Temperature Relays and MINIKA®, Mains Monitoring, Digital Panelmeters MINIPAN®, Switching Relays and Controls<br />

<strong>Operating</strong> <strong>Instructions</strong> <strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong><br />

- Frequency- and Revolutions relay<br />

ZIEHL industrie – elektronik GmbH + Co KG<br />

Daimlerstraße 13, D – 74523 Schwäbisch Hall<br />

+ 49 791 504-0, info@<strong>ziehl</strong>.<strong>de</strong>, www.<strong>ziehl</strong>.<strong>de</strong><br />

updated: 121024 Sc<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 1 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


Table of contents<br />

1 Application and short <strong>de</strong>scription ......................................................................................................... 3<br />

2 Overview of functions ............................................................................................................................ 3<br />

3 Connecting diagram ............................................................................................................................... 4<br />

4 Display and operation parts ................................................................................................................... 4<br />

5 Programs................................................................................................................................................. 4<br />

6 Important Information ............................................................................................................................ 5<br />

7 Installation .............................................................................................................................................. 6<br />

8 Putting into operation ............................................................................................................................ 6<br />

8.1 Display mo<strong>de</strong> ................................................................................................................................. 6<br />

8.2 Menu mo<strong>de</strong> (Decimal point behind the last digit ON) ..................................................................... 6<br />

8.3 Parameter setting mo<strong>de</strong> (Decimal point behind the last digit BLINKS) ........................................... 6<br />

8.4 Indications of the digital display ..................................................................................................... 9<br />

9 Operation .............................................................................................................................................. 10<br />

9.1 Program 1: Pr1 / Speed Monitoring ............................................................................................. 10<br />

9.2 Program 2: Pr2 / Frequency Monitoring ....................................................................................... 11<br />

10 Factory setting ...................................................................................................................................... 12<br />

11 Error search and measures ................................................................................................................. 12<br />

12 Technical data ...................................................................................................................................... 13<br />

13 Type V4 ................................................................................................................................................. 15<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 2 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


1 Application and short <strong>de</strong>scription<br />

The <strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> is a speed-monitor, a frequency-monitor and a measuring-transducer (<strong>FR</strong><strong>MU</strong> only) in one<br />

<strong>de</strong>vice.<br />

2 limits with 1 relay each can be programmed for un<strong>de</strong>r- or overspeed or un<strong>de</strong>r- or over-frequency or each<br />

monitoring a range (window min/max).<br />

The input for monitoring of speed can evaluate signals from proximity-sensors 2- or 3-wire, npn or pnp. The<br />

display can be scaled. Thus the real speed of a shaft can be displayed, even though there are several<br />

pulses per revolution, e.g. from a cogwheel.<br />

Application as Frequency-Relay:<br />

Monitoring of frequencies in mains 16 2/3 to 400 Hz on maintaining a range (min/max).<br />

Measuring input voltage (f-in) - AC 80...440 V / AC 20…200 V (Or<strong>de</strong>r-number U226134 + U226135)<br />

- AC 210...830 V / AC 110…300 V (Or<strong>de</strong>r-number U226138)<br />

Application as Speed-Relay:<br />

Monitoring of overspeed or un<strong>de</strong>rspeed, each with pre-alarm and alarm, monitoring of maintaining a range<br />

(min/max) or monitoring of stop at machines and equipment, e.g. at conveyors, escalators or lifts or for<br />

monitoring drive-belts.<br />

Applications as Measuring Transducer: (<strong>FR</strong><strong>MU</strong> only)<br />

In addition the <strong>FR</strong><strong>MU</strong><strong>1000</strong> can be used as a measuring-transducer to convert the input-signal into a<br />

standard-signal 0/4-20 mA or 0-10 V.<br />

2 Overview of functions<br />

General:<br />

� Setting in Hz or 1/min<br />

� 5-digit display<br />

� 2 limits / 2 relays<br />

� Programmable for each relay:<br />

- monitoring of min.-, max.- or window<br />

- hysteresis<br />

- autoreset or reclosing lock<br />

- <strong>de</strong>lay-time for switching and switching back down to 50 ms<br />

- operating- or closed-current-mo<strong>de</strong><br />

� LEDs for state of relay and unit (Hz or 1/min)<br />

� Storage of min- und max-values of the inputs<br />

� Easy setting with 3 buttons<br />

� Enable-input (E1-E2 closed = monitoring not active / open = monitoring active)<br />

