

14


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

14.20 Supply and install hot and cold water collectors<br />

3/4" type "Giacomini" or equivalent. Collectors are<br />

installed in the ceiling of bathrooms with all<br />

required hangers and accessories. The price<br />

should include all main valves, sub valves, vents,<br />

and all accessories<br />

EYE 15<br />

14.21 Ditto , but 1" collectors. EYE 80<br />

14.22 Supply and install bronze gate valve made by<br />

"Giacomini" or equivalent, of the following size:<br />

14.23 Ditto, 3/4" valve. UNIT 3<br />

14.24 Ditto, 1" valve. UNIT 4<br />

14.25 Ditto, 11/4"valve. UNIT 4<br />

14.26 Ditto, 1 1/2" valve. UNIT 4<br />

14.27 Ditto, 2" valve. UNIT 4<br />

14.28 Supply and install resilient butterfly type valve 3"<br />

rilsan coated and lever operated, made by<br />

"Hakohav" or equal, with flanges and counter<br />

flanges.<br />

UNIT 4<br />

14.29 Ditto, 4" valve. UNIT 2<br />

14.30 Supply and install a hose cabinet reel for fire<br />

extinguisher hose. Reel base, made of metal<br />

which can be rotated on a central shaft, on which a<br />

3/4" rubber or plastic hose 25 m long is wrapped,<br />

provided with a multi-purpose nozzle with quickopening<br />

valve, all to the approval of the Engineer<br />

and local fire department.<br />

14.31 Supply and install Fire hydrant landing valve 2"-<br />

2.5" with "Schturz" couplings for rapid hookup of<br />

fabric hose approved by Fire Service.<br />

14.32 Supply and install terilyne hose of superior quality,<br />

2" dia. X 25 m long, with multipurpose nozzle.<br />

"Schturz" couplings at both hose ends. The hose<br />

will be rolled up, tied and stored in fire fighting<br />

cabinet (price does not include cabinets).<br />

ASSY 1<br />

UNIT 1<br />

UNIT 2<br />

14.33 Supply and install 6 kg fire extinguisher. UNIT 1<br />

14.34 Supply and install sheet metal cabinet 1.5 mm<br />

thick with 80X110 cm size, oven backed paint to<br />

freely accommodate all materials described under<br />

item 14.9. The cabinet shall be painted in red and<br />

identified as "Fire Fighting Cabinet".<br />

UNIT 1<br />

14.35 Supply and install eccentric silent flush valve, by<br />

Shell or equivalent. Price includes shutoff valve,<br />

flush pipe, rubber shoe. Shutoff valve, flush pipe<br />

and brass disks to be chrome plated for suspended<br />

toilet bowl. All done as per specifications, drawings<br />

and the approval of the Engineer.<br />

14.36 Supply and install 1/2"chrome-plated hot and cold<br />

water faucet battery "Ideal Standard Slim line<br />

Model no. A5390" or equivalent, Battery of type<br />

installed on walls.<br />

UNIT 15<br />

UNIT 15<br />

14.37 Ditto, model no. A 5398 or equivalent. UNIT 4<br />

15


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

14.38 Supply and install shower Mixer unit Ideal<br />

Standard Slim line Model no. A 5394 or equivalent<br />

.<br />

14.39 Supply and install 1/2" angle valve "Giacomini" or<br />

equivalent.<br />

14.40 Supply and install Hand Spray type Grohi or<br />

equivalent and hose made by or equivalent.<br />

14.41 Supply and install Expansion connectors for water,<br />

with 0.5"- 2" tapped joints, for expansion to 30 mm,<br />

made by "Tozen'' or equivalent.<br />

UNIT 13<br />

UNIT 15<br />

UNIT 15<br />

UNIT 5<br />

14.42 Supply and install 3/4"-11/2" non-return valve. UNIT 2<br />

14.43 2" non-return valve. UNIT 3<br />

14.44 Supply and install 3/4" vent valve, made by<br />

"Giacomini" or equal.<br />

UNIT 10<br />

14.45 Ditto, but 1". UNIT 4<br />

14.46 Supply and install 3/4" - 2" safety valve. UNIT 1<br />

14.47 Supply and Install and test Domestic Pressure<br />

Booster system (Factory assembeled and<br />

Approved type "WILLO/Germany or equivalent<br />

"consisting of 2 pumps one operating and the other<br />

stand by Single stage pump with water flow of<br />

20m3/hr and 40 meter head,3 sealed Pressure<br />

Vessel with capacity of 1000 liter<br />

each,collectors,Strainers,Non return valve,Valves,2<br />

Pressure stat type "Danfuss" or equivalent,<br />

electrical control panel. the price include untivibrators<br />

base ,spring shock absorbers for each<br />

pump, all electrical and mechanical switches, wires<br />

and cables and connections needed for full<br />

installation<br />

Total of Cold and Hot Water Supply….carried to<br />

summary:<br />

JOB 1<br />

16


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

15 Wastewater and Drainage Systems:<br />

15.1 Supply and install UPVC pipes made by Al-Hilal /<br />

Egypt of size 1/14" for waste water, air<br />

conditioning drainage, and standpipes. Pipes run<br />

exposed and are fastened to walls, partitions,<br />

ceilings, shafts, suspended floors, or pipes laid<br />

within walls and under floors, Price includes all<br />

fittings, supports and fasteners, corrosion<br />

protection and 5 cm mortar over pipes under floors,<br />

connection with floor drains.<br />

M 130<br />

15.2 Ditto, but 1 1/2" dia. M 100<br />

15.3 Ditto, but 2 " dia. M 65<br />

15.2 Supply and install 4" UPVC pipe by Al-Hilal-Egypt<br />

or equivalent , running exposed along partition,<br />

false ceilings, walls, shafts, floor bottoms or laid in<br />

walls. Price includes all kind of fittings(by Al-Hilal-<br />

Egypt),supports, testing,5cm concrete layer over<br />

pipes under floors. The price should include all<br />

digging work in concrete walls and floors needed<br />

to connect with existing pipes.<br />

M 250<br />

15.3 Supply and install 4"/2" UPVC floor trap with<br />

chrome threads mesh cover 20*20cm, as per Rit or<br />

equivalent.<br />

UNIT 15<br />

15.4 Ditto but 4"/4" UPVC floor trap. UNIT 15<br />

15.5 Supply and install 4" UPVC inspection chamber<br />

with several inlets, with threaded removable<br />

hermetically closed cover of chrome 20*20cm.<br />

UNIT 3<br />

15.6 Ditto 4" clean out . UNIT 18<br />

15.7 Supply and install UPVC vent cap for 4" vent pipes. UNIT 15<br />

15.8 Supply and install 2" sink trap made of PVC by " Al-<br />

Hilal-Egypt" or equivalent.<br />

Total of Waste and Drainage Systems…carried<br />

to summary:<br />

UNIT 4<br />

17


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

16 Sanitary fixture and their Accessories:<br />

16.1 Supply and install white ceramic wash basin made<br />

by Ideal Standard SanRemo model no. E7460 or<br />

equivalent, and semi pedestal SanRemo E7492 or<br />

equivalent, installed on wall and resting on<br />

brackets.<br />

16.2 Ditto, Ideal Standard SanRemo model no. E7450<br />

or Equivalent, and semi pedestal SanRemo E7492<br />

or equivalent.<br />

assy 7<br />

assy 7<br />

16.3 Supply and install chrome-plated brass towel rack. assy 14<br />

16.4 Supply and install suspended wall hung toilet bowl<br />

by SANREMO from IS Model no. G6481 or<br />

equivalent, including PVC without cover by Ideal<br />

Standard or equivalent , all accessories, and<br />

required wall preparation.<br />

16.5 Supply and install suspended white ceramic slop<br />

sink, by" Ideal Standard" Douro model no. R3806<br />

or equivalent, and stainless steel grill type Douro<br />

model no. R6378 or equivalent, with chrom-plated<br />

fastening screws, strainer, plastic shoe.<br />

16.6 Supply and install dish washing sink type 35006 by<br />

"Twyfords", "Macintosh" or equivalent, including<br />

trap, connection to hot and cold water, mixer type<br />

Ideal Standard Slimline model no. A5396 or<br />

equivalent, including special wall consoles.<br />

16.7 Supply and install refrigerated water fountain,<br />

made by Frigeria / Italy or equivalent, of 40 liter/hr<br />

capacity, with chrom-plated push- button water<br />

faucet, compressor for cooling the water and<br />

appropriate motor rotating at 1450 rpm, a 4 liter<br />

water reservoir, connection works to water supply<br />

and connection to waste water.<br />

Total of Sanitary Fixtures and…carried to<br />

summary:<br />

assy 14<br />

assy 1<br />

assy 3<br />

assy 1<br />

18


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

17 Rainwater Drain Pipes:<br />

17.1 Supply and install high quality 4" dia. G.I. grade<br />

"B" rainwater thread jointed pipes in columns or<br />

walls. The price should include all digging works<br />

needed to connect with existing pipes, all types of<br />

fittings(elbow,T…etc)and galvanized plugs to close<br />

the existing opening.<br />

17.2 Supply and install metal rain water outlets dim. 4"<br />

with domical grade on roof with flange size 380mm<br />

by "Zurn,harmer",or equivalent.<br />

Total of Rainwater Drain Pipes…..carried to<br />

summary:<br />

18 Air Conditioning Works:<br />

18.1 Supply and install galvanized sheet metal air duct,<br />

as described, and to SMACNA standard. The price<br />

should include all wooden sleeves, all required<br />

hanger,supports,flexible connection<br />

near(AHU'S,fancoils), fire and volume dampers,<br />

and all required accessories. Price to include 1"<br />

thick fire insulation of 24 kg/m3 as per<br />

specifications.<br />

18.2 Supply and install sch-40 black steel pipe1/2" with<br />

insulation("Anabid" sleeves 19mm thick wrapped<br />

with plastic fabric secured with sheet metal<br />

strap),threaded jointing, running along or are within<br />

partition or ducts. The price includes all fasteners,<br />

supports and hanging parts as per specifications,<br />

drawings and the approval of the Engineer.<br />

M 30<br />

UNIT 4<br />

M2 200<br />

M 70<br />

18.3 Ditto but 3/4." M 75<br />

18.4 Ditto but 1". M 30<br />

18.5 Ditto but 11/4". M 45<br />

18.6 Ditto but 11/2". M 80<br />

18.7 Ditto but 2". M 690<br />

18.8 Ditto but 21/2", Jointing by welding, insulation thick<br />

25mm<br />

M 20<br />

18.9 Ditto but 3." M 150<br />

18.10 Ditto but 4". M 10<br />

18.11 Ditto but 5". M 10<br />

18.12 Ditto but 6." M 12<br />

19


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

18.13 Supply and install Galvanized sheet metal<br />

protection 0.7mm, on insulated piping and fittings<br />

of various diameters.<br />

18.14 Supply and install flexible Connection for various<br />

pipe diameters(4"-6") by "Tozen" or equal.<br />

18.15 Supply and install bronze gate valve 1" by" Crane"<br />

or equal.<br />

M 650<br />

UNIT 4<br />

UNIT 2<br />

18.16 Ditto, but 11/4". UNIT 2<br />

18.17 Ditto, but 11/2". UNIT 4<br />

18.18 Ditto, but 2". UNIT 10<br />

18.19 Ditto, but 5". UNIT 2<br />

18.20 Supply and install butterfly valve 3" with flange and<br />

opposed flange by" Hakohav" or equal.<br />

UNIT 2<br />

18.21 Ditto, but 4". UNIT 5<br />

18.22 Ditto, but 5". UNIT 2<br />

18.23 Ditto, but 6". UNIT 2<br />

18.24 Supply and install regulating bronze globe valve 2"<br />

by "Crane" or equal.<br />

UNIT 2<br />

18.25 Ditto, but 4" . UNIT 2<br />

18.26 Ditto, but 5". UNIT 2<br />

18.27 Supply and install 3- way modulating valve 1" ,<br />

including sensor, transmitter and actuator(24V)<br />

and thermostat( on -off ,3 speeds) by "Landys &<br />

Gear" or equivalent complete with all electrical<br />

works needed(material, labor).<br />

18.28 Supply and install non-return valve, 3" dia., spring<br />

loaded solid disc, by "Hakohav" or equivalent with<br />

flanges and counter- flanges, and all required<br />

fittings.<br />

UNIT 3<br />

UNIT 2<br />

18.29 Ditto, but 2" ,threaded. UNIT 2<br />

18.30 Supply and install Pressure regulating valve for 2". UNIT 2<br />

18.31 Ditto, but for 3". UNIT 2<br />

18.32 Supply and install thermometer 4" on water pipe ,<br />

by "Kobold" or equal including ball valve 1/2"for<br />

mounting and all preparation work.<br />

UNIT 4<br />

18.33 Ditto but pressure gauge. UNIT 10<br />

18.34 Supply and install Water filter, 6" dia. "Hakohav" or<br />

equal with flanges and counter-flanges.<br />

UNIT 1<br />

18.35 Ditto, but 4". UNIT 1<br />

18.36 Ditto, but 2" . Crane UNIT 2<br />

