Code Name/Description Factory<br />
settings<br />
tCC<br />
3C<br />
LOC<br />
[2/3 wire control] [2 wire] (2C)<br />
This parameter is only visible the first time the drive is switched on.<br />
It can be modified subsequently in the [INPUTS / OUTPUTS CFG] (I-O-) menu if required.<br />
2C • [2 wire] (2C) 2-wire control: The open or closed state of the input controls running or<br />
stopping.<br />
Wiring example:<br />
2 s LI1: forward<br />
LIx: reverse<br />
24 V LI1 LIx<br />
2 s<br />
• [3 wire] (3C) 3-wire control (pulse control): A "forward" or "reverse" pulse is sufficient to<br />
control starting, a "stop" pulse is sufficient to control stopping. Refer to the programming<br />
<strong>manual</strong>.<br />
Wiring example:<br />
LI1: stop<br />
LI2: forward<br />
LIx: reverse<br />
24 V LI1 LI2 LIx<br />
• [Local] (LOC) Local control (drive or remote keypad RUN/STOP/RESET).<br />
DANGER<br />
UNINTENDED EQUIPMENT OPERATION<br />
When [2/3 wire control] (tCC) assignment is modified, the following parameters [Reverse<br />
assign.] (rrS), [2 wire type] (tCt) and all functions affecting logic inputs will return to their<br />
factory setting value.<br />
Check that this change is compatible with the wiring diagram used.<br />
Failure to follow these instructions will result in death or serious injury.<br />
To change the assignment of this parameter press the “ENT” key for 2 s.<br />