� Co<strong>de</strong> lock against manipulation of settings<br />

� Universal power supply unit AC/DC 24...240 V<br />

� Terminals pluggable<br />

� Analog output DC 0/4-20 mA or DC 0-10 V,<br />

freely scaleable (with isolation to frequency-input “f – in”), <strong>FR</strong><strong>MU</strong> only<br />

Frequency:<br />

� Measuring input voltage - AC 80...440 V / AC 20…200 V (Or<strong>de</strong>r-number U226134 + U226135)<br />

- AC 210...830 V / AC 110…300 V (Or<strong>de</strong>r-number U226138)<br />

� Measuring-input for ZIEHL frequency-sensor STWA 1 FFH<br />

� Monitoring of frequency of own supply-voltage<br />

� Monitoring range 10...500 Hz<br />

� Resolution of display 0,01 Hz<br />

Speed:<br />

� Monitoring range 5...99999 1/min<br />

� Display can be scaled<br />

� Measuring input for proximity switch, 2- or 3-conductor, PNP or NPN<br />

� Start-up-<strong>de</strong>lay programmable<br />

� Enable-input (E1-E2 closed = monitoring not active / open = monitoring active)<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 3 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


3 Connecting diagram<br />

4 Display and operation parts<br />

1 LEDs relay state<br />

2 Digital display, 5 digits<br />

3 LED speed measuring (1/min)<br />

4 LED frequency measuring (Hz)<br />

5 Pushbutton up<br />

6 Pushbutton set/reset<br />

7 Pushbutton down<br />

5 Programs<br />

2 programs (Pr) can be selected. Due to these Programs the <strong>de</strong>vice can be easily adapted to the<br />

application.<br />

Choose the Program fitting to your application and after that change the parameters! When changing the<br />

program all parameters are reseted upon "factory setting".<br />

(see chart " factory setting")<br />

Selecting the program:<br />

Keep the button "Set" pressed for 10 s when applying the supply voltage. Then program (Pr 1 ... Pr 2)<br />

can be choosen with the pushbuttons up/down and confirmed with set.<br />

Pr 1 = Revolutions control (factory setting) (1/min)<br />

Pr 2 = Frequency control (Hz)<br />

1) <strong>FR</strong><strong>MU</strong> only<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 4 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


6 Important Information<br />

DANGER!<br />

Hazardous voltage!<br />

Will cause <strong>de</strong>ath or serious injury. Turn off and lock out all power<br />

supplying this <strong>de</strong>vice before working on this <strong>de</strong>vice.<br />

To use the equipment flawless and safe, transport and store properly, install and start professionally and<br />

operate as directed.<br />

Only let persons work with the equipment who are familiar with installation, start and use and who have<br />

appropriate qualification corresponding to their function. They must observe the contents of the<br />

instructions manual, the information which are written on the equipment and the relevant security<br />

instructions for the setting up and the use of electrical units.<br />

The equipments are built according to DIN / EN and checked and leave the plant according to security in<br />

perfect condition. If, in any case the information in the instructions manual is not sufficient, please contact<br />

our company or the responsible representative.<br />

Instead of the industrial norms and regulations written in this instructions manual valid for Europe, you<br />

must observe out of their geographical scope the valid and relevant regulations of the corresponding<br />

country.<br />

Observe the maximum temperature permissible when installing in switching cabinet.<br />

Make sure sufficient space to other equipment or heat sources. If the cooling becomes<br />

more difficult e.g. through close proximity of apparatus with elevated surface<br />

temperature or hindrance of the cooling air, the tolerable environmental temperature is<br />

diminishing.<br />

!<br />

Attention!<br />

When all relays are programmed in operation current mo<strong>de</strong> (= pick up at alarm), a loss of the<br />

supply voltage or an instrument failure can remain uni<strong>de</strong>ntified. When the relay is applied as<br />

control instrument, the operator must ensure, that this error is recognized by regular<br />

examinations. We recommend to program and accordingly evaluate at least one relay in the<br />

closed-circuit current mo<strong>de</strong>.<br />

Universal power supply<br />

The <strong>de</strong>vice has got a universal power supply, that is suitable for DC- and AC-voltages. Before connecting<br />

the <strong>de</strong>vice to supply-voltage make sure that the connected voltage corresponds with the voltage on the<br />

lateral type on the <strong>de</strong>vice.<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 5 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


