Power supply<br />

CHAPTER 1: BEFORE YOU START<br />

Figure 4: D20 VME chassis - VME bus backplane and D20M+ termination panel<br />

WESTERM D20VME -<br />

VME Bus Backplane<br />

D20 VME Chassis<br />

The chassis-mounted power supply modules are switch-mode converters that provide<br />

output power for the <strong>D20MX</strong> processor board, VME cards, modems and D20 Peripheral I/O<br />

modules, as required. A redundant power supply can be installed to provide fail-over<br />

protection to ensure continuous power to the D20.<br />

If you have an extended system with more than five peripherals, the chassis-mounted D20<br />

power supply is not adequate. In this case, you need to install an external power supply.<br />

Table 5 lists the standard power supplies that are available. Other power supplies are<br />

available for specific requirements. Contact <strong>GE</strong> <strong>Digital</strong> <strong>Energy</strong> for details.<br />

Table 5: Available power supplies<br />

WESTERM D20M+<br />

Termination Panel<br />

<strong>GE</strong> part number Input Output<br />

580-2004 20 to 60 V DC +5 V, 7 A; +12 V, 2 A; -12 V, 1 A; 24 V DC, 3 A<br />

580-2005 20 to 60 V DC +5 V, 7 A; +12 V, 2 A; -12 V, 1 A; 48 V DC, 1.5 A<br />

580-2006 100 to 300 V DC or 85 to 264 V AC +5 V, 7 A; +12 V, 2 A; -12 V, 1 A; 24 V DC, 3 A<br />

580-2007 100 to 300 V DC or 85 to 264 V AC +5 V, 7 A; +12 V, 2 A; -12 V, 1 A; 48 V DC, 1.5 A<br />

Ensure your D20 power input is externally protected for over-current; otherwise damage to<br />

the <strong>D20MX</strong> may occur. The required fuse rating depends on the power consumption of<br />

your system.<br />

The D20 available power supplies, listed in Table 5 are equipped with two field replaceable<br />

fuses.; see Figure 5.<br />

20 <strong>GE</strong>NERAL <strong>D20MX</strong> HARDWARE USER’S MANUAL