just selected, determine the gas dem<strong>and</strong> <strong>for</strong> the outlet. If<br />

the exact figure of dem<strong>and</strong> is not shown, choose the next<br />

larger figure in the horizontal line.<br />

(f) Above the dem<strong>and</strong> figure will be the correct size of gas<br />

piping.<br />

(g) Proceed in a similar manner <strong>for</strong> each outlet <strong>and</strong> each section<br />

of gas piping. For each section of piping, determine the<br />

total gas dem<strong>and</strong> by that section as follows (using an<br />

assumed gas content of 890 Btu/Cu. Ft.).<br />

EXAMPLE OF SIZING A HOUSE PIPING SYSTEM<br />

FIGURE 4<br />

SOLUTION AND EXAMPLE: (Rated Input/890 Btu/Cfh)<br />

(1) Maximum dem<strong>and</strong> <strong>for</strong> outlet “A” 34 CFH<br />

Maximum dem<strong>and</strong> <strong>for</strong> outlet “B” 28 CFH<br />

Maximum dem<strong>and</strong> <strong>for</strong> outlet “C” 84 CFH<br />

Maximum dem<strong>and</strong> <strong>for</strong> outlet “D” 153 CFH<br />

Total Dem<strong>and</strong> 299 CFH<br />

39