7 Installation<br />

The unit can be installed as follows:<br />

� Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715<br />

� With screws M4 for installation on walls or panel. (additional latch inclu<strong>de</strong>d in <strong>de</strong>livery)<br />

Connection according to connection plan or type plate.<br />

8 Putting into operation<br />

Decimal point behind the last digit:<br />

Off = display mo<strong>de</strong>, displays values of measuring inputs<br />

On = menu mo<strong>de</strong>, select the menu items<br />

blinking = parameter setting mo<strong>de</strong><br />

8.1 Display mo<strong>de</strong><br />

Indication of the current measured value<br />

LEDs Relay (K1, K2)<br />

ON = relay picked up<br />

LED Speed (1/min) / Frequency (Hz)<br />

ON = according program selected<br />

Function button UP/DOWN<br />

Push short change into menu mo<strong>de</strong><br />

Push for > 2 s display of the stored MIN- or MAX-<br />

values of the choosen input<br />

Function button SET/RESET<br />

Push for 2 s Reset restart interlock<br />

Push for 4 s display of the choosen program<br />

Push for 10 s display of the software version<br />

8.2 Menu mo<strong>de</strong> (Decimal point behind the last digit ON)<br />

Selection of the menu items for changing the parameters.<br />

Function button UP/DOWN<br />

Push short Selection of menu item; Change into display mo<strong>de</strong><br />

Function button SET/RESET<br />

Push short Change into parameter setting mo<strong>de</strong><br />

8.3 Parameter setting mo<strong>de</strong> (Decimal point behind the last digit BLINKS)<br />

LEDs indicate relays concerned by the parameter setting.<br />

Function button UP/DOWN<br />

Press short/long Changement of parameter value (slow/fast)<br />

Function button SET/RESET<br />

Press short Acceptation of setting and choice of next parameters,<br />

after the last parameter change into menu mo<strong>de</strong><br />

Selecting the inputs (Inpvt):<br />

Choose menu item with up/down until InpVt and type alternate in display.<br />

Here it can be read, which input is selected.<br />

Enter in programming with Set.<br />

Select input with up/down and store with Set.<br />

Multiplier/divisor (Mvlt / div) :<br />

The indicated or limit value is calculated from the formula: input * Mvlt / div<br />

Mean value (SvM):<br />

Valid measured value = mean value from 1...8 (SvM) measuring cycles.<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 6 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


Setting the alarms (AL 1 / AL 2):<br />

Choose menu item with up/down until AL 1 and limit (limit value) alternate.<br />

Here it can be read clearly which limit value is programmed.<br />

Begin to program with set.<br />

Set limit with up/down and store with set. At window monitoring, this value is the lower limit of the<br />

window.<br />

Choose function:<br />

off Alarm OFF, relay is released all the time<br />

•:∆ Overspeed / overfrequency without reclosing lock<br />

•:: Overspeed / overfrequency with reclosing lock. Reset only possible after signal is below the limit<br />

(with hysterisis) and after the switchback-<strong>de</strong>lay. The switchback-<strong>de</strong>lay is indicated with blinking<br />

„A12L“ in the display.<br />

w_r Un<strong>de</strong>rspeed / un<strong>de</strong>rfrequency without reclosing lock<br />

w__ Un<strong>de</strong>rspeed / un<strong>de</strong>rfrequency with reclosing lock. Reset only possible after signal is below the<br />

limit (with hysterisis) and after the switchback-<strong>de</strong>lay. The switchback-<strong>de</strong>lay is indicated with blinking<br />

„A12L“ in the display..<br />

«k Window monitoring without reclosing lock.<br />

«« Window monitoring with reclosing lock. Reset only possible after signal is within the window (with<br />

hysterisis) and after the switchback-<strong>de</strong>lay. The switchback-<strong>de</strong>lay is indicated with „A12L“ in the<br />

display.<br />

ALHi upper limit at window monitoring. Lower limit = AL 1 set limit.<br />

Set Hysteresis<br />

Alarm <strong>de</strong>lay time dAL: An alarm is suppressed for this time, short-time exceeding of the limits does not<br />

cause an alarm.<br />

Switch-back <strong>de</strong>lay doF: Alarms are switched off this time after the signal has returned into good-state.<br />

