TECHNICAL DATA<br />

GB<br />

MODEL GAS 3/2 GAS 4/2 GAS 5/2 GAS 6/2 GAS 7/2<br />

TYPE 521 T1 522 T1 523 T1 524 T1 525 T1<br />

OUTPUT (1) 2nd stage kW 130 - 350 180 - 470 320 - 660 520 - 1050 800 - 1760<br />

Mcal/h<br />

112 - 301 155 - 404 275 - 568 447 - 903 688 - 1514<br />

1st stage kW<br />

Mcal/h<br />

80 - 175<br />

69 - 150<br />

120 - 235<br />

104 - 202<br />

155 - 330<br />

133 - 284<br />

300 - 520<br />

258 - 447<br />

400 - 880<br />

344 - 757<br />

FUEL<br />

NATURAL GAS: G20 - G21 - G22 - G23 - G25<br />

G20 G25 G20 G25 G20 G25 G20 G25 G20 G25<br />

- Net calorific value kWh/Nm 3<br />

Mcal/Nm 3 10<br />

8,6<br />

8,6<br />

7,4<br />

- Absolute density kg/Nm 3 0,71 0,78 0,71 0,78 0,71 0,78 0,71 0,78 0,71 0,78<br />

- Max delivery Nm 3 /h 35 41 47 54 66 77 105 122 176 205<br />

- Pressure at maximum delivery (2) mbar 11,1 16,4 9,8 14,5 9,8 14,5 12,3 18,2 14,5 21,4<br />

OPERATION<br />

• Intermittent (min. 1 stop in 24 hours)<br />

• Two-stage (high and low flame) and single-stage (all - nothing)<br />

STANDARD APPLICATIONS<br />

Boilers: water, steam, diathermic oil<br />

AMBIENT TEMPERATURE °C 0 - 40<br />

COMBUSTION AIR TEMPERATURE °C max 60<br />

ELECTRICAL SUPPLY<br />

ELECTRIC MOTOR<br />

V<br />

Hz<br />

rpm<br />

W<br />

V<br />

A<br />

MOTOR CAPACITOR µF<br />

V<br />

IGNITION TRANSFORMER<br />

V1 - V2<br />

I1 - I2<br />

230 ~ +/-10%<br />

50 - single-phase<br />

2750<br />

250<br />

220 - 240<br />

1,8<br />

8<br />

450/500<br />

(1) Reference conditions: Ambient temperature 20 ÈC - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.<br />

(2) Pressure at test point 12)(A)p.8, with zero pressure in the combustion chamber, with open <strong>gas</strong> ring 2)(B)p.16 and maximum burner output.<br />

10<br />

8,6<br />

8,6<br />

7,4<br />

2810<br />

370<br />

220 - 240<br />

2,9<br />

12,5<br />

400/450<br />

10<br />

8,6<br />

8,6<br />

7,4<br />

10<br />

8,6<br />

8,6<br />

7,4<br />

230 - 400 with neutral ~ +/-10%<br />

50 - three-phase<br />

2870<br />

750<br />

220/240-380/415<br />

2,85 - 1,65<br />

230 V - 1 x 8 kV<br />

1,8 A - 30 mA<br />

2840<br />

1500<br />

220/240-380/415<br />

5,9 - 3,4<br />

10<br />

8,6<br />

8,6<br />

7,4<br />

2840<br />

3000<br />

220/240-380/415<br />

10,9 - 6,3<br />

ELECTRICAL POWER CONSUMPTION W max 400 540 850 1700 3400<br />

ELECTRICAL PROTECTION IP 40<br />

IN CONFORMITY WITH EEC DIRECTIVES 90/396 - 89/336 - 73/23 - 92/42<br />

APPROVAL CE 0085AQ0707<br />

COUNTRY<br />

IT - AT - GR - DK - FI - SE<br />

ES - GB - IE - PT<br />

NL<br />

FR<br />

CATEGORY<br />

II 2H3B / P<br />

II 2H3P<br />

II 2L3B / P<br />

II 2Er3P<br />

DE II 2ELL3B /P<br />

BE<br />

I 2E(R)B, I 3P<br />

LU II 2E3B /P<br />

Important:<br />

The installer is responsible for the addition of any safety device not forseen in the present manual.<br />