18.37 Supply and install cold forged Aluminum 4-way<br />

ceiling diffuser 6"*6" with volume damper, by<br />

"Cooling Industries" or equally equivalent.<br />

UNIT 4<br />

18.38 Ditto, but 12"*12". UNIT 8<br />

20


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

18.39 Supply and install return grill, exhaust grill with<br />

volume damper size 8"*4" by "Cooling Industries"<br />

or equal.<br />

UNIT 15<br />

18.40 Ditto, but 14"*10". UNIT 3<br />

18.41 Ditto, but 14"*12". UNIT 3<br />

18.42 Ditto, but 24"*18". UNIT 4<br />

18.43 Ditto, but 30"*8". (Provisional) UNIT 3<br />

18.44 Supply and install decorative vertical fan coil made<br />

by Carrier (France), Daikin (Japan) or equivalent,<br />

unit FC1 with cooling capacity shown on drawings,<br />

complete with painted plastic cover, washable air<br />

filter, 2 shut-off valves, drain pan, double deflection<br />

plastic grilles (manually operated) for the supply air<br />

and fixed deflection plastic grilles for the return air.<br />

The price includes thermostat (on-off ,3 - speed<br />

switch) by "Landys & Gear"or equal, and 3-way<br />

valve.<br />

The price should include also all electrical works<br />

needed (material, labor), connection with water<br />

lines and drainage.<br />

UNIT 4<br />

18.45 Ditto, but FC2. UNIT 6<br />

18.46 Ditto, but FC3. UNIT 1<br />

18.47 Supply and install ducted horizontal fan coil made<br />

by Carrier (France), Daikin (Japan) or equivalent,<br />

unit FC8 without cover with cooling capacity<br />

shown on drawing, complete with plenum,<br />

aluminum mesh flat filter, drain pan, 2 shut-off<br />

valves and hangers. The price should not include<br />

thermostat. The price should include all electrical<br />

works needed (material, labor), connecting with<br />

water and drainage lines, price to include 3-way<br />

valve.<br />

18.48 (Provisional) Supply and install complete air cooled<br />

chilling unit for 85 TR (same as installed in first<br />

stage) made by Carrier (France), Daikin (Japan) or<br />

equivalent, including condenser, screw type<br />

compressors, shock absorbers, accessories, all as<br />

described.<br />

18.49 (Provisional) Connect the above unit with existing<br />

electric switchboard and the control including all<br />

material and wiring, cabling and labor.<br />

18.50 (Provisional) Supply and install cooling/heating<br />

water pumps (same as installed in first stage) as<br />

described, by "Grundfos" or equivalent.<br />

UNIT 2<br />

UNIT 1<br />

L.S 1<br />

UNIT 1<br />

21


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

18.51 (Provisional) Connect the above unit with existing<br />

electric switchboard including all material, cabling,<br />

wiring and labor.<br />

18.52 (Provisional) Supply and Install chiller Electrical<br />

switchboard to be weatherproof including<br />

controling,all material and labor. All as per the<br />

approval of the Engineer.<br />

18.53 (Provisional) Supply and Install pumps Electrical<br />

switchboard to be weatherproof including<br />

controlling, all material and labor. All as per the<br />

approval of the Engineer.<br />

18.54 (Provisional) Supply and install hermetic expansion<br />

tank 50 lit type Reflex, Elbi or equivalent.<br />

L.S 1<br />

L.S 1<br />

L.S 1<br />

UNIT 1<br />

18.55 (Provisional) Supply and install check valve 2'' UNIT 10<br />

18.56 (Provisional) Supply and install Automatic Air Vent UNIT 4<br />

18.57 (Provisional) Supply , install and connect flow<br />

switch<br />

18.58 (Provisional) Supply and install pressure break<br />

valve for 1".<br />

18.59 (Provisional) Supply and install floating concrete<br />

base with iron profile frame, spring type shock<br />

absorbers for pumps as described.<br />

18.60 Supply, install and connect in line exhaust fan unit<br />

8" as per vortice or equivalent. Price includes<br />

propper connection with the duct system from both<br />

sides as per specifications and connection with<br />

electrical power and control as per the approval of<br />

the Engineer.<br />

UNIT 2<br />

UNIT 4<br />

UNIT 1<br />

UNIT 2<br />

18.61 Ditto, but 6" made by Vortice or equivalent. UNIT 4<br />

Total of Air Conditioning Works….carried to<br />

summary:<br />

22


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

19 Supply, install, and test Black steel gas pipes 1/2"<br />

diameter coated with extruded<br />

Polyethelene,shrinkable sleeves at threaded joints.<br />

the line to be laid at 90 cm from ground level. Price<br />

to include the excavation and backfilling with<br />

20cm sand around the gas line, compacted base<br />

coarse and asphalt.<br />

20 Medical Gas Supply:<br />

20.1 Copper pipes type (L) degreased medical oxygen<br />

compatible seamless type. The pipes must be<br />

cleaned and treated for medical gas usage<br />

including capping the ends of each pipe to ensure<br />

that no foreign bodies, dust, or vapors affect the<br />

interior of the pipes. The copper pipes must meet<br />

the international standard.<br />

ASTM B-280 and to be cleaned for medical usage<br />

(degreased) according to CE 0473. Price includes<br />

proper isolation for piping under plastering and in<br />

penetrations, hangers, brackets, fasteners, etc.., as<br />

well as various fittings and accessories needed to<br />

complete the works as shown on drawings and as<br />

per specifications. Price also includes proper<br />

flushing of the entire piping network using Nitrogen<br />

or Medical Compressed Air.<br />

Mr 70<br />

20.1.a ½ inch O.D. MR 90<br />

20.1.b 5/8 inch O.D. MR 250<br />

20.1.c 7/8 inch O.D. MR 280<br />

20.1.d 1 3/8 inch O.D. MR 100<br />

20.1.e 1 1/8 inch O.D. MR 130<br />

20.1.f 1 5/8 inch O.D. MR 30<br />

20.2 Supply and Installation of Area Valves Control<br />

Boxes:<br />

Recessed area valve control box for medical<br />

oxygen, medical compressed air and vacuum.<br />

Including 3 full-port 3-parts NIBCO shut off valves<br />

which controls the supply of gases or vacuum<br />

through the pipelines, and line pressure and<br />

vacuum gauges. The valves diameter varies<br />

between 15 up to 35 mm, as per drawings. The<br />

area valves control boxes should also include an<br />

emergency external supply port, equipped with disk<br />

and clutch mechanism for quick plug-in connection<br />

of the emergency external supply source.<br />

The front should be made of labeled transparent<br />

polycarbonate flexible unbreakable cover to ease<br />

access in emergency situation, all as per<br />

Silbermann or equally approved<br />

NO. 1<br />

23


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

20.3 Supply and Installation of bed head units:<br />

20.3.a Factory-preassembled Bed head unit for one bed,<br />

according to CE-0473, EN-46001, ISO 9001<br />

Encompassing extruded aluminum duct system,<br />

with four cavities, three of which are directly<br />

accessed using snap-on covers. Supplying<br />

electrical and lighting service, as well as medical<br />

gas service. The gas outlets should be installed in<br />

a separate compartment, The number of electrical<br />

circuits, apart of the low voltage circuit, should be<br />

three: main line power circuit, UPS power circuit,<br />

and lighting circuit, each connected to a separate<br />

terminal at the main special electrical connection<br />

compound in the bed-head unit.<br />

The bed head unit is equipped with the following<br />

services:<br />

One oxygen outlet<br />

One compressed air outlet<br />

One vacuum outlet<br />

2 electrical sockets, Main line<br />

2 electrical sockets, coded-UPS line<br />

one potential grounding socket<br />

indirect light<br />

direct light<br />

direct light (2 PL BIAX lamps)<br />

cut-off switch for direct / indirect lights<br />

one telephone socket<br />

preparation for nurse call socket<br />

The Price should include hanging rail and suction<br />

bottles bracket, complete interior wiring, cabling,<br />

piping, insulating, etc. for complete installation.<br />

The contractor must provide detailed schemes<br />

prior to supply and installation, supported with allr<br />

required conformities to standards, to be approved.<br />

NO. 2<br />

20.3.b Same as item 20.3.a, but for two beds NO. 3<br />

20.3.c Same as item 20.3.a, but for three beds NO. 7<br />

20.4<br />

Supply and installation of Local Area Pressure and<br />

Vacuum Alarm Box:<br />

local audio-visual pressure alarm box for medical<br />

oxygen, medical compressed air and vacuum to<br />

indicate pressure and vacuum failures by means of<br />

green LED, red LED, audio buzzer and pressure or<br />

vacuum gauge for each gas, as well as shut-off<br />

valves for each gas or vacuum, operated by means<br />

of one central PC card (microprocessor card) and<br />

pressure/vacuum switches for each gas, recessed<br />

type with anodized aluminum panel.<br />

Total of Medical Gas Supply…carried to<br />

summary:<br />

NO. 1<br />

24


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

Section III - Electrical Works<br />

Note: All materials and accessories to be used<br />

shall be according to the Approved<br />

Manufacturer List attached to the tender<br />

Documents, or equally approved.<br />

22 Electrical Points:<br />

a Cost of Electrical points shall include cost of<br />

connections electric supply from electrical<br />

switchboard to first point in circuit is included in the<br />

price of that point (by means of cable or leads in<br />

conduit).<br />

b Conduit and wires or cables to the points by means<br />

of or self-extinguishing conduit and cables, as req.<br />

22.1 Supply, install and connect standard lighting point<br />

(internal or external) embedded in concrete slabs<br />

or above false ceiling. Cost of the point shall<br />

include 16 mm diameter conduit or trunk, 1.5<br />

sq.mm cross-section leads or cable, lighting<br />

switches (single , double, two way or push button),<br />

outlet for luminary with junction box and terminals.<br />

Comp. 100<br />

22.2 Ditto but for emergency lighting point Comp. 20<br />

22.3 Supply, install and connect 16A wall socket points.<br />

Cost of point shall include 16 mm dia.conduit or<br />

trunks, 3x2.5mm2 leads or cables and (16 A) wall<br />

socket .<br />

Comp. 40<br />

22.4 Ditto but for fan coil units Comp. 15<br />

22.5 Ditto as item 22.1.03 but double socket. Comp. 20<br />

22.6 Ditto as item 22.1.05but with water proof double<br />

socket.<br />

Comp. 10<br />

22.7 Ditto as item 22.1.03 but with water proof cover. Comp. 10<br />

22.8 Supply, install and connect three-phase (5x16) A,<br />

single-circuit wall socket point, to include a 23 mm<br />

diameter conduit or trunk, (5x2.5) sq.mm cross<br />

section leads or cables and a (5x16) single-circuit<br />

wall socket accessory .<br />

22.9 Supply, install and connect Intercom connection<br />

point (Price includes 16 mm diameter conduit with<br />

a standard Intercom cable, leading from point to<br />

the Intercom section in LV box).<br />

22.10 Supply, install and connect Public Address System<br />

connection point (Price includes 16 mm diameter<br />

conduit with cable, leading from point to the LV box<br />

to the nearest point).<br />

22.11 Supply, install and connect Fire Alarm connection<br />

point (Price includes 16 mm diameter conduit with<br />

cable, leading from point to the LV box to the<br />

nearest point).<br />

Comp. 2<br />

Comp. 8<br />

Comp. 5<br />

Comp. 11<br />

25


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

22.12 Supply, install and connect TV connection point<br />

(Price includes 23 mm diameter conduit with<br />

cable, leading from point to the LV box).<br />

22.13 Supply, install and connect Nurse Call point (Price<br />

includes 16 mm diameter conduit with cable,<br />

leading from point to the nurse call station).<br />

22.14 Supply, install and connect computer outlet point<br />