Function of relay:<br />

r-Closed-current circuit mo<strong>de</strong>. Relay is picked up in GOOD and releases when the limit is excee<strong>de</strong>d =<br />

alarm. Advantage: errors and faults normally cause an alarm. Disadvantage: alarm also when<br />

supply-voltage is switched off and after switching on until the relay has picked up.<br />

A- <strong>Operating</strong>-current mo<strong>de</strong>: relay is released in GOOD state and picks up when the limit is excee<strong>de</strong>d.<br />

No alarm at errors and when supply-voltage is switched off.<br />

Start-up-<strong>de</strong>lay (dEnab):<br />

Monitoring starts this time after switching on the supply-voltage and after opening the enable -input E1-<br />

E2.<br />

Display <strong>de</strong>lay (ddisp):<br />

Defines the rate for updating the display. Set to higher values at nervous display.<br />

Simulation (Si):<br />

Here a measured input signal can be simulated with the buttons up/down. All functions of the <strong>de</strong>vice<br />

work as if this value was at the input. If no button is pressed for 15 minutes the <strong>de</strong>vice automatically<br />

switches back into the display mo<strong>de</strong>.<br />

Co<strong>de</strong>-lock (CodE):<br />

After setting all parameters they can be protected by activating the co<strong>de</strong> lock. After pushing Set, the<br />

display indicates Pin.<br />

Adjust with buttons up/down Pin 00504 (factory setting). After pushing Set, co<strong>de</strong> lock can be<br />

activated or switched off. After pushing Set again, an individual Pin can be selected (write down).<br />

When co<strong>de</strong> lock is activated all parameters can be seen but not be changed anymore.<br />

In case of problems with the co<strong>de</strong> lock (forgotten Pin) the lock can be switched off<br />

and the Pin can be set back to 00504, by pushing button set while connecting the<br />

<strong>de</strong>vice to supply-voltage until Cod / ofF is indicated in the display.<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 7 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


Tips:<br />

- With the pre-setting Pr1 and Pr2 the most important parameters can be set in advance, so that only little<br />

modifications are necessary , e.g. setting of the limits (limit values) for each alarm.<br />

- When the right <strong>de</strong>cimal point in the 7 segment display is on, the display mo<strong>de</strong> has been left, and the<br />

menu items can be chosen with up/down (menu mo<strong>de</strong>).<br />

- When the right <strong>de</strong>cimal point blinks, you are in the parameter setting mo<strong>de</strong> and can change the setting<br />

with up/down.<br />

- After finishing one menu item it is switched automatically on the next one.<br />

- Long pushing on up/down speeds up the changes in the display.<br />

- Pushing button up and down at the same time sets values to zero.<br />

- With reset (press Set/Reset for 2s) the display mo<strong>de</strong> can be reached from every position (exception:<br />

simulation) of the parameter setting mo<strong>de</strong> (the last selected value in is being stored).<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 8 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


8.4 Indications of the digital display<br />

Pr 1 / Pr 2 program number<br />

A1 , A2 alarm 1 , alarm 2 active<br />

A12 alarm 1 and alarm 2 active<br />

+ L alarm locked (locked), „reset“ is necessary.<br />

DEn<br />

remaining time until monitoring is activated<br />

(start-up-<strong>de</strong>lay dEnab is ending)<br />

Inpvt input<br />

U1-U2 frequency input (f - in)<br />

npn three wire proximity-switch NPN<br />

pnp three wire proxy-switch PNP or two wire proxy-switch<br />

mvlt multiplier<br />

div divisor<br />

Svm mean value<br />

AL 1, AL 2 alarm limit (lower limit when monitoring a window)<br />

Fvnc alarm function<br />

off alarm off<br />

•:∆ overspeed / over frequency without reclosing lock<br />

•:: overspeed / over frequency with reclosing lock.<br />

w_r un<strong>de</strong>rspeed / un<strong>de</strong>r frequency without reclosing lock<br />

w__ un<strong>de</strong>rspeed / un<strong>de</strong>r frequency with reclosing lock<br />

«k window monitoring without reclosing lock<br />

«« window monitoring with reclosing lock<br />

alhi upper limit when monitoring a window<br />

H hysterisis<br />

dal switching-<strong>de</strong>lay<br />

doF switch-back-<strong>de</strong>lay<br />

rEl function of relay<br />

r closed-current mo<strong>de</strong>, contacts 11-12 resp. 21-22 close at an alarm<br />

