3.3.4.2.2.2 Outgoing<br />

Global parameters<br />

General Reference Guide <strong>eWON</strong> Configuration<br />

Figure 34: Modem Outgoing Global setup page<br />

Control Description<br />

Dial and connection timeout<br />

Enable compression<br />

Delay between dialout retries<br />

Idle time before hanging up<br />

Max outgoing call duration<br />

Hang up if no outgoing action<br />

after<br />

Time allowed for the whole establishment of the PPP link to be up. This means modem call,<br />

modem negotiation, PPP negotiation and logon. This time includes all trials on each server.<br />

This is thus a global time.<br />

Enable the compression negotiation request when an outgoing call occurs. This includes all<br />

compression modes known by the <strong>eWON</strong> PPP engine (Van Jacobson, header<br />

compression,…).<br />

In case of an unsuccessful attempt to establish the outgoing communication, then <strong>eWON</strong> will<br />

retry to establish it again. This parameter will allow you to define the amount of time the<br />

<strong>eWON</strong> will wait to try and establish again the outgoing action.<br />

<strong>eWON</strong> will hang up after this amount of time if no data transfer occurs on the PPP link<br />

between the <strong>eWON</strong> (any type of PPP packet) and a remote host (Computer).<br />

Select between Check incoming or Check outgoing to select the<br />

monitored traffic.<br />

Note: this is the same parameter as for incoming connection.<br />

The maximum amount of time of the outgoing call. When this amount of time is reached, then<br />

the <strong>eWON</strong> stops the PPP communication.<br />

When a PPP link is triggered by an outgoing action (not by DialOnDemand), you can force the<br />

interruption of the line immediately after the actions (set 0) or let the PPP active for an amount<br />

of time (set >0). The PPP link will be shut down after the x minutes even if transfers are in<br />

progress.<br />

The Idle time before hanging up is always active.<br />

Table 35: outgoing calls configuration controls<br />

RG-001-0-EN ver 1.10 <strong>eWON</strong>® - 09/09/2010 - ©<strong>eWON</strong> sa Page 41