(Price includes 16 mm diameter conduit with pull<br />

wire, leading from point to the nearest HUB in the<br />

nearest LV box).<br />

22.15 Supply, install and connect telephone socket point<br />

in 23 mm conduit including 23 mm diameter<br />

conduit from nearest telephone cabinet to<br />

accessory output in junction box, standard socket<br />

telephone accessory, and standard 2x2x.5mm2<br />

telephone lead, inserted from cabinet to accessory<br />

including connection at both ends.<br />

22.16 Supply, install and connect point for thermostat<br />

including16 mm diameter conduit installed on one<br />

side near socket for fan coils and termination with<br />

a suitable box on other side at thermostat output.<br />

3 mm thick Nylon draw-string shall be inserted<br />

inside conduit.<br />

22.17 Supply, install and connect 6 sq. mm grounding<br />

point - to include a 16 mm diameter conduit,<br />

connect at one end to grounding bus-bar in nearest<br />

switchboard, and at other end to grounded element<br />

(air-conditioning ducts, acoustic ceiling, alum.<br />

Partitions etc.<br />

22.18 Supply, install and connect emergency push-button<br />

point, to include a 16 mm diameter conduit, (3x1.5)<br />

sq.mm cross-section leads, and a dual contact<br />

emergency push-button installed in a box with<br />

frame, transparent plastic cover to be broken in<br />

case of emergency, and engraved Bakelite<br />

"sandwich" type sign, per plan (box such as<br />

TELEMENIA model ZAS-E25).<br />

22.19 Supply, install and connect point for bed head<br />

units including 3x2.5mm2 NYY cable and 23mm<br />

dia conduit from electrical switchboard to BHU<br />

junction box with all required accessories and<br />

materials.<br />

22.20 Supply, install, and connect point as above, but by<br />

a 3x1.5 sq.mm NYY cable and16mm dia conduit.<br />

22.21 Supply, install and connect point as above, but by<br />

a 6 sq.mm cross-section grounding lead and 23<br />

mm diameter conduit.<br />

22.22 Supply, install and connect point as above, but for<br />

communication, by a 23 mm conduit diameter<br />

conduit.<br />

Comp. 9<br />

Comp. 94<br />

Comp. 9<br />

Comp. 9<br />

Comp. 11<br />

Comp. 15<br />

Comp. 1<br />

No. 25<br />

No. 12<br />

No. 12<br />

No. 12<br />

26


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

22.23 Re-route existing power lines at the building to be<br />

connected to the new distribution board ( DB-2),<br />

the works shall include all necessary materials,<br />

cables, conduits, trunks and all needed civil works.<br />

22.24 Ditto as above but for general low voltage<br />

installations at the building<br />

Total of Electrical Points….carried to summary:<br />

23 Conduit, Rigid Piping and Excavation Works:<br />

Supply, install and connect Self-extinguishing type<br />

plastic conduit, processed over or under plaster or<br />

inside castings, including junction boxes, unions,<br />

connectors, etc. including galvanized draw-strings,<br />

ready for use (for works not included in points).<br />

No. 10<br />

No. 30<br />

23.1 23 mm diameter. ML 50<br />

23.2 29 mm diameter. ML 50<br />

Total of Conduit, Rigid Piping and<br />

Excv…..carried to summary:<br />

24 Cables:<br />

Supply, install and connect XLPE non-armored<br />

type thermoplastic copper cables, including<br />

insertion into conduit or attachment to structural<br />

elements or laying in ductwork, including all<br />

associated materials, insulation materials, unions,<br />

Ladders, Z Constructions, cable shoes, and<br />

connection of cable at both ends.<br />

24.1 5x16 sq.mm cross section. M.L. 60<br />

24.2 5x10 sq.mm cross section. M.L. 210<br />

24.3 5x6 sq.mm cross section. M.L. 100<br />

24.4 5x4 sq.mm cross section. M.L. 100<br />

Total of Cables ……carried to summary:<br />

27


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

25 Structural Elements, Cabinets and Ductwork:<br />

Supply, install and connect Prefabricated<br />

perforated cable tray mounted on walls or attached<br />

to ceilings. Price to include all reinforcing and<br />

attaching hardware, structural elements, brackets<br />

construction, covers were required and hangers<br />

etc.<br />

25.1 20/10 cm. M.L. 45<br />

25.2 40/10 cm. M.L. 45<br />

25.3 Ditto same as item 25.1 but 20/10 with cover M.L. 60<br />

Total of Structural Elements, Cabinets…..<br />

carried to summary:<br />

26 Grounding:<br />

26.1 Supply, install and connect Complete lightning<br />

system including exciter,120mm copper<br />

conductor, 3-earth electrodes ,earth pit and all<br />

required materials and accessories needed to<br />

complete the job as specifications and Engineer<br />

instructions.<br />

Total of Grounding …..carried to summary:<br />

27 Electrical Switchboards:<br />

a. Supply, install and connect the electrical<br />

switchboards to the site, including all associated<br />

materials and labor, as described in the technical<br />

specifications.<br />

b. Cabinets with no access from the rear, made up of<br />

transparent polycarbonate cells, or sheet-metal<br />

cabinets with a 25% surplus space.<br />

c. The switchboards are to be placed on the floor, in<br />

a niche against the wall.<br />

d. Main supply lines enter from the switchboard<br />

bottom, top or side, while outgoing lines exit the<br />

switchboard from both its bottom and top sides.<br />

e. Price to include all structural elements required in<br />

order to install the switchboard, including bus-bars,<br />

terminals, wiring, bolts, clamps, etc. and for the<br />

equipment listed below.<br />

g. Prices for supply, installation and connection of<br />

various accessories including all associated labor<br />

and materials such as bus-bars, terminals, wiring<br />

reinforcements, mounts, engraved "sandwich" type<br />

identification plates, etc. including connection to<br />

ma<br />

L.S 1<br />

27.1 Distribution Board(DB2) Unit 1<br />

Total of Electrical Switchboards…..carried to<br />

summary:<br />

28


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

28 Luminaries Supply and Installation:<br />

a. Supply and installation of Lighting fixtures as<br />

described below, including all necessary<br />

accessories, required in order to light it with lamps<br />

and electronic starter, complete.<br />

b. It is hereby stressed that the client is entitled to<br />

furnish all or part of the luminaries through other<br />

supply sources.<br />

c. All lamps shall be of the energy-saving type (18,36,<br />

58 Watts).<br />

28.1 Type (A) 2x36W fluorescent light fixture Prismatic<br />

type.<br />

Unit 20<br />

28.2 Type (AE) Ditto as A but with emergency charger. Unit 14<br />

28.3 Type (B) 2D 16W Globe with opal diffuser. Unit 18<br />

28.4 Type (E) 1 x 8W fluorescent emergency exit sign<br />

luminaries with white steel body, for maintained<br />

emergency lighting of 3 hour duration, legend<br />

panels (3) included (down, left and right).<br />

28.5 Type (G) 5W Recessed night light corrosion proof<br />

IP65.<br />

28.6 Type (J) Ceiling mounted lighting 2XPL-L 11 lamp<br />

compact fluorescent with opal diffuser controller<br />

IP20.<br />

28.7 Type (K) 2x36W, fluorescent lighting fixture, ceiling<br />

mounted with prismatic diffuser ( Internal primes)<br />

IP20.<br />

Unit 1<br />

Unit 10<br />

Unit 6<br />

Unit 7<br />

28.8 Type (KE) Ditto as K but with emergency charger. Unit 8<br />

28.9 Type (L) Down light, recessed in false ceiling, with<br />

PL-C 13 W compact fluorescent energy saving<br />

lamp, cast aluminum cover and ring silver ( frosted)<br />

aluminum reflector, IP20.<br />

28.1 Type (M) 2x36W, fluorescent lighting fixture, ceiling<br />

/ pendant. Body of grey fiber-glass reinforced<br />

polyester, prismatic polycarbonate diffuser, IP54.<br />

28.11 Type (P) 4x18W, fluorescent lighting fixture,<br />

recessed in false ceiling, with prismatic diffuser (<br />

Internal primes), IP20.<br />

Unit 5<br />

Unit 3<br />

Unit 3<br />

28.12 Type(PE) as P with 3 hrs emergency kit. Unit 2<br />

Total of Luminaries Supply…carried to<br />

summary:<br />

29


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

29 Nurse Calling System:<br />

Note: All equipment items for the nurse- calling<br />

system shall be according to the approved<br />

manufacturer list.. The work to include the supply<br />

of the equipment specified, installation of same,<br />

connection, wiring, commissioning and all other<br />

details, as specified in the technical specification<br />

and drawings.<br />

29.1 Master station 30- call master. Unit 1<br />

29.2 Reset button. Unit 11<br />

29.3 Bedside call switch. Unit 31<br />

29.4 NBY-1A metal jack. Unit 31<br />

29.5 Corridor lamp. Unit 11<br />

29.6 Ceiling mount 180mm O(7-1/8"O) NB-L Unit 11<br />

29.7 Moisture resistant pull cord switch. Unit 11<br />

29.8 Power supply for the master station. Unit 1<br />

Total of Nurse Calling System…carried to<br />

summary:<br />

30 Fire Alarm System:<br />

Supply install and connect complete in place and<br />

in an operable manner the fire alarm system. The<br />

work is to include the supply of the equipment<br />

specified, installation of same connection, wiring,<br />

cables, commissioning and all of the details and<br />

connecting to the existing system as specified in<br />

the technical specifications and drawings.<br />

30.1 Maintenance work for the existing fire alarm panel,<br />

this includes changing any required equipments in<br />

side the panel and doing any required repairs for<br />

the existing lines of the existing points including<br />

changing the glass covers of the broken break<br />

glass points.<br />

Job 1<br />

30.2 Manually operated alarm call point . Unit 5<br />

30.3 Interior Alarm horn for fire detection system . Unit 2<br />

30.4 Ionization smoke detector . Unit 5<br />

30.5 Ionization heat detector . Unit 1<br />

Total of Fire Alarm System Carried to Summary:<br />

30


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

31.00 Intercom System:<br />

Note: All equipment items for the intercom system<br />

shall be according to the approved manufacturer<br />

list.. Work is to include the supply of the equipment<br />

specified installation of same, connection, wiring,<br />

commissioning and all other details, as specified in<br />

the technical specifications and drawings.<br />

31.1 Hands free master station . Unit 1<br />

31.2 Power supply adaptor . Unit 1<br />

31.3 Door phone adaptor . Unit 1<br />

31.4 Door station . Unit 1<br />

31.5 Power supply adaptor . Unit 1<br />

31.6 Door release . Unit 1<br />

31.7 AC transformer for door release . Unit 1<br />

31.8 Digital keypad . Unit 1<br />

31.9 12V AC power supply transformer Unit 1<br />

Total of Intercom System carried to summary:<br />

32 Public Address System:<br />

Supply, install, test and commission a public<br />

address system, the system shall be according to<br />

the approved manufacturer list, including all<br />

required connections with the existing system of<br />

the Hospital including all required cables and<br />

conduits complete ready for work.<br />

32.1 9/6 watt ceiling loudspeaker, 8” round with metal<br />

grille, screw mount.<br />

Total of Public Address System carried to<br />

summary:<br />

33 Telephone System:<br />

33.1 Supply install and connect main telephone cables<br />

from telephone exchange to the LV2 boxes. Rate<br />

to include 2 NO's. 25 pair cables, conduits,<br />

terminal blocks and all accessories as specified in<br />

the technical specification and drawings.<br />

33.2 Adding two internal cards type SLC8 for the<br />

existing Alcatel telephone exchange.<br />

Total of Telephone System carried to summary:<br />

Unit 10<br />

Job 1<br />

Job 1<br />

31


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Item Description Unit QTY Unit Rate Amount<br />