A operating-current mo<strong>de</strong>, contacts 11-14 (21-24) close at an alarm<br />

<strong>de</strong>nab start-up-<strong>de</strong>lay<br />

ddisp display <strong>de</strong>lay<br />

on, oFF on/off<br />

Si simulation<br />

CodE co<strong>de</strong> (pin)<br />

Pin ex works 00504<br />

<strong>FR</strong><strong>MU</strong> only:<br />

ovt analog output<br />

0-10 0...10 V voltage output<br />

0/4-20 0/4...20 mA current output<br />

____ value for 0 V, 0/4 mA at the output<br />

,,,, value for 10 V, 20 mA at the output<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 9 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


9 Operation<br />

9.1 Program 1: Pr1 / Speed Monitoring<br />

Menu mo<strong>de</strong><br />

<strong>FR</strong><strong>MU</strong><br />

only<br />

2 s = Max<br />

2 s = Min<br />

Inpvt<br />

mvlt<br />

div<br />

Svm<br />

AL 1<br />

AL 2<br />

<strong>de</strong>nab<br />

ddisp<br />

ovt<br />

CodE<br />

Display<br />

Si<br />

Typ<br />

Value<br />

Value<br />

Value<br />

Limit<br />

Limit<br />

Value<br />

Value<br />

Typ<br />

on /<br />

oFF<br />

....<br />

Pin<br />

U1-U2<br />

nPn<br />

pnp<br />

00001<br />

00250<br />

00001<br />

00250<br />

00001<br />

00008<br />

00005<br />

...99999<br />

0000.0<br />

...0060.0 s<br />

0000.1<br />

...0002.0 s<br />

oFF<br />

0-10<br />

0-20<br />

4-20<br />

00000<br />

...99999<br />

00000<br />

...09999<br />

Display mo<strong>de</strong><br />

Parameter setting mo<strong>de</strong><br />

fvnc off<br />

____ ,,,,<br />

3x Err<br />

00000<br />

...99999<br />

o.k.<br />

•:±<br />

•::<br />

w_r<br />

w__<br />

«k<br />

««<br />

on<br />

oFF<br />

00000<br />

...99999<br />

Zero Fullscale<br />

3x on / oFF<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 10 / 15 www.<strong>ziehl</strong>.<strong>de</strong><br />

alHi<br />

Pin<br />

00005<br />

...99999<br />

dAL 000.05<br />

..099.99 s<br />

00000<br />

...09999<br />

H<br />

00001<br />

...<strong>1000</strong>0<br />

doF 000.05<br />

..099.99 s<br />

Operation with pushbuttons:<br />

Up<br />

Down<br />

rEL rA<br />

Set<br />

Reset<br />

= >2s Set<br />

Up/down at same time sets values<br />

on zero.<br />

Co<strong>de</strong>-reset = 2 s set while switching<br />

in.<br />

(Pin = 00504)<br />

error messages:<br />

Er 9 = <strong>de</strong>vice error<br />

Err = general error<br />

EEE = superordinated range


9.2 Program 2: Pr2 / Frequency Monitoring<br />

Menu mo<strong>de</strong><br />

<strong>FR</strong><strong>MU</strong><br />

only<br />

2 s = Max<br />

2 s = Min<br />

Inpvt<br />

Svm<br />

AL 1<br />

AL 2<br />

<strong>de</strong>nab<br />

ddisp<br />

ovt<br />

CodE<br />

Display<br />

Si<br />

Typ<br />

1...8<br />

Limit<br />

Limit<br />

Value<br />

Value<br />

Typ<br />

on /<br />

oFF<br />

....<br />

Pin<br />

U1-U2<br />

nPn<br />

pnp<br />

00001<br />

00008<br />

010.00<br />

...500.00<br />

0000.0<br />

...0060.0 s<br />

0000.1<br />

...0002.0 s<br />

oFF<br />

0-10<br />

0-20<br />

4-20<br />

010.00<br />

...500.00<br />

00000<br />

...09999<br />

Display mo<strong>de</strong><br />

Parameter setting mo<strong>de</strong><br />

fvnc off<br />

____ ,,,,<br />

3x Err<br />

000.00<br />

...500.00<br />

o.k.<br />

•:±<br />

•::<br />

w_r<br />

w__<br />

«k<br />

««<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 11 / 15 www.<strong>ziehl</strong>.<strong>de</strong><br />

