General wiring diagram<br />

WARNING<br />

RISK OF DRIVE DESTRUCTION<br />

• The drive will be damaged if input line voltage is applied to the output terminals (U/T1,V/T2,<br />

W/T3).<br />

• Check the power connections before energizing the drive.<br />

• If replacing another drive, verify that all wiring connections to the <strong>ER23K</strong> drive comply with wiring<br />

instructions in this <strong>manual</strong>.<br />

Failure to follow these instructions can result in death, serious injury, or equipment damage.<br />

WARNING<br />

INADEQUATE OVERCURRENT PROTECTION<br />

• Overcurrent protective devices must be properly coordinated.<br />

• The Canadian Electrical Code and the National Electrical Code require branch circuit protection. Use<br />

the fuses recommended in the installation <strong>manual</strong>.<br />

• Do not connect the drive to a power feeder whose short-circuit capacity exceeds the drive short-circuit<br />

current rating listed in the installation <strong>manual</strong>.<br />

Failure to follow these instructions can result in death, serious injury, or equipment damage.<br />

U1<br />

R / L1<br />

R / L1<br />

U / T1<br />

(1)<br />

V1<br />

S / L2<br />

S / L2<br />

V / T2<br />

W1<br />

M<br />

3 a<br />

T / L3<br />

R1A<br />

W / T3<br />

(1)<br />

ER23-...K<br />

Single phase supply<br />

ER23-.../3K/4K/6K<br />

3-phase supply<br />

R1C<br />

(2)<br />

P0<br />

R1B<br />

(3)<br />

PA / +<br />

R2A<br />

PB<br />

Braking<br />

resistor<br />

(if used)<br />

R2C<br />

PC / -<br />

CLI<br />

LI1<br />

+10<br />

LI2<br />

AI1<br />

LI3<br />

COM<br />

Reference<br />

potentiometer<br />

LI4<br />

LI5<br />

AI3<br />

X - Y mA<br />

0 + 10 V<br />

LI6<br />

AI2<br />

24V<br />

AOV<br />

AOC<br />

Use of the<br />

analog output<br />

as a logic output<br />

(1) Line choke, if used (single phase or 3-phase)<br />

(2) Relay contacts for remote signalling of drive status<br />

(3) If a braking resistor is connected, set [Dec ramp adapt.] (brA) parameter to yes (refer to the progamming<br />

<strong>manual</strong>).<br />

Note: Use interference suppressors on all inductive circuits near the drive or coupled to the same circuit<br />

(relays, contactors, solenoid valves, etc).<br />

02/2010 11<br />

COM<br />

A0C<br />

24 V relay<br />

or<br />

24V PLC input<br />

or<br />

LED