Product manual 2009English - Wöhner
Product manual 2009English - Wöhner
Product manual 2009English - Wöhner
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
new page<br />
QUADRON®CrossLinkSwitch<br />
Bus-mounting switch disconnector<br />
Panel-mounting and busbar-mounting<br />
DIN VDE 0660 part 107 / EN 60947-3 / IEC 60947-3<br />
3-pole switching, double-breaking main contacts<br />
Safe, operator-independent switching, lockable with 3 padlocks in OFF position<br />
Shock protection complies with DIN EN 50274<br />
Degree of protection IP30 (front side), degree of protection near terminal depends on installation<br />
Recommended mounting position: handle at top<br />
Busbar-mounting version:<br />
Mounting on a 60mm system (size 00)<br />
Screwless busbar contacting<br />
Gentle snapping onto busbar systems<br />
Panel-mounting version:<br />
– size 00: to be screwed on to mounting plate<br />
Terminal space for box terminal:<br />
– size 00: Cu 1.5–70/95mm 2 f; Cu 1.5–70mm 2 sol(r), s(r), f + AE<br />
Terminal space (W x H) 13 x 13mm<br />
2 x 10mm 2 , 2 x 16mm 2 f + AE, both conductors are identical, aligned side by side,<br />
Square crimping<br />
fl. Cu 9–13mm wide<br />
Size 200<br />
Type of current AC (50–60Hz)<br />
Max. rated operating voltage (Ue) 690V AC<br />
Rated insulation voltage (Ui) 800V<br />
Rated surge withstand capacity (Uimp) 6kV<br />
Max. rated operating current (Ie)* 200A<br />
Conditional rated short-circuit current 50kA<br />
with series fuses gG<br />
* During continuous operation of several devices side-by-side, the rated load factor specified according to<br />
VDE 0660 part 500 / EN 60 439 -1, table 1, must be observed.<br />
size 00; 125A – 690V<br />
Pilot switch for lid position indication<br />
1 (changeover) switch can be used<br />
Rated operating voltage (rated operating current)<br />
250V AC (5A), 30V DC (4A)<br />
8<br />
27