safety <strong>Manual</strong> <strong>9116</strong> UNiVeRsal coNVeRteR<br />

For RtD and linear resistance input sensors, cable resistances of up to 50 W per wire can be<br />

compensated if 3- or 4-wire connection is configured.<br />

For thermocouple sensors, cold junction temperature errors can be compensated, either by an<br />

internally mounted temperature sensor, or by an accessory connector with a built-in temperature<br />

sensor. the selection of cJc measurement must be done and verified by the end user.<br />

6 functional specification of the non-safety functions<br />

the status relay (terminal 33 and 34), error signal on power rail (terminal 91) and leD outputs<br />

are not suitable for use in any safety instrumented Function.<br />

7 Safety parameters<br />

RtD, tc, linR and Potentiometer input, current output<br />

Probability of dangerous Failure per Hour (PFH) 4.30e-08<br />

Note 1<br />

Probability of failure on demand (PFD) -<br />

1 year proof test interval<br />

6 Version No. V1R0<br />

2.82e-04<br />

Proof test interval (10% of loop PFD) 4 years<br />

safe Failure Fraction 93%<br />

RtD, tc, linR and Potentiometer input, Relay output<br />

Probability of dangerous Failure per Hour (PFH) 6.20e-08<br />

Note 1<br />

Probability of failure on demand (PFD) -<br />

1 year proof test interval<br />

4.03e-04<br />

Proof test interval (10% of loop PFD) 3 years<br />

safe Failure Fraction 90%<br />

Voltage input, current output<br />

Probability of dangerous Failure per Hour (PFH) 5.60e-08<br />

Note 1<br />

Probability of failure on demand (PFD) -<br />

1 year proof test interval<br />

3.66e-04<br />

Proof test interval (10% of loop PFD) 3 years<br />

safe Failure Fraction 93%<br />

Voltage input, Relay output<br />

Probability of dangerous Failure per Hour (PFH) 7.60e-08<br />

Note 1<br />

Probability of failure on demand (PFD) -<br />

1 year proof test interval<br />

4.89e-04<br />

Proof test interval (10% of loop PFD) 2 years<br />

safe Failure Fraction 91%