34 LV Boxes:<br />

34.1 Supply install and connect the following LV boxes.<br />

Rate to include all required materials, conduits,<br />

wires, cables and accessories manufacturing from<br />

galvanized sheet metal sheets, painted with the<br />

same color of the switch boards all as specified.<br />

LVB2 Approximate dim. (80x60x25) cm No. 1<br />

Total of LV Boxes carried to summary:<br />

32


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor 16 June 09<br />

Bill Description Total<br />

Section I Civil Works Summary<br />

1 Preparation Works<br />

2 Concrete Works<br />

3 Block work<br />

4 Sealing Works<br />

5 Carpentry and Metal Works<br />

6 Stainless Steel Works<br />

7 Plastering Works<br />

8 Flooring and Covering Works<br />

9 Painting Works<br />

10 Aluminum Works<br />

11 Stone Works<br />

12 Suspended ceiling<br />

13 Fixed Furniture<br />

Total of Civil Works<br />

Section II Mechanical Works Summary<br />

14 Cold and Hot Water Supply System:<br />

15 Waste and Drainage Systems:<br />

16 Sanitary fixture and their Accessories:<br />

17 Rainwater Drain Pipes:<br />

18 Air Conditioning Works:<br />

19 Gas System<br />

20 Medical Gas Supply:<br />

Total of Mechanical Works<br />

AMS<br />

Engineering Unit @ <strong>UNDP</strong>/PAPP<br />

Summary of Part 1


ATLAS # 14163 Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor 16 June 09<br />

Section III Electrical Works Summary<br />

22 Electrical Points<br />

23 Conduit, Rigid Piping and Excavation Works<br />

24 Cables<br />

25 Structural Elements, Cabinets and Ductwork<br />

26 Grounding<br />

27 Electrical Switchboards<br />

28 Luminaries Supply and Installation<br />

29 Nurse Calling System<br />

30 Fire Alarm System<br />

31 Intercom System<br />

32 Public Address System<br />

33 Telephone System<br />

34 LV Boxes<br />

Total Electrical Works<br />

NET TOTAL SUM (in words ) :<br />

SIGNED AND SEALED :<br />

AUTHOURIZED PERSON :<br />

TITLE :<br />

SIGNATURE :<br />

DATE :<br />

AMS<br />

Engineering Unit @ <strong>UNDP</strong>/PAPP<br />

Total of Part 1 (Excluding VAT)<br />

Discount %<br />

Discount Amount<br />

Net Total - Part 1 (Excluding VAT)


