CORREGATED STAINLESS STEEL<br />

TUBING (CSST)<br />

Regulator Pipe Size Capacity Leak Limiter<br />

**Maxitrol 325-3LX 3/8” & ½” 250 CFH 12A09<br />

**Maxitrol 325-5ALX ½” 425 CFH 12A39<br />

**Maxitrol 325-5ALX ¾” & 1” 550 CFH 12A39<br />

**Maxitrol 325-7L 1 ¼” & 1 ½” 1,000 CFH Vent<br />

**300 O.A.R.A. ½” 250 CFH “O” 3-18<br />

**600 O.A.R.A. ¾” 550 CFH “O” 6-38<br />

“FAGAS F-BH 2 ½” 250 CFH #F<br />

*Z21.80 only **Z21.18 & Z21.80<br />

TABLE VI (continued)<br />

Z21.18 the ANSI st<strong>and</strong>ard <strong>for</strong> appliance regulators, intended <strong>for</strong> application in natural gas systems.<br />

Z21.80 the ANSI st<strong>and</strong>ard <strong>for</strong> line pressure regulators, intended <strong>for</strong> application in natural gas systems.<br />

To con<strong>for</strong>m to the ANSI Z21-80 st<strong>and</strong>ard <strong>for</strong> line pressure regulators, installations exceeding 2 psi (up to <strong>and</strong><br />

including 5 psi) require a tested <strong>and</strong> approved over-protection device (OPD) <strong>for</strong> use with the regulator. The OPD<br />

will limit the downstream pressure to 2-psi maximum in the event of line regulator failure.<br />

OPD47 – Maxitrol 325-3LX reg. (3/8” &1/2”)<br />

OPD48 – Maxitrol 325-3LX reg. (1/2”)<br />

OPD48 – Maxitrol 325-5ALX reg. (1/2” &3/4”)<br />

OPD600 – Maxitrol 325-5ALX reg. (3/4” & 1”)<br />

OPD210 – Maxitrol 325-7L reg. (1 ¼” & 1 ½”)<br />

45