on<br />

oFF<br />

alHi<br />

Pin<br />

010.00<br />

...500.00<br />

dAL 000.05<br />

..099.99 s<br />

000.00<br />

...500.00<br />

Zero Fullscale<br />

00000<br />

...09999<br />

H<br />

3x on / oFF<br />

000.10<br />

...010.00<br />

doF 000.05<br />

..099.99 s<br />

Operation with pushbuttons:<br />

Up<br />

Down<br />

rEL rA<br />

Set<br />

Reset<br />

= >2s Set<br />

Up/down on same time sets values<br />

on zero.<br />

Co<strong>de</strong>-reset = 2 s set while switching<br />

in.<br />

(Pin = 00504)<br />

error messages:<br />

Er 9 = <strong>de</strong>vice error<br />

Err = general error<br />

EEE = superordinated range


10 Factory setting<br />

In case of programme change all parameters are set back on factory setting.<br />

Menuitem<br />

Parameter<br />

Value<br />

Pr 1 Pr 2<br />

Inpvt Input type PnP U1-U2<br />

mvlt Multiplier 1 -<br />

div Divisor 1 -<br />

svm Mean value 4 4<br />

Alarm 1<br />

AL 1<br />

Alarm 2<br />

AL 2<br />

Limit 1 (lower window limit) 500 48Z00<br />

Fvnc (Function) w_r «k<br />

alHi (upper window limit) - 52Z00<br />

H (Hysterisis) 10 1Z00<br />

dAL (Alarm-<strong>de</strong>lay) 0Z50 0Z10<br />

dof (Switch-back <strong>de</strong>lay) 0Z50 0Z10<br />

rel (Relais function) r r<br />

Limit 2 (lower window limit) 5000 47Z00<br />

Fvnc (Function) •:∆ «k<br />

alHi (upper window limit) - 53Z00<br />

H (Hysterisis) 100 1Z00<br />

dAL (Alarm-<strong>de</strong>lay) 0Z50 0Z10<br />

dof (Switch-back <strong>de</strong>lay) 0Z50 0Z10<br />

rel (Relais function) r r<br />

<strong>de</strong>nab Start-up-<strong>de</strong>lay 2Z0 0Z1<br />

ddisp Display <strong>de</strong>lay 0Z5 0Z5<br />

ovt Type 0-10 0-10<br />

(nur ____ (Zero) 0 0.00<br />

<strong>FR</strong><strong>MU</strong>) ,,,, (Fullscale) 5000 100Z00<br />

Co<strong>de</strong><br />

on / oFF<br />

Pin<br />

off<br />

00504<br />

off<br />

00504<br />

Indication of software version: push „Set“ 10 s in display mo<strong>de</strong>.<br />

11 Error search and measures<br />

My<br />

data<br />

Device cannot be programmed – Co<strong>de</strong> lock<br />

The co<strong>de</strong> lock gives protection against unauthorized manipulation of the <strong>de</strong>vice. When co<strong>de</strong> lock is<br />

activated the parameters can not be changed. The pin can be typed in by the user.<br />

Pin unknown? Make co<strong>de</strong>-reset: When switching in supply-voltage keep pushed button „Set“ for 2 s.<br />

Display shows: "88888"; "CodE"; "oFF"; "88888" release button „Set“.<br />

Co<strong>de</strong> = oFF, Pin = 00504.<br />

Indicated value does not correspond to input signal<br />

Correct program chosen?<br />

Input type (Inpvt) selected correct?<br />

Multiplier and divisor programmed correct when monitoring speed (PR 1)?<br />

Indication „Er9“<br />

Er9 is an internal fault of the <strong>de</strong>vice. Switch off- and on the power-supply.<br />

If after that there still is an error indicated, the unit must be sent to the factory for repair.<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 12 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