Bill of Quantities<br />

Part 2<br />

Rehabilitation of the X-ray Department and the Internal Medicine Ward<br />

at Hebron Hospital<br />

Prepared By<br />

Lamasat Office<br />

Architects & Interior Designers<br />

June 2009


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

Section I - Civil Works<br />

1 Demolishing & Removal Works<br />

The contractor shall visit the proposed site to familiarize<br />

himself with the required scope of work and the existing site<br />

conditions. Unit price shall include costs of the needed<br />

material and the workmanship which are required to<br />

complete the work. The price shall include costs for<br />

making the necessary temporary works to ensure the safety<br />

of the visitors of the functioning hospital and to protect the<br />

finished works rendered in the existing hospital. Price shall<br />

also include cost of hauling away the demolished material.<br />

The contractor shall preserve, protect and make the<br />

necessary works to maintain the existing electromechanical<br />

system to serve the functioning hospital. It<br />

shall be clearly understood that all salvaged materials and<br />

fittings are the property of the Hospital and must be handed<br />

over to the director of Hospital<br />

1.1 Demolishing and removal of portions of existing concrete<br />

walls to make new openings or enlarge existing opening.<br />

The unit price shall include dismantling and preserving the<br />

existing doors or windows. For details refer to drawing No.<br />

A03. All as directed by the Engineer<br />

1.2 Demolishing and removal of existing block, gypsum or<br />

wood partition walls. The unit price shall include<br />

dismantling and preserving the existing doors and windows.<br />

For details refer to drawing No. A03. All as directed by the<br />

Engineer<br />

1.3 Demolishing and removal of the existing tiles. The unit price<br />

shall include dismantling the panel tiles. All as directed by<br />

the Engineer.<br />

1.4 Careful dismantle and preserve the existing doors and<br />

frames.<br />

1.5 Chipping off and removal of existing plaster in areas<br />

specified by the Engineer and make ready to receive new<br />

plastering or tiles.<br />

Total of Demolish & Removal Works carried to civil<br />

summary:<br />

2 Block Works<br />

M2 20<br />

M2 230<br />

M2 630<br />

NO 48<br />

M2 100<br />

Supply and construct hollow concrete block (type A,<br />

compressive strength 35kg/cm2) walls using cement and<br />

sand mortar (1:4) . The price includes cost of cutting,<br />

bonding, anchoring, control and expansion joints, utilities<br />

openings, dummy columns and reinforced concrete lintels<br />

(of 4 steel bars 12mm dia and 8mm stirrups@ 20cm c/c)<br />

over doors and windows opening and accross the whole<br />

width of the wall. For more details refer to drawing No<br />

A04,A11.<br />

2.1 Ditto for 10 cm block walls M2 240<br />

2.2 Ditto, but for 15 cm block walls M2 60<br />

Total of Block Works carried to civil summary:<br />

1


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

3 Plastering Works<br />

Three layers of internal plastering 20mm thick composed of<br />

a bond coat, base coat, and finish coat, including plaster<br />

stops, corner beads, casing beads, metal laths,<br />

scaffoldings, shuttering, bonding agents and all<br />

requirements as specified.<br />

The surfaces to be plastered are to be dashed with white<br />

cement & sand mix 1:1 to from a key, allowed to harden<br />

before applying two coats: the first coat mix. 1:1:3 (cement:<br />

sand: fine aggregate) and the second coat mix 1:4:1<br />

(cement: sand: lime). The unit rate includes furnishing and<br />

installing of reinforcing wire mesh 200mm wide to all<br />

chases of electro mechanical works and to junctions of<br />

block work & concrete surfaces.<br />

3.1 For walls, columns,..etc. M2 320<br />

3.2 Two coats plaster to receive ceramic wall tiles M2 110<br />

Total of Plaster Works carried to civil summary:<br />

4 Tiling Works<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses of all<br />

requirements stipulated in the preambles, drawings and<br />

technical specification of the contract.<br />

Samples should be submitted for engineers approval<br />

This item includes spacers<br />

4.1 Supply and install 30x30x1cm Turkish "TOBRAC"or<br />

equivalent floor tiles similar to existing or equally approved.<br />

Rate includes 30cm x 10cm x 1 cm skirting, 3 cm cement<br />

sand mortar (1:3 ), sand fill materials, cuttings, fittings,<br />

trims, grouting with white cement and polishing, all in<br />

accordance with the specifications and applicable<br />

Standards. For more details refer to drawing No. A06.<br />

4.2 Corridor Walls<br />

supply and installation of 200x200x6mm high quality<br />

ceramic tiles (Negev or equally approved) laid on 10 mm<br />

thick mortar backing (1:1:4). Rates include roughening of<br />

walls and all needed preparation work to receive tiles, 2mm<br />

thick stainless steel angles to be installed on corners as per<br />

the drawings. For more details refer to drawing No. A16.<br />

4.3 WC & kitchen tiles<br />

4.3.1 To walls:<br />

200x200x6mm high quality glazed white ceramic tiles laid<br />

on 10 mm thick mortar backing (1:1:4). For more details<br />

refer to drawing No A16.<br />

4.3.2 To floor:<br />

200x200x8mm high quality no-split ceramic tiles laid on<br />

30mm thick mortar bed (1:3) on sand bed or<br />

aggregate as needed. For details refer to drawing No A06<br />

4.4 Stair treads:<br />

Supply and install 3cm thick, 35cm width and 150cm length<br />

polished local marble ( Sour Moeen or equally approved )<br />

round edge nose treads, including sand bed underlay,<br />

bedding and jointing in white cement and sand (1:4) and<br />

pointing in white or colored approved pointing material cut<br />

to size as shown on drawing No. A17 and as per the<br />

engineer's instructions. The rate includes an edge piece for<br />

water stop.<br />

2<br />

M2 630<br />

M2 640<br />

M2 130<br />

M2 160<br />

M.R 40


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

4.5 Stair risers:<br />

Supply and install 2cm thick and 150 cm length polished<br />

local marble( Sour Moeen or equally approved ) risers,<br />

bedding and jointing in white cement and sand (1:4) and<br />

pointing in white or colored approved, pointing material cut<br />

to size as shown on related details and as per the<br />

engineer's instructions & drawing No A17.<br />

4.6 Stair case skirting:<br />

1.5cm thick variable height polished local marble ( Sour<br />

Moeenor equally approved ) skirting bedding and jointing<br />

in white cement and sand (1:4) and pointing in white or<br />

colored approved pointing material cut to size as shown on<br />

drawing No A17and as per the engineer's instructions:<br />

Total of Tile Finishing carried to civil summary:<br />

5 False Ceiling Works<br />

The contractor shall, when pricing this bill ,take into<br />

consideration and allow for the costs or expenses of all<br />

requirements stipulated in the preambles drawings and<br />

technical specifications of the contract.<br />

5.1 Supply & install non perforated acoustical ceiling made of<br />

formed galvanized sheet metal trays for bathrooms and wet<br />

areas. The metal trays should be of 0.8 mm thick 45mm<br />

high coated with “pvc”200 microns thick. For details refer to<br />

drawing A05.<br />

5.2 Supply & install perforated metal sheets (20%-25%<br />

perforation). The metal trays should be covered with<br />

continuous and uniform manner of rock wool mats 25 mm<br />

thick of 25 kg\m³ density. The rock wool mats shall be<br />

wrapped by inflammable polyethylene sacks,(in accordance<br />

with the safety regulations and standards). For details refer<br />

to drawing A05.<br />

5.3 Dismantling, cleaning and re-installing existing false ceiling<br />

panels. For details refer to drawing A05.<br />

Total of False Ceiling Works carried to civil summary:<br />

3<br />

M.R 40<br />

M.R 20<br />

M2 60<br />

M2 260<br />

M2 410


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

6 Painting Works<br />

The contractor shall, when pricing this bill, take into<br />

consideration and allow for the costs or expenses of all<br />

requirements stipulated in the preambles, drawings and<br />

technical specification of the contract, including scrubing of<br />

old paint where needed.<br />

The contractor should allow in his pricing that the engineer<br />

will use as many different colors or combination of colors to<br />

meet an approved color scheme.<br />

*Colors of paint shall be coordinated with the engineer for<br />

approval.<br />

*The Contractor shall prepare 1 m2 samples for approval<br />

by the Engineer<br />

*All painting material shall be made by Tambour or equally<br />

approved<br />

6.1 Supply and apply one layer of emulsion paint to ceiling and<br />

walls above suspended ceiling level and where instructed<br />

by the engineer.<br />

6.2 Supply and apply one coat of primer fill and three coats of<br />

policed paint for plastered walls and ceiling<br />

6.3 Supply and apply one coat of primer fill, two coats of putty<br />

and three coats of emulsion paint for plastered walls<br />

M2 1340<br />

M2 190<br />

M2 3000<br />

6.4 Supply and apply oil paint for wet areas composed of<br />

primer fill ,two coats of putty, one coat of under coat, and<br />

three coats of oil paint.<br />

M2 80<br />

6.5 Painting of walls with “Acrinol” by Deluxe or equally<br />

approved for mildew and fungus protector<br />

M2 320<br />

6.6 Supply and apply oil paint for metallic surfaces "Superlac" . M2 66<br />

Total of Painting Works carried to civil summary:<br />

4


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

7 Carpentry & Joinery<br />

Note: wood works include painting, varnishing, polishing<br />

oiling & the like.<br />

7.1 Wood Doors & Frames:<br />

Fabricate, supply and fix in position the following wooden<br />

doors, flush faced on both sides with (PVC) laminate<br />

complete with and including standard pressed steel door<br />

frame fill in all voids with mortar grout, door closer, extruded<br />

aluminum kick plate, bolts, door locks by "Yale" or equally<br />

approved, door stops, heavy duty hinges, fix glass panels<br />

etc. complete as per details and door finishing schedule. (3<br />

Master keys shall be provided).<br />

7.1.1 Doors With Half Glazed:<br />

this item includes sand plast glass panels for doors.<br />

Type DR1 overall size 210x140cm NO 1<br />

7.1.2 X-Ray Rooms Doors<br />

Supply and fix in position wooden doors for X-ray rooms<br />

comprising hard wood edgings (ZAN) 75x32 lead lining<br />

5mm thick both sides, plywood face for both sides 1mm<br />

thick (PVC) laminate, 5mm thick gypsum board both sides,<br />

softwood core, extruded aluminum kick plate, complete with<br />

and including pressed steel frame filled with mortar grout,<br />

door closer, bolts, door locks by "Yale" or equally approved,<br />

door stop, heavy duty hinges, sealant, etc. as per finishing<br />

door schedule (Master key shall be provided).<br />

a Type DR2 overall size 210x120cm NO 1<br />

b Type DR3 overall size 210x110cm NO 1<br />

7.1.3 WC Doors<br />

this item including 12 cm height aluminum kick plate.<br />

a Type DR4 overall size 210x70cm NO 8<br />

b Type DR12 overall size 210x70cm NO 9<br />

7.1.4 Single Doors<br />

a Type DR5 overall size 210x80cm NO 1<br />

b Type DR6 overall size 210x85cm NO 1<br />

c Type DR7 overall size 210x90cm NO 3<br />

d Type DR8 overall size 210x100cm NO 1<br />

e Type DR9 overall size 210x110cm NO 1<br />

f Type DR10 overall size 210x115cm NO 2<br />

g Type DR11 overall size 210x135cm NO 1<br />

h Type DR13 overall size 210x80cm NO 3<br />

i Type DR14 overall size 210x95cm NO 3<br />

j Type DR15 overall size 210x100cm NO 1<br />

k Type DR16 overall size 210x110cm NO 9<br />

l Type DR17 overall size 210x115cm NO 1<br />

5


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

7.2 kitchen cupboards<br />

7.2.1 Top cupboard unit<br />

Supply And install plywood kitchen cupboard Overall size<br />

220 x 30 x 60 cm. consisting of three double aluminum<br />

doors ,17 mm plywood shelves both sides covered with<br />

Formica laminate Complete with, ironmongery, hardware,<br />

and painting.<br />

All according to drawing A14& engineer instructions<br />

Samples of Formica to be approved by the engineer<br />

7.2.2 Bottom cupboard unit<br />

Supply And install marble kitchen cupboard Overall size<br />

220 x 60 x 90 cm. consisting of two double aluminum doors<br />

,17 mm plywood shelves both sides covered with Formica<br />

laminate and a set of four aluminum face drawers,<br />

laminate cover high quality Formica ). Complete with,<br />

ironmongery, hardware, and painting.<br />

including granite counter top "Tiger eye" with top& bottom<br />

skirting, beads, polishing, routings, jointing…etc and all<br />

preparatory woks for the installation of the required sink<br />

and sanitary fixtures. Amples of Formica to be approved by<br />

the engineer All according to drawing A14 & engineer<br />

instructions.<br />

7.3 Nurses Station desk<br />

Fabricate, supply and install wooden L shape desk as per<br />

drawings and specifications, for details refer to drawing<br />

A15.<br />

7.4 Wood Frame for Reception Desk<br />

Fabricate, supply and fix in position solid zan wood frame,<br />

for details refer to drawing No A13.<br />

7.5 X-Ray Control Booth<br />

Supply and fix in position wooden control booth for X-ray<br />

room comprising lead lining 5mm thick both sides, plywood<br />

face for both sides , 11mm thick gypsum board both sides,<br />

this item including 40*40*1 cm lead- glass panel for<br />

window.<br />

7.6 Wall Protector<br />

Supply and install a wooden wall guards cut to size<br />

according to the site requirements as made by (SPM ) or<br />

equally approved by the engineer including all necessary<br />

fittings. The color will be selected by the Engineer. For<br />

details refer to drawing No A 21.<br />

Total of Carpentry & Joinery Works carried to civil<br />

summary:<br />

6<br />

NO 3<br />

NO 3<br />

M.R 3<br />

M.R 25<br />

