Montageanleitung Fangstange - Dehn + Söhne Blitzschutzsysteme
Montageanleitung Fangstange - Dehn + Söhne Blitzschutzsysteme
Montageanleitung Fangstange - Dehn + Söhne Blitzschutzsysteme
Sie wollen auch ein ePaper? Erhöhen Sie die Reichweite Ihrer Titel.
YUMPU macht aus Druck-PDFs automatisch weboptimierte ePaper, die Google liebt.
3.3 Adjustment of the air-termination rod in case of roof inclinations up to an inclination angle<br />
of 10°<br />
3.3.1 Adjustment of the adapter<br />
The adapter attached to the brace frame allows the installation of self-supporting air-termination<br />
rods with a diameter of 22 mm. This adapter compensates air-termination rods in case of roof<br />
inclinations or slopes up to an inclination angle of 10° (see Fig. 3.3).<br />
Depending on the inclination angle, the air-termination rod ( 22 mm; aluminium tube) is<br />
inserted into the adapter and the four M8 locking bolts are tightened.<br />
Moreover, the four hexagon nuts have to tightened against the adapter. The specified tightening<br />
torques have to be observed (see Fig. 3.2, page 11 and Fig. 3.3, page 12.<br />
M8 hexagon nut<br />
15 Nm<br />
max. 10°<br />
Fig. 3.3 Adjustment of the air-termination rod<br />
Page 12<br />
lower part of the<br />
air-termination rod<br />
22 x 4 mm; aluminium tube<br />
tightening torque for the<br />
M8 locking bolt<br />
M 8; 15 Nm<br />
MO_1712_DE_GB_1209_057867