2. DESIGN CALCULATIONS (Subroutine DESIGN)<br />

Overv iew<br />

The design subroutine (DESIGN) ensures that all the various quantities needed<br />

for the system simulation are given values. These values are either<br />

(1) specified by the user,<br />

(2) defaults built into the program, or<br />

(3) calculated for peak cooling and heating conditions that were<br />

determined in the LOADS program.<br />

This subroutine also ensures consistency among the multiple values of related<br />

data. The hourly simulation requires:<br />

(1) a value for the air flow rate (for air systems) for each conditioned<br />

zone,<br />

(2) a heating and cooling capacity for each system, unit, or coil,<br />

(3) the electrical consumption of fans and direct expansion<br />

condenser-compressor arrangements,<br />

(4) minimum and maximum air flow rates for variable-air volume flow<br />

equipment,<br />

(5) outside ventilation air flow rates, and<br />

(6) other controller set point or operational information.<br />

Because the built-in calculations of this subroutine may not always do things<br />

as the user wishes, it is sometimes necessary for critical keywords to be<br />

specified in such a manner that will result in the desired sizing.<br />

The design calculations are performed for each SYSTEM specified in a PLANT­<br />

ASSIGNMENT instruction and for each ZONE in one of these SYSTEMs. The results<br />

of the calculations can be found in the SYSTEMS verification report, SV-A.<br />

Calculation Outline<br />

A. Correct the zone peak heating and cooling loads if the user has specified<br />

SIZING-OPTION = ADJUST-LOADS in the ZONE instruction.<br />

For each SYSTEM that has a PLANT-ASSIGNMENT instruction:<br />

B. Calculate the supply air and return air fan heat gain and energy consumption<br />

at the design air flow rate.<br />

C. Calculate for each ZONE attached to this SYSTEM<br />

1. the outside ventilation air flow rate,<br />

2. the total zone supply air flow rate,<br />

3. the heating capacity for zone coil systems (zonal systems),<br />

4. the cooling capacity for zone coil systems (zonal systems),<br />

5. the minimum supply air flow rate for non-zonal systems (central<br />

sys tems ), and<br />

6. the sum of the various quantities needed for the central air handler<br />

calculation, if present.<br />