M2 5<br />

M.R 200


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

8 Insulation Works<br />

Fluid Applied Waterproofing:<br />

All finishes shall be measured superficially net unless<br />

otherwise stated clearly.Triangular shaped fillets and<br />

cement and sand lining to gutters shall be measured in<br />

linear meter, unless otherwise stated clearly.<br />

Rates for cement and sand work shall include for :<br />

Hacking concrete, applying cement slurry or raking out<br />

joints of blockwork to form key. Application to any surface.<br />

Finish to surface, to falls, cross falls and currents forming<br />

bays including joints. Finish to edges and arises. Making<br />

good around steel sections, pipes, tubes, bars, brackets,<br />

outlets, and the like.<br />

Measurement for water proofing shall be for sectional roof<br />

area only.<br />

Rates for waterproofing and roof sheeting shall include for:<br />

Preparation of surface, cuting in edges. overlaps, priming<br />

over parapets and stub columns including forming groove<br />

to receive edge of elasticized bitumen membrane and<br />

sealing with elastic sealer. Side and end laps, fittings<br />

including bolts, hook bolts, screws and washers, Sheets of<br />

any width or length .<br />

8.1 Internal wall insulation:<br />

for details refer to drawing No. A12. M2 25<br />

WC & kitchens floor insulation<br />

8.2 Supply and apply three coats of hot asphalt layers (25\75)<br />

at rate of 500 g/m2 for each layer, reinforced by two layers<br />

of fiberglass and a prime coat GS474 .all according to the<br />

manufacture and to the engineer’s approval<br />

8.3 Supply and install one layer of water proofing membrane of<br />

bitumen rolls 5mm thick, covered with white gravel,<br />

"Pazkar"or equally approved. The unit price shall include<br />

cost of a prime coat GS474 at a rate of 0.25 kg /m2 and all<br />

sheets flashing, including all the necessary material and<br />

workmanship, as specified.<br />

This item includes dismantling and removing the existing<br />

waterproofing material and cleaning the surface on the<br />

existing roof (where needed and as directed by the<br />

engineer ) to allow for the new waterproofing works.<br />

8.4 Repair and maintenance of certain areas of the existing<br />

waterproofing. The unit rates shall include cleaning of the<br />

existing waterproofing surfaces and supply and installtion of<br />

waterproofing material.<br />

8.5 Repair and maintenance of small patches (appox.<br />

100cmx100cm) of existing waterproofing. This item to be<br />

measured by the number of patches repaired.<br />

Total of Insulation Works carried to civil summary:<br />

9 Glass Works<br />

9.1 Sekurit Glass<br />

9.1.1 Sekurit Glass Panels<br />

Supply and install 100 cm hight,1cm thick high quality<br />

sekurit glass panels, including all accessories. For more<br />

dimensions & details refer to drawing A13,A14.<br />

9.2 Sand Glass Sekurit Panels<br />

Supply and install sand plast 1cm thick sekurit glass panels<br />

for door. For more dimensions & details refer to drawing<br />

A14.<br />

Total of Glass Works carried to civil summary:<br />

7<br />

M2 80<br />

M2 500<br />

M2 50<br />

NO 15<br />

M2 12<br />

M2 1.5


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

10 Metal work<br />

10.1 ALUMINUM<br />

All the profiles must be NAPCO 7700 for sliding windows,<br />

and NAPCO 2200 for fixed windows or equally approved.<br />

Fabricate supply and fix in position the following anodized<br />

aluminum windows & doors, complete with double glazing<br />

with 6mm thick clear glass for both inner and outer panels<br />

similar to existing windows, and 12mm thick air space filled<br />

with argon gas, and butyl framing rubber, perforated<br />

aluminum frame and polysulphide mastic between<br />

aluminum frame and glass, including aluminum woven<br />

mesh fly screen, all necessary frames, sub frames, fixing,<br />

fittings, accessories weather stripping and hardware as per<br />

specifications<br />

* Shop drawings & samples to be approved by the<br />

Engineer.<br />

10.1.1 Windows<br />

For windows details refer to drawing A18.<br />

Type W1 overall size 728x60cm NAPCO 2200 or<br />

equivalent .Complete with frame, glazing, mastic sealant,<br />

ironmongery and hardware.<br />

10.1.2 Doors<br />

Emergency Door<br />

Type door ED1 overall size 228x110cm.Thickness 52 mm<br />

Weight =29 kg/m². Complete with galvanized frame,<br />

glazing, mastic sealant, paint of door and frame according<br />

to engineer instructions and approval, ironmongery and<br />

hardware and including 15mm glass vision panel for more<br />

details refer to drawing No A18<br />

10.2 Metal Cupboards<br />

Supply and install painted metal cupboards overall size<br />

200x47 x60 cm including all accessories all as per<br />

drawings and details, for details refer to drawing No A15.<br />

NO 3<br />

NO 1<br />

NO 14<br />

10.3 Wall Signs<br />

supply & install wall signs.<br />

Aluminum plaques in Arabic & English with a special<br />

solvent proof,weather and temperature resistant fixed on<br />

the door or the wall .<br />

The price include labor work and all fixing materials.<br />

a size 25x12 cm NO 40<br />

b size 40x15 cm NO 5<br />

10.4 Curtain Tracks.<br />

All the profiles shall be of Clickeze, InPro Podiatric or<br />

equally approved. This item includes overhead metal<br />

curtain track, track accessories OPTITRAC (or equivalent),<br />

extruded aluminum cubicle track with clear anodized<br />

aluminum or white baked acrylic enamel finish. Aluminum<br />

shall be 6063-T5. Dimensions: height 3/4" (19.05mm),<br />

width 13/8" (34.93mm).<br />

a Supply & install L- shape tracks for curtains around beds,<br />

420cm long.<br />

NO 12<br />

b Ditto, but 300 cm long (straight). NO 5<br />

10.5 Steel -Wood Handrail<br />

Fabricate and supply and fix in position handrail for<br />

emergency stair case as per detail No A17 and Engineer<br />

approval. This item includes wood panels and all<br />

accessories for fixing in position.<br />

Total of Metal Works carried to civil summary:<br />

8<br />

M.R 8


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

11 Sand-blasting Works<br />

This item includes cleaning of existing stone facades with<br />

dry abrasive material forced by compressed air from tank<br />

through hose and nozzle. Cleaning material must be dustfree<br />

and abrasive. Material size shall be approved by<br />

engineer. Air pressure delivered by compressor to blasting<br />

tank may range from 40 lbs. to 100 lbs. per square inch<br />

according to the first test cleaning which shall approved by<br />

the engineer. Lightly sanded, coated, slurry, should not be<br />

cleaned by sandblasting.<br />

"pre-cleaning" process includes removing all large mortar<br />

particles with hand tools before blasting. Use wooden<br />

paddle, the rough edge of a brick, or metal scrape hoe.<br />

Chisels may be used if necessary to remove hardened<br />

mortar or concrete.<br />

The contractor shall provide adequate protection for all nonmasonry<br />

surfaces adjacent to work areas, Use plastic<br />

sheeting and duct tape to protect windows, doors, etc. If<br />

possible, painting, caulking, etc. should be done after<br />

sandblast operation is completed.<br />

Sandblast Cleaning of stone facades M2 1000<br />

Total of Other Works carried to civil summary:<br />

9


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

Section II - Mechanical Works<br />

12 SANITARY SYSTEM<br />

12.1 Supply and install of UPVC, type Redi - Italy made or E.A,<br />

drainage pipes to floor drains or to existing sewage pipes<br />

with all required fittings", "T" etc. The price includes<br />

digging and plastering, incasing with concrete cover for<br />

underground pipes, connection to existing riser pipes as<br />

shown in drawings, and approval of supervisor engineer.<br />

12.1.1 size 2 inch diameter M.R 75<br />

12.1.3 size 4 inch diameter M.R 50<br />

12.2 Supply and install of CPVC - Italy made, suspended and<br />

underground condensate drainage pipes from AC units to<br />

floor drains or to existing sewage pipes with all required<br />

fittings needed for installation. The price includes digging<br />

and plastering, concrete cover for underground pipes,<br />

hangers and supports for suspended pipes, as shown in<br />

drawings, and approval of supervisor engineer.<br />

12.2.1 size 2 inch diameter M.R 90<br />

12.3 Supply and install Floor Clean Out 4"UPVC type Redi -<br />

Italy made or E.A, including chrome plated (sealed type)<br />

cover (15*15 cm) complete with connection to drain pipes<br />

as located in drawings , specifications and approval of<br />

supervisor engineer.<br />

NO 5<br />

12.4 Supply and install of polypropylene DALLMER type 54 floor<br />

drain body with trap,rodding eye,DN 50 outlet, DALLMER<br />

grating KE 15<br />

NO 2<br />

12.5 Supply and install 4" floor trap UPVC, type Redi - Italy<br />

made or E.A, include chrome plated screw type cover<br />

(15*15 cm) completed with connections to drain pipes as<br />

located in drawings, specifications and approval of<br />

supervisor engineer.<br />

NO 11<br />

12.6 Ditto but floor drain size 4"/2" diameter NO 11<br />

12.7 Dismantle all the existing sanitary fixtures with pipes<br />

networks (where required) in internal medicine ward and X-<br />

Ray Departments with all accessories and fittings as per<br />

engineer's instructions and keep safe in hospital store<br />

(where possible).<br />

JOB 1<br />

12.8 Supply and install fire glazed wall hung washbasin, white<br />

colour, of size 55*45 cm type Roca or E.A, complete with<br />

chrome plated mixer, type Hamat, 1/2" * 3/8" angle valves,<br />

supports, 2" waste outlet down to floor drain, plastic siphon<br />

trap, including connections to drain and water outlets, as<br />

shown in drawings, and approval of supervisor engineer.<br />

NO 30<br />

12.9 Supply and install fire glazed kitchen sink, white colour, of<br />

size 55*45 cm type Roca, or E.A, complete with chrome<br />

plated mixer, type Hamat, 1/2" * 3/8" angle valves,<br />

supports, 2" waste outlet down to floor drain, plastic siphon<br />

trap, including connections to drain and water outlets, as<br />

shown in drawings, and approval of supervisor engineer.<br />

12.10 Supply and install fire glazed wall mounted vitreous china<br />

water closets, white colour, type Roca or E.A, including<br />

recessed cistern type Schwab, complete with cistern,<br />

valves , fittings, solid seat and cover, toilet roll paper holder<br />

, chrome plated 1/2" stop angle valve of approved quality,<br />

chrome plated 13mm hose, including connection to drain<br />

and water outlets, plug, flexible pipe with the hand spray<br />

and all accessories for complete installation, all is<br />

according to drawings, and approval of supervisor<br />

engineer.<br />

10<br />

NO 3<br />

NO 22


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

12.11 Supply and install white glazed shower tray, white colour,<br />

type Roca or E.A, of size 90X90cm, complete with chrome<br />

plated mixers, type Hamat, plug and chain, 1.5m flexible<br />

hose with chrome lever handle and stand, and all<br />

associated water supply pipes, and brackets screwed to<br />

concrete or block work, sealing joint to worktop or wall with<br />

NO 3<br />

mastic sealant.<br />

12.12 Supply and install water mixer for shower, type Hamat, with<br />

chrome lever handle and stand. Price includes connections<br />

to supply water pipes and all accessories needed to<br />

complete the job.<br />

Total of Sanitary System Works carried to Mechanical<br />

summary:<br />

NO 2<br />

13 WATER AND FIRE FIGHTING SYSTEMS<br />

13.1 Supply and install SCH40 galvanized steel pipes<br />

(Seamless type) for domestic cold water and fire fighting<br />

systems, to be connected from the existing main supply<br />

suspended pipes in false ceiling up to copper collectors<br />

and fire hose cabinets, with all necessary fittings like<br />

valves, elbows ,tees, vents, of approved quality. The price<br />

include supports, hangers and dismantling the existing<br />

pipes (where required) as shown on drawings, and as<br />

follows:<br />

13.1.1 size 2" diameter M.R 10<br />

13.1.2 size 1 1/2" diameter M.R 40<br />

13.1.3 size 1 1/4" diameter M.R 110<br />

13.1.4 size 1" diameter M.R 30<br />

13.1.5 size 3/4" diameter M.R 30<br />

13.2 Supply and install SCH40 galvanized steel pipes<br />

(Seamless type) for domestic hot water system, to be<br />

connected from the existing main supply suspended pipes<br />

in false ceiling up to copper collectors, with all necessary<br />

fittings like valves, elbows ,tees, vents, of approved quality.<br />

The price include 13mm vidoflex or Armaflex insulation<br />

rolled by plastic bonds, supports, hangers and dismantling<br />

the existing pipes (where required) as shown on drawings,<br />

and as follows:<br />

13.2.1 size 2" diameter M.R 10<br />

13.2.2 size 1 1/2" diameter M.R 20<br />

13.2.3 size 1 1/4" diameter M.R 30<br />

13.2.4 size 1" diameter M.R 75<br />

13.2.5 size 3/4" diameter M.R 40<br />

13.2.6 size 1/2" diameter M.R 15<br />

13.3 Supply and install cold and hot water copper collectors,<br />

type Tieme or E.A with all necessary fittings, nipples, nuts,<br />

unions, brass fittings adapter, shut off valves on main and<br />

branch pipes.....etc. The price should include supplying and<br />

installing 16mm pexgol plastic pipes with its 25mm plastic<br />

conduits to be connected from the copper collectors<br />

openings up to location of sanitary fixtures outlets<br />

according to plans and engineer’s instructions.<br />

13.3.1 Collector 3/4" diameter (Unit is in collector openings) Open. 10<br />

13.3.2 Collector 1" diameter (Unit is in collector openings) Open. 66<br />

13.4 supply and install metallic painted steel cabinets of<br />

approved quality, including cover with double doors for<br />

domestic water collectors. The cabinets should be<br />

recessed in walls and fixed on wooden frame constructed<br />

in the wall. The sizes of the cabinets are as follows:<br />

13.4.1 80cm X 60cm NO 4<br />

13.4.2 60cm X 60cm NO 2<br />

