Speed 3000 rev/min<br />
Turbine gross effective power 1035 MW<br />
Length of turbine-generator system 55 m<br />
Generator<br />
Apparent power 1190 MVA<br />
Power factor (cos �) 0.9<br />
Terminal voltage 27 kV<br />
Frequency 50 Hz<br />
Cooling rotor winding hydrogen (6 bar), 7 bar abs.<br />
Cooling stator winding water (27 kg/s)<br />
Key technical data<br />
Generator transformer<br />
Number/type 3 single-phase units <strong>and</strong> 1 st<strong>and</strong>-by unit<br />
High voltage side 409 kV<br />
Low voltage side 27 kV<br />
Power capacity 1200 MVA<br />
Main feedwater pumps<br />
Number/type 3 double-flow double-stage<br />
radial centrifugal pumps<br />
Discharge head (backing <strong>and</strong> main pump) 812 m<br />
Design flow rate per pump 844 kg/s<br />
Motor power 8600 kW<br />
Cooling tower<br />
Number/type natural circulation wet-type<br />
Height 150 m<br />
Diameter at base 117 m<br />
Diameter at top opening 74 m<br />
Throat diameter 70 m<br />
Bottom shell thickness 750 mm<br />
Minimum shell thickness 160 mm<br />
Water flow rate 33.8 m 3 /s<br />
Warm water temperature 36°C<br />
Cold water temperature 22°C<br />
Dry bulb temperature 7.8°C<br />
Wet bulb temperature 6.2°C<br />
Air-flow rate 25,400 m 3 /s<br />
Water evaporation rate 0.4–0.7 m 3 /s<br />
Circulating water pumps<br />
Number/type 2 single-stage, mixed flow<br />
centrifugal pumps<br />
Discharge head 20.5 m<br />
Nominal flow rate per pump 16.9 m 3 /s<br />
Speed 248 rev/min<br />
Motor power 4100 kW<br />
� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