The water flow rate has been set by the chi llers, and the fans must be<br />

opera ti ng at fu 11 speed, if the temperature is fl oati ng above the set poi nt.<br />

The rating factor is, therefore:<br />

AREA<br />

Fr = gpm •<br />

The range has been set by the chillers (heat rejection / lbs water flow) and<br />

the wet-bulb temperature is known. The approach can be found from the<br />

performance charts, or by an equation fitted to the charts:<br />

The leaving water temperature is then<br />

TTOWR = TWb + Ap.<br />

30<br />

10<br />

9<br />

8<br />

7<br />

6<br />

5<br />

0.2 0.3 0.4<br />

60° Wet Bulb Chart<br />

0.6 0.8 LO 2.0<br />

Rating Factor<br />

3.0 4.0 5.0 6.0 7.08.0 10.0<br />

Fig. V.II. Cooling Tower Performance Chart for TWb = 60"F.<br />

V.53