13.5 Supply and install Halon Powder fire extinguisher cylinders,<br />

of approved quality. The price includes all accessories and<br />

fittings needed for installation and fixing on wall. The<br />

capacities of cylinders are as follows:<br />

11


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

13.5.1 6 kg Capacity NO 2<br />

13.5.2 3 kg Capacity NO 3<br />

13.6 Supply and install 80*80*30 cm steel fire hose reel cabinet,<br />

25mm diam., mounted on swinging reel, an angle isolation<br />

valve inside the cabinet, a jet nozzle with an incorporated<br />

cock, and 25m long textile hose. Each cabinet should be<br />

supplied with 3 kg powder fire extinguisher, as shown on<br />

drawings, and approval of supervisor engineer.<br />

NO 2<br />

Total of Water and Fire Fighting System Works carried<br />

to Mechanical summary:<br />

14 CENTRAL HEATING SYSTEM<br />

14.1 Dismantle all the existing central heating pipes networks<br />

and radiators distributed in all spaces and rooms in internal<br />

medicine ward and X-Ray Departments with all accessories<br />

and fittings as per engineer's instructions and keep safe in<br />

hospital store (where possible).<br />

14.2 Supply, install and test cast iron radiator, type Chappee, or<br />

E.A , of size 68cm, 3 section in depth (68/3). The price<br />

includes all necessary fittings, i.e shutt off and control<br />

valves, vents, hangers, reducers, chrome nipples, gaskets,<br />

plastic covers on nipples and whatever to complete the job,<br />

all is according to specifications, drawings and approval of<br />

supervisor engineer.<br />

14.3 Supply and install black steel of schedule 40 pipes for<br />

heating system, including all required insulation by vidoflex<br />

of 13mm thickness rolled by plastic bonds, sleeves, gate<br />

valves on branch pipes, automatic air vents, gav. hangers<br />

and supports, drain cocks with all required fittings and<br />

connections, all according to drawings, specifications and<br />

approval of supervisor engineer and as follows:<br />

JOB 1<br />

SEC 380<br />

14.3.1 size 1 1/2" diameter M.R 15<br />

14.3.2 size 1 1/4" diameter M.R 50<br />

14.4 Supply and install copper collectors for central heating<br />

system, type Gaicomini or E.A, with all necessary fittings,<br />

nipples, nuts, unions, quick shut off valves on main pipes<br />

and branch pipes, brass fittings adapter, automatic vents<br />

..Etc of approved quality. The price should also supplying<br />

and installing 16mm pexgol plastic pipes with its 25mm<br />

plastic conduits with 5cm thick concrete layer to radiator<br />

outlets, copper elbows recessed in walls and all civil works<br />

needed, all according to drawings and engineer’s<br />

instructions, and as follows:<br />

14.4.1 Collector 11/4" diameter (Unit is in collector openings) EYE 58<br />

14.5 supply and install metallic painted steel cabinets, size<br />

(80*60cm) of approved quality, including cover with double<br />

doors for heating collectors. The cabinets should be<br />

recessed in walls and fixed on wooden frame constructed<br />

in the wall.<br />

NO 3<br />

14.6 Supply only pressure tank of 125 liters capacity, type Reflex<br />

or E.A.<br />

Total of Central Heating System Works carried to<br />

Mechanical summary:<br />

NO 1<br />

12


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

15 VENTILATION SYSTEM<br />

15.1 Supply and install ducted outdoor centrifugal exhaust and<br />

fresh air fans, type Wood, S&P or EA. The price includes<br />

vibration isolators, metallic steel base, galvanized adapter,<br />

flexible connection, insect mesh at fan outlet of fan and all<br />

accessories needed for installation and commissioning.<br />

The price shall also include electrical and control cables<br />

and connections to main distribution board, all according to<br />

drawings and engineer’s instructions. The fan capacity is<br />

as follows:<br />

15.1.1 * 950 L/s Air Flow @ 0.8" Static pressure NO 1<br />

15.1.2 * 750 L/s Air Flow @ 0.8" Static pressure NO 1<br />

15.1.3 * 560 L/s Air Flow @ 0.5" Static pressure NO 1<br />

15.2 Supply and install ducted in-line exhaust fan, type Wood,<br />

S&P or EA. The price includes vibration isolators,<br />

galvanized adapter, flexible connection and all accessories<br />

needed for installation and commissioning. The price shall<br />

also include outdoor rain water gravity grilles with insect<br />

mesh and shutter according to the sizes shown on<br />

drawings, and also electrical and control cables and<br />

connections to main distribution board, all according to<br />

drawings and engineer’s instructions. The fans capacities<br />

are as follows:<br />

15.2.1 * 135 L/s Air Flow @ 0.2" Static pressure NO 2<br />

15.2.2 * 120 L/s Air Flow @ 0.2" Static pressure NO 1<br />

15.2.3 * 100 L/s Air Flow @ 0.2" Static pressure NO 1<br />

15.3 Supply, install and commission window and wall type<br />

exhaust air fan, type Wood, S&P or E.A, with automatic<br />

shutter. The price includes openings in walls or windows,<br />

electrical wirings and connections to main distribution board<br />

according to engineer’s instructions and as follows:<br />

15.3.1 · 25 L/s Air Flow NO 1<br />

15.3.2 · 40 L/s Air Flow (suitable for duct connection) NO 1<br />

15.3.3 · 60 L/s Air Flow NO 1<br />

15.3.4 · 75 L/s Air Flow NO 1<br />

15.3.5 · 100 L/s Air Flow NO 1<br />

15.4 Supply and install galvanized metal sheet duct, with<br />

thickness according to ASHRAE Standards, for exhaust<br />

and fresh air system. The price includes all joints, sealant<br />

compound, fire retardant sealant and all necessary<br />

accessories, dampers (where required), splitter dampers,<br />

galvanized hangers, and hooks.<br />

M2 150<br />

15.5 Supply and install white anodized Aluminum, of approved<br />

quality, exhaust and fresh air grilles, type Cooling Industry<br />

or E.A, with registers. The price includes galvanized<br />

adapter, opening in false ceiling or gypsum boards, and<br />

duct flexible connection of size as shown on the drawings.<br />

The sizes of grilles are as follows:<br />

15.5.1 * 60cm X 15cm NO 2<br />

15.5.2 * 55cm X 15cm NO 3<br />

15.5.3 * 45cm X 15cm NO 7<br />

15.5.4 * 35cm X 15cm NO 3<br />

15.5.5 * 23cm X 23cm NO 15<br />

15.5.6 * 15cm X 15cm NO 2<br />

15.6 Supply and install white anodized Aluminum, of approved<br />

quality, fresh air intake louvers, type Cooling Industry or<br />

E.A, with insect mesh and filter. The price includes<br />

galvanized adapter, opening in walls and connection to<br />

fresh air duct as shown on the drawings. The sizes of<br />

grilles are as follows:<br />

15.6.1 * 55cm X 35cm<br />

Total of Ventilation System Works carried to<br />

Mechanical summary:<br />

NO 2<br />

13


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

16 AIR CONDITIONING SYSTEM<br />

16.1 Supply, install and commission outdoor Variable<br />

Refrigerant Flow (VRF) heat pump air conditioning sets<br />

based on refrigerant R410, type Daikin, Toshiba or E.A,<br />

consisting of two units (2 X 20 kW) cooling capacity and (2<br />

X 22 kW) heating capacity. The price include control<br />

system, steel bases, gas pipes network from outdoor units<br />

till the indoor units located in the X-Ray department, in<br />

addition to headers and pipes branches and all accessories<br />

needed to complete the job. The price shall also include<br />

electrical wirings and connection to main distribution<br />

boards.<br />

16.2 Supply, install, and commission indoor VRF air conditioning<br />

units, type Daikin, Toshiba or E.A, decorative type,<br />

complete with remote control, drain pipes to floor drains,<br />

builders work, electrical wirings and connections to main<br />

distribution boards, all according to drawings,<br />

specifications, and approval of supervisor engineer:<br />

SET 1<br />

16.2.1 * 7 kW cooling Cap. & 330 L/s Air Flow NO 2<br />

16.2.2 * 5.2 kW cooling Cap. & 280 L/s Air Flow NO 3<br />

16.2.3 * 2.6 kW cooling Cap. & 150 L/s Air Flow NO 3<br />

16.3 Supply, install, and commission indoor VRF air conditioning<br />

units, type Daikin, Toshiba or E.A, ducted concealed type,<br />

complete with copper pipes connections, acoustic<br />

insulation adapter between the units and ducts, room<br />

thermostat, drain pan and connections to floor drains,<br />

supports and hangers, builders work, flexible connections,<br />

connections with supply and fresh air duct, electrical<br />

wirings and connections to main distribution boards, all<br />

according to drawings, specifications, and approval of<br />

supervisor engineer, as follows:<br />

16.3.1 * 14 kW cooling Cap. & 540 L/s Air Flow NO 2<br />

16.4 Supply, install, and commission ducted mini-central heat<br />

pumps split units, type Daikin, Toshiba or E.A. The price<br />

includes all accessories and fittings needed for installation<br />

and commissioning, flexible connections, connection of<br />

drain pipe, acoustic insulation adapter between the units<br />

and ducts, vibration isolators, hangers and supports, high<br />

performance washable filters, wall mounted thermostat<br />

(three fan speeds – summer/winter changeover –<br />

temperature setting module), drain pan, insulated copper<br />

pipes, metallic steel base for outdoor units and all electrical<br />

wiring and control cable, in addition to connection to MDB.<br />

Rate shall also include openings in walls through sleeves<br />

of good quality, and refilling works:<br />

16.4.1 10 kW Cooling Capacity & 380 L/s Air Flow NO 1<br />

16.5 Supply and install galvanized metal sheet rectangular duct,<br />

with thickness according to ASHRAE Standards, for air<br />

conditioning system. The price includes thermal external<br />

insulation (1" thick, 24kg/m 3 density), all joints, sealant<br />

compound, fire retardant sealant, dampers (where<br />

required), splitter dampers, galvanized hangers, and<br />

M2 50<br />

hooks.<br />

16.6 Supply and install white anodized Aluminum, of approved<br />

quality, 4-way supply air diffusers, type Cooling Industry<br />

E.A, with registers. The price includes galvanized adapter,<br />

opening in false ceiling or gypsum boards, and duct<br />

flexible connection of size as shown on the drawings. The<br />

sizes of grilles are as follows:<br />

16.6.1 * 30cm X 30cm NO 8<br />

14


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

16.7 Supply and install white anodized Aluminum, of approved<br />

quality, return air grilles, type Cooling Industry or E.A. The<br />

price includes opening in false ceiling or gypsum boards.<br />

The sizes of grilles are as follows:<br />

16.7.1 * 60cm X 60cm NO 1<br />

16.7.2 * 30cm X 30cm<br />

Total of Air Conditioning System Works carried to<br />

Mechanical summary:<br />

NO 1<br />

17 MEDICAL GAS SYSTEM<br />

17.1 Supply and install area valve control box for medical<br />

oxygen and vacuum, including 2-full port, 3 parts shut off<br />

valves which controls the supply of oxygen or vacuum<br />

through the pipe lines, and line pressure and vacuum<br />

gauges. The area valves control boxes should also include<br />

an emergency external supply port, equipped with disk and<br />

clutch mechanism for quick plug-in connection of the<br />

emergency external supply source.<br />

NO 1<br />

17.2 Supply and install local area pressure and vacuum alarm<br />

box; local audio-visual pressure alarm box for medical<br />

oxygen and vacuum to indicate pressure and vacuum<br />

failures by means of green LED, red LED, operated by<br />

means of one central PC card and switches, recessed type<br />

with anodized aluminum panel.<br />

17.3 Supply and install of factory preassembled bed head unit<br />

for two beds, according to CE-0473, EN-46001, ISO9001<br />

encompassing extruded aluminum duct system, with four<br />

cavities, three of which are directly accessed using snap-on<br />

covers. Supply electrical and lighting service, as well as<br />

medical gas service. The gas outlets should be installed in<br />

a separate compartment. The number of electrical circuits,<br />

apart of the low voltage circuit, should be two, main lines<br />

power circuit and lighting circuit, each connected to a<br />

separate terminal at the main special electrical connection<br />

compound in the bed-head unit.<br />

NO 1<br />

NO 11<br />

Two oxygen outlet<br />

Two vacuum outlet<br />

Four electrical sockets, main line<br />

Two potential grounding sockets<br />

Indirect Light<br />

Direct Light<br />

Cutt-off switch for direct-indirect lights<br />

Two telephone sockets<br />

preparation for nurse call sockets<br />

17.4 Ditto, but for one head-Bed Unit. NO 1<br />

17.5 Supply, install, test and commission connect to the served<br />

terminals, phosphorous de-oxidized non-arsenical copper<br />

(C106) to BS 1172 pipes complete with, such as, but not<br />

limited to, fittings, valves, supports, brackets, etc., taking<br />

into consideration of all safety prepotions that must be<br />

applied to avoid damage of pipes or contaminations. The<br />

price also include different gas ID marks & rubber ceiling<br />

between band & pipes, all according to drawings and<br />

engineer's instruction. The sizes of the pipes are as follows:<br />

17.5.1 1 1/8'' diameter (O.D) M.R 60<br />

17.5.2 7/8'' diameter (O.D) M.R 75<br />

17.5.3 5/8'' diameter (O.D) M.R 110<br />

17.5.4 3/8'' diameter (I.D) M.R 80<br />

Total of Medical Gas System Works carried to<br />

Mechanical summary:<br />

15


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

Section III - Electrical Works<br />

18 Lighting<br />

18.1 Light Point:-<br />

Supply, install, test and commission a complete indoor ,<br />

outdoor lighting point including all conductors, cables,<br />

conduits (PVC or galvanized), switches (type Legrand<br />

Mosaic Cross decorative plates range modular components<br />

and self-supporting plates or equal approved), boxes,<br />

ceiling rose, flexible connection and all other accessories,<br />

from appropriate distribution board to lighting point, as<br />

specified and detailed on drawings and the Engineer's<br />

instructions.<br />

18.2 Light Fixture:-<br />

Supply, install, test and commission complete lighting<br />

