Index Page General 2 Approvals 3 Technical Information 5 Mounting ...
Index Page General 2 Approvals 3 Technical Information 5 Mounting ...
Index Page General 2 Approvals 3 Technical Information 5 Mounting ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Contactors<br />
Utilization Categories<br />
For easier choice of devices and in order to make the comparison<br />
of different products simplier are utilization categories for contactors<br />
and motor-starters according to IEC 947-4-1 and VDE 0660 Part 102, for<br />
Type of Cate- Typical applications Rated Test conditions for the number of Test conditions for<br />
current gory operational on-load operating cycles making and breaking capacities<br />
current Make Break Make Break<br />
I/I e U/U e cosϕ I c /I e U r /U e cosϕ I/I e U/U e cosϕ I c /I e U r /U e cosϕ<br />
Alter- Non-inductive or<br />
nating AC1 slightly inductive loads all values 1 1 0,95 1 1 0,95 1,5 1,05 0,8 1,5 1,05 0,8<br />
Current resistance furnaces<br />
Slip-ring motors:<br />
AC2 starting, switching off all values 2,5 1 0,65 2,5 1 0,65 4 1,05 0,65 4 1,05 0,65<br />
Squirrel-cage motors: I e ≤ 17A 6 1 0,65 1 0,17 0,65 10 1,05 0,45 8 1,05 0,45<br />
AC3 starting, switching off 17A< I e ≤ 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,45 8 1,05 0,45<br />
motors during running I e > 100A 6 1 0,35 1 0,17 0,35 10 1,05 0,35 8 1,05 0,35<br />
Squirrel-cage motors: I e ≤ 17A 6 1 0,65 6 1 0,65 12 1,05 0,45 10 1,05 0,45<br />
AC4 starting, plugging, 17A< I e ≤ 100A 6 1 0,35 6 1 0,35 12 1,05 0,45 10 1,05 0,45<br />
inching I e > 100A 6 1 0,35 6 1 0,35 12 1,05 0,35 10 1,05 0,35<br />
Switching of electric<br />
AC5a discharge lamp controls all values - - - - - - 3 1,05 0,45 3 1,05 0,45<br />
Switching of<br />
AC5b incandescent lamps all values - - - - - - 1,5 1,05 1) 4 1,05 1)<br />
Switching of<br />
AC6a transformers I e ≤ 100A - - - - - - 4,5 1,05 0,45 3,6 1,05 0,45<br />
I e > 100A - - - - - - 4,5 1,05 0,35 3,6 1,05 0,35<br />
Switching of<br />
AC6b capacitors - - - - - - - 2) 2)<br />
Slightly inductive loads<br />
AC7a in household appliances all values - - - - - - 1,5 1,05 0,8 1,5 1,05 0,8<br />
and similar applications<br />
AC7b<br />
Motor loads<br />
for household applications I ≤ e<br />
I > e<br />
100A<br />
100A<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
8<br />
8<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
6<br />
6<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
Hermetic refrigerant compressor<br />
AC8a motor control with manual<br />
resetting of overload releases<br />
Hermetic refrigerant compressor<br />
I ≤ e<br />
I > e<br />
100A<br />
100A<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
6<br />
6<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
6<br />
6<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
AC8b motor control with automatic<br />
resetting of overload releases<br />
I ≤ e<br />
I > e<br />
100A<br />
100A<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
-<br />
6<br />
6<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
6<br />
6<br />
1,05<br />
1,05<br />
0,45<br />
0,35<br />
Control of resistive loads and<br />
AC12 solid state loads with all values - - - - - - 1 1 0,9 1 1 0.9<br />
isolation by opto couplers<br />
Control of<br />
AC13 solid state loads with all values - - - - - - 10 1,1 0,65 1,1 1,1 0,65<br />
transformer isolation<br />
Control of<br />
AC14 small electromagnetic loads - - - - - - - 6 1,1 0,7 6 1,1 0,7<br />
(≤72VA)<br />
Control of<br />
AC15 electromagnetic load - 10 1 0,7 1 1 0,4 10 1,1 0,3 10 1,1 0,3<br />
(>72VA)<br />
Make L/R Break L/R Make L/R Break L/R<br />
I/I e U/U e [ms] I c /I e U r /U e [ms] I/I e U/U e [ms] I c /I e U r /U e [ms]<br />
Direct Non-inductive or<br />
Current DC1 slightly inductive loads all values 1 1 1 1 1 1 1,5 1,05 1 1,5 1,05 1<br />
resistance furnaces<br />
Shunt-motors:<br />
DC3 starting, plugging, inching all values 2,5 1 2 2,5 1 2 4 1,05 2,5 4 1,05 2,5<br />
dynamic braking of d.c. motors<br />
Series-motors:<br />
DC5 starting, plugging, inching all values 2,5 1 7,5 2,5 1 7,5 4 1,05 15 4 1,05 15<br />
dynamic braking of d.c. motors<br />
Switching of<br />
DC6 incandescent lamps all values - - - - - - 1,5 1,05 1) 4 1,05 1)<br />
Control of resistive loads and<br />
DC12 solid state loads with all values - - - - - - 1 1 1 1 1 1<br />
isolation by opto couplers<br />
Control of<br />
DC13 electromagnets all values 1 1 ≤300 1 1 ≤300 1,1 1,1 ≤300 1,1 1,1 ≤300<br />
Control of<br />
DC14 electromagnetic loads having all values - - - - - - 10 1,1 15 10 1,1 15<br />
economy resistors in circuit<br />
U e Rated operational voltage, U Voltage before make, U r Recovery voltage, I e Rated operational current, I Current make, I c Current broken<br />
1) Test with incandescent lamps<br />
2) Test conditions according to standard<br />
control circuit devices and switching elements according to<br />
IEC 947-5-1 and VDE 0660 Part 200 determind. The table offers different<br />
utilization categories, typical applications and assorted test conditions.<br />
D677E 61