2.2 Air-termination rod<br />
The air-termination rod with a diameter of 16/10 mm is screwed into the top of the lower part<br />
of the air-termination rod (Æ 22 x 4 mm) and the M 16 hexagon nut is tightened (see Fig. 2.2,<br />
page 6).<br />
The assembled air-termination rod is vertically inserted into the adapter of the brace frame and<br />
the four M10 locking bolts are tightened (tightening torque of 25 Nm).<br />
The four M10 hexagon nuts have to be tightened against the adapter (see Fig. 2.2, page 6).<br />
2.2.1 Down conductor<br />
The down conductor (round wire 8-10 mm) is connected via a rod clamp (positioned for<br />
transport) on the lower part of the air-termination rod and has to be connected to the next airtermination<br />
system or earth-termination system while maintaining the required separation<br />
distance.<br />
A tightening torque of 25 Nm has to be applied when connecting the down conductor via the<br />
rod clamp.<br />
Page 5<br />