Fixtures, including all supports, lamps, connections,<br />

suspensions, clamps, capacitors, internal connections,<br />

conductors, bridges, trenching and all other accessories<br />

necessary to provide a complete fittings with all terminals<br />

according to specifications, drawings and the Engineer's<br />

instructions.<br />

18.2.1 TYPE A : 2X26w recessed low energy compact fluorescent<br />

cat2 louver type Thorn or equal approved.<br />

18.2.2 TYPE B : 2X26w recessed low energy compact fluorescent<br />

cat2 louver type Thorn or equal approved.<br />

18.2.3 TYPE C: 2X13w recessed low energy compact fluorescent<br />

with glass IP44 type Thorn or equal approved.<br />

18.2.4 As type A but with non-maintained 3HR conversion packs<br />

integrated into lighting fittings throughout, the batteries and<br />

inverter gear shall be self contained in the emergency<br />

lights. Batteries shall be sealed nickel cadmium or nickel<br />

meta-hydride type with life expectancy of 5 year min.<br />

18.2.5 As type B but with non-maintained 3HR conversion packs<br />

integrated into lighting fittings throughout, the batteries and<br />

inverter gear shall be self contained in the emergency<br />

lights. Batteries shall be sealed nickel cadmium or nickel<br />

meta-hydride type with life expectancy of 5 year min.<br />

18.2.6 As type C but with non-maintained 3HR conversion packs<br />

integrated into lighting fittings throughout, the batteries and<br />

inverter gear shall be self contained in the emergency<br />

lights. Batteries shall be sealed nickel cadmium or nickel<br />

meta-hydride type with life expectancy of 5 year min.<br />

NO 153<br />

NO 6<br />

NO 12<br />

NO 31<br />

NO 2<br />

NO 3<br />

NO 10<br />

18.2.7 TYPE D : 2X36W high frequency recessed light fixture with<br />

prismatic diffuser type Cooper or equal approved.<br />

NO 64<br />

18.2.8 As type D: but with non-maintained 3HR conversion packs<br />

integrated into lighting fittings throughout, the batteries and<br />

inverter gear shall be self contained in the emergency lights<br />

batteries shall be sealed nickel cadmium or nickel metahydride<br />

ty<br />

NO 15<br />

18.2.9 As type D: but with special lamp for dark room NO 4<br />

18.2.10 TYPE E: 1x8W Self contained, recessed ceiling mounted<br />

edge-lit double sided exit sign for maintained emergency<br />

lighting of 3 hour duration.<br />

NO 4<br />

18.2.11 TYPE F: 2x9 watt surface mounted luminary with opal<br />

diffuser type Thorn, RZB or equal approved.<br />

NO 4<br />

18.2.12 TYPE G : 2X36W Waterproof fluorescent with acrylic<br />

diffuser IP65 type Thorn or equal approved.<br />

Total of Lighting System works carried to Electrical<br />

summary:<br />

NO 2<br />

16


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

19 Power System Works<br />

19.1 Main Feeder:-<br />

Supply, install, test and commission 600/1000V XLPE<br />

copper cables including glands, cable ties, labeling, and all<br />

associated accessories according to the drawings,<br />

specifications and relevant codes of practice and highest<br />

prevailing engineering standards, for the following:<br />

19.1.1 3 X 150 + 70 mm 2 + 150 mm 2. M.R 35<br />

19.1.2 3 X 35 + 16 mm 2 + 35 mm 2. M.R 40<br />

19.1.3 5 X 25 mm 2. M.R 75<br />

19.1.4 5 X 10 mm 2 M.R 24<br />

19.1.5 5 X 6 mm 2 M.R 20<br />

19.2 Distribution Boards:<br />

Supply, install, test and commission complete main<br />

distribution board inclusive of all circuit breakers type<br />

Moeller or equal approved for outing and incoming cables,<br />

bus bars and their coupling unit, casing spaces for cables,<br />

cable clamps/terminals, cable shoes, protection equipment,<br />

as required to form a complete unit for. All shall be in<br />

accordance with the drawings, specification, the codes of<br />

practice and highest prevailing standards of engineering.<br />

19.2.1<br />

The Contractor shall submit detailed shop drawings for the<br />

board to take approval from the Engineer before<br />

manufacturing.<br />

DB-X-RAY NO 1<br />

19.2.2 DB-IMW NO 1<br />

19.3 Earthing System:-<br />

Supply, install, test and commission a complete ring<br />

grounding system for mechanical plants and all big metallic<br />

masses, etc., including all conductors, copper bars, clamps,<br />

conduits fixing etc., all in accordance with specifications,<br />

drawings and codes of practice.<br />

L.S 1<br />

19.4 Sub-Installation:<br />

Supply, install, test, number and commission a complete<br />

single phase single socket outlets, including all conductors,<br />

cables, conduits, boxes, sockets outlets (type Legrand<br />

Mosaic Cross decorative plates range modular components<br />

and self-supporting plates or equal approved), and all<br />

connections between the appropriate distribution board to<br />

the terminal point, as specified and as detailed on<br />

NO 66<br />

drawings:<br />

19.4.1 Supply, install, test and commission as per item 1, but 13A<br />

single phase double socket outlets.<br />

NO 4<br />

19.4.2 Supply, install, test and commission as per item 1, but 13A<br />

single phase water proof socket outlets.<br />

NO 15<br />

19.4.3 Supply, install, test and commission as per item 1, but 16A<br />

isolating switch for fan coil.<br />

NO 8<br />

19.4.4 Supply, install, test and commission as per item 1, but 16A<br />

3 phase isolating switch IP65.<br />

NO 1<br />

19.4.5 Supply, install, test and commission as per item 1, but 63A<br />

isolating switch IP65.<br />

NO 1<br />

19.4.6 Supply, install, test and commission as per item 1, but 16A<br />

single phase socket outlets for exhaust fan with indication<br />

lamp.<br />

NO 1<br />

19.4.7 Supply, install Modular flush floor service outlet box<br />

300x200x80mm, three compartments, including double<br />

socket outlet, RJ45 data socket outlet, RJ11 telephone<br />

socket outlet type Legrand or equal approved..<br />

NO 1<br />

19.4.8 Supply, install, test and commission a stainless steel hand<br />

dryer, automatic type, operated by photo cell, surface type,<br />

AC supply, 1500 W, 220V, 50Hz, Including cables,<br />

conduits, boxes and all other accessories from appropriate<br />

distribution board to the hand dryer as specified and<br />

detailed on drawings.<br />

NO 4<br />

17


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

19.4.9 Supply, install, test and commission hot deep galvanized<br />

steel perforated cable tray, complete with all mounting<br />

accessories, tees, reducers, covers, elbows, etc. as shown<br />

on the drawings and specification for the following:<br />

19.4.10 30cm wide M.R 72<br />

19.5 Bed Head Unit<br />

Supply, install, test and commission a complete electrical<br />

point for units including conductors, conduits, accessories,<br />

boxes, wiring interconnections, earthing, etc., for complete<br />

workable unit. Point consist of lighting point, power<br />

receptacles points, telephone point, nurse call point, as<br />

specified and as detailed on drawings.<br />

NO 12<br />

Total of Power System works carried to Electrical<br />

summary:<br />

20 Telephone & Computer Networks Systems<br />

20.1 Telephone System:<br />

20.1.1 Supply, install, test and commission complete telephone<br />

point including all conduits, boxes (flush or surface<br />

mounted), cabling (Cat5e 4 pair unscreened) type Teldor,<br />

RG 45 Cat5e outlet type Legrand or equal approved.<br />

According to specifications, and drawings. All Telephone<br />

outlets shall be numbered in sequence.<br />

20.1.2 Supply, install, test and commission telephone terminal<br />

boards (TTB) complete with all accessories needed for<br />

complete work, incoming cables, as specified and as<br />

detailed on drawings for the followings:<br />

NO 6<br />

a 30 pairs L.S 1<br />

b 20 pairs L.S 1<br />

20.2 Computer Networks Systems:<br />

20.2.1 Supply, install, connect and commission complete data<br />

point including all conduits, boxes (flush or surface<br />

mounted), cables STP cat6 type Teldor, RG 45 Cat 6 outlet<br />

type 3M or equal approved. According to specification and<br />

drawings. All Data outlets shall be numbered in sequence.<br />

NO 5<br />

20.2.2 Supply, install, test, and commissioning Data Panel(DP)<br />

18U including 1 air patch panels,1 patch panels type 3M,<br />

power strip all needed internal cables, connections and all<br />

accessories to complete the work. as specified and as<br />

detailed on drawings, and to the Engineer's instructions.<br />

20.2.3 Supply, install, test and commission complete satellite point<br />

including all conduits, cable, conduit accessories, boxes<br />

outlet type Legrand or equal approved. According to<br />

specifications, and drawings. All outlets shall be numbered<br />

in sequence.<br />

20.2.4 Supply, install, test and commission hot deep galvanized<br />

steel perforated cable tray, complete with all mounting<br />

accessories, tees, reducers, covers, elbows, etc. as shown<br />

on the drawings and specification for the following:<br />

20cm wide.<br />

Total of Telephone & Computer Networks Systems<br />

works carried to Electrical summary:<br />

18<br />

L.S 1<br />

NO 8<br />

M.R 42


ATLAS # 14163<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Item DESCRIPTION Unit QTY Unit Price Total Amount<br />

21 Fire Alarm System<br />

21.1 Supply, install, test and commission new fire alarm loop,<br />

this loop shall be connected to existing FACP (the existing<br />

fire alarm panel Type Edward) including commission FACP,<br />

all conduits, boxes, cabling type Teldor, According to<br />

specifications.<br />

21.2 Supply, install, test and commission a fire alarm photooptical<br />

smoke detector including all conduits fixing, boxes,<br />

and cables (type Teldor or equal approved), . According to<br />

specification and drawings. Type Edward<br />

21.3 Supply, install, test and commission a fire-alarm heatdetector<br />

including all conduits fixing, boxes, and cables.<br />

According to specification and drawings.<br />

21.4 Supply, install, test and commission a fire alarm electronic<br />

sounder Banshee type including all conduits fixing, boxes,<br />

and cables. According to specification and drawings.<br />

21.5 Supply, install, test and commission a flush mounted fire<br />

alarm manual pull station including all conduits fixing,<br />

boxes, and cables. According to specification and<br />

drawings.<br />

Total of Fire Alarm System works carried to Electrical<br />

summary:<br />

22 Nurse Call System:<br />

22.1 Supply, install, test and commission 50 call master station<br />

nurse call including conduits, conduit accessories, boxes,<br />

cabling, etc., all in accordance with drawings and<br />

specifications and engineer instructions type Aiphone or<br />

equal approved<br />

22.2 Supply, install, test and commission central control unit<br />

including power supply, conduits, conduit accessories,<br />

boxes, cabling, etc., all in accordance with drawings and<br />

specifications and engineer instructions type Aiphone or<br />

equal approved.<br />

22.3 Supply, install, test and commission wall mounted single<br />

jack including conductors, and/or cables, conduits, boxes,<br />

etc., from the appropriate nurse call panel to the point the<br />

price includes also beside call switch in accordance with<br />

the specifications and drawings.<br />

22.4 Supply, install, test and commission as per item 1, but dual<br />

jack.<br />

22.5 Supply, install, test and commission as per item 1, but<br />

corridor lamp with red lamp<br />

22.6 Supply, install, test and commission as per item 1, but Zone<br />

lamp<br />

22.7 Supply, install, test and commission as per item 1, but<br />

emergency bathroom pull cord.<br />

Total of Nurse Call System works carried to Electrical<br />

summary:<br />

23 Public Address System<br />

23.1 Connect, test and commission the new loudspeaker to<br />

existing system including all conduits, boxes, cabling ,<br />

According to specifications and engineer instructions<br />

23.2 Supply, install, test and commission the 6 watt flush-mount<br />

ceiling loudspeaker with matching transformer.<br />

Total of Public Address System works carried to<br />

Electrical summary:<br />

19<br />

L.S 1<br />

NO 32<br />

NO 2<br />

NO 3<br />

NO 3<br />

L.S 1<br />

L.S 1<br />

NO 1<br />

NO 11<br />

NO 9<br />

NO 1<br />

NO 2<br />

L.S 1<br />

NO 6


ATLAS # 14163 Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

Bill Description Total<br />

Section I Civil Works Summary<br />

1 Demolish and Removal Works<br />

2 Block work<br />

3 Plastering Works<br />

4 Tile Finishing Works<br />

5 False Ceiling Works<br />

6 Painting Works<br />

7 Carpentary & Joinery Works<br />

8 Insulatuion Works<br />

9 Glass Works<br />

10 Metal Works<br />

11 Sand-blasting Works<br />

Total of Civil Works<br />

Section II Mechanical Works Summary<br />

12 Sanitary fixture and their Accessories:<br />

13 Water & Fire Fighting Works<br />

14 Central Heating Works<br />

15 Ventalation Works<br />

16 Air Conditioning Works:<br />

17 Medical Gas Supply:<br />

Total of Mechanical Works<br />

Section III Electrical Works Summary<br />

18 Lighting System Works<br />

19 Power System Works<br />

20 Telephone & IT System<br />

21 Fire Alarm System<br />

22 Nurse Calling System<br />

23 Public Address System<br />

Total of Electrical Works<br />

NET TOTAL SUM (in words ) :<br />

SIGNED AND SEALED :<br />

AUTHOURIZED PERSON :<br />

TITLE :<br />

SIGNATURE :<br />

DATE :<br />

Summary of Part 2<br />

Total of Part 2 (Excluding VAT)<br />

Discount %<br />

Discount Amount<br />

Net Total - Part 2 (Excluding VAT)


ATLAS # 14163 <strong>Alia</strong> Hospital<br />

Item Description Total<br />

Bill 1<br />

Bill 2<br />

Part 1: Construction of the remaining works at <strong>Alia</strong> Hospital 2nd floor<br />

Part 2: Rehabilitation Works For <strong>Alia</strong> Hospital<br />

NET TOTAL SUM (in words ) :<br />

SIGNED AND SEALED :<br />

AUTHOURIZED PERSON :<br />

TITLE :<br />

SIGNATURE :<br />

DATE :<br />

Grand Summary (Part 1 + Part 2)<br />

Grand Total Part 1 & Part 2 (Excluding VAT)<br />

Discount %<br />

Discount Amount<br />

Net Total Part 1 & Part 2 (Excluding VAT)