<strong>Appliance</strong>s may be connected to the fuel gas piping by means<br />

of an approved listed quick-disconnect device with an approved<br />

shut-off valve connected to the rigid gas piping.<br />

16. REQUIRED GAS SUPPLY: <strong>Gas</strong> piping shall be sized by CFH.<br />

To obtain the cubic-feet-per-hour of gas required, divide the<br />

input of appliances by the average Btu heating value per cubic<br />

foot of the gas. See Table X, Pages 87-90 or consult <strong>Questar</strong><br />

<strong>Gas</strong> Company <strong>for</strong> the average Btu per cubic foot if it is not<br />

known.<br />

Example: 100,000 Btu/h rated furnace installed in an area with<br />

890 Btu per cubic foot.<br />

100,000 = 112 CFH<br />

890<br />

FIGURE 3<br />

CSST BONDING<br />

37