QH = (FTEMP - MIN-FLUID-T) * FLUID-HEAT-CAP. (IV.446)<br />

Some system-level quantities are saved for reporting. These include the<br />

total system electrical energy consumption,<br />

nzones<br />

= L ZKW nz * MULTIPLIER nz '<br />

nz=l<br />

total electrical input for cooling,<br />

nzones<br />

SKWQC = L EIRnz * QCT nz * MULTIPLIER nz * 0.000293<br />

nz=l<br />

(where 0.000293, or 1/3413, converts Btu/hr to kilowatt-hr),<br />

total electrical input for heating,<br />

nzones<br />

SKWQH = - L EIRnz * QHT nz * MULTIPLIER nz * 0.000293,<br />

nz=l<br />

total fan electrical energy consumption,<br />

nzones<br />

FANKW = L (FH nz + FC nz ) * MULTIPLIER nz * ' and<br />

nz=l<br />

total space latent heat gain from people and equipment,<br />

nzones<br />

QCLAT = L QCLATZ nz * MULTIPLIER nz '<br />

nz=l<br />

IV.153<br />

(IV.447)<br />

(IV.448)<br />

(IV.449)<br />

(IV.450)<br />

(IV .451)