12 Technical data<br />

Rated supply voltage Us: AC/DC 24 – 240 V<br />

Tolerance DC 20,4 - 297 V AC 20 - 264 V<br />

Frequency 0, 40...500 Hz, from AC 80 V: 10...500 Hz<br />

Input < 3 W < 10 VA<br />

Relay-output: 2 x 1 Changer (CO)<br />

Switching voltage max. AC 400 V<br />

Switching current max. 5 A<br />

Switching power max. 1250 VA (ohm resistive load)<br />

max. 48 W at DC 24 V<br />

Nominal operating current Ie:<br />

AC15 Ie = 1,25 A Ue = 400 V<br />

Ie = 2 A Ue = 250 V<br />

DC13 Ie = 2 A Ue = 24 V<br />

Recommen<strong>de</strong>d fuse T 3,15 A (gL)<br />

Contact life mechanic 15 x 10 6 Switching cycles<br />

Contact life electrical. 2 x 10 5 Switching cycles at AC 250 V / 3 A<br />

5 x 10 5 Switching cycles at AC 250 V / 2 A<br />

1 x 10 5 Switching cycles at AC 250 V / 0,8 A<br />

Test conditions EN 60255 / EN 60947<br />

Rated impulse voltage 4000 V<br />

- measuring input f-in 4000 V -> Or<strong>de</strong>r-number U226134 + U226135<br />

6000 V -> Or<strong>de</strong>r-number U226138<br />

Contamination level 2<br />

Rated insulation voltage Ui 300 V<br />

- measuring input f-in 300 V -> Or<strong>de</strong>r-number U226134 + U226135<br />

600 V -> Or<strong>de</strong>r-number U226138<br />

On-time 100 %<br />

Permitted ambient air temperature -20 °C ... +60 °C<br />

EN 60068-2-2 dry heat<br />

Interference resistance EN 6<strong>1000</strong>-6-2<br />

Interference transmission EN 6<strong>1000</strong>-6-3<br />

Vibration resistance EN 60068-2-6 2…25 Hz ±1,6 mm<br />

25 ... 150 Hz 5 g<br />

<strong>FR</strong>(<strong>MU</strong>)<strong>1000</strong> 12460-0701-03 Page 13 / 15 www.<strong>ziehl</strong>.<strong>de</strong>


Measuring inputs<br />

f-in -> Or<strong>de</strong>r-number U226134 + U226135 Frequency 10,00 ... 500,00 Hz<br />

� admissible voltage AC 20...200 V<br />

� admissible voltage AC 80...440 V<br />

f-in -> Or<strong>de</strong>r-number U226138 Frequency 10,00 ... 500,00 Hz<br />

� admissible voltage AC 110...300 V<br />

� admissible voltage AC 210...830 V<br />

Three wire - PNP UMax 28 V; switching threshold approx. 10 V<br />

Three wire - NPN 18 V / 3,5 mA; switching threshold approx. 9 V<br />

Two wire- proximity switch 18 V / 3,5 mA ( 24 V DC )<br />

Switching threshold approx. 1,5 mA<br />

Switching frequency max. 1,6 kHz; 99999 1/min<br />

Cable length for proximity switch PNP, NPN, 2-wire<br />

Resistance of line ≤ 10 Ω / line<br />

Capacity of line ≤ 22 nF 0…800Hz; ≤ 10 nF 800...1600 Hz<br />

e.g. max. length of cable < 150 m with cable LIFYY11Y 3*0,34 mm<br />

at 0…800Hz<br />

Measuring error ± 0,05 % of measured value ± 1 Digit<br />

Temperature factor < 0,002 %/K<br />

Measuring time 1 Period * Svm (number mean values)<br />

>= 3 Periods; after placing the measuring signal<br />

Auxiliary supply +18 V 20 mA 16 ... 21 V max. 20 mA<br />

Enable E1-E2 18 V / 3 mA Switching threshold approx. 9 V<br />

Analogue output: (<strong>FR</strong><strong>MU</strong> only) electrically insulated to input f - in (U1-U2)<br />

Voltage output 0...10 V max. 10 mA error


61,8<br />

13 Type V4<br />

Dimensions in mm<br />

45<br />

58<br />

48<br />

16,5<br />

1 2 3<br />

1 Cover<br />

2 Base<br />

3 Bar for snap mounting<br />

4 Latch for sealing<br />

5 Front panel<br />

6 Position downward<br />

7 For fixing to wall with screws, Ø 4,2 mm.<br />

3<br />

(90)<br />

4<br />

Sie fin<strong>de</strong>n diese und weitere Betriebsanleitungen, soweit verfügbar auch in englisch, auf unserer Homepage<br />

www.<strong>ziehl</strong>.<strong>de</strong>.<br />

You find this and other operating-manuals on our homepage www.<strong>ziehl</strong>.<strong>de</strong>, as far as available also in<br />