25.04.2013 Views

HVAC SYSTEMS - HFT Stuttgart

HVAC SYSTEMS - HFT Stuttgart

HVAC SYSTEMS - HFT Stuttgart

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Page - 3 -<br />

CHAPTER 01<br />

fans and pumps, but they do not give any hint for the dimensioning of the solar<br />

collectors or any indication of the solar thermal contribution to total energy<br />

requirements. This annual system performance depends on the details of the<br />

collector, storage and absorption chiller dimensions and efficiencies for the<br />

varying control strategies and building load conditions. An analysis of the<br />

primary energy savings for a given configuration with renewable energy heat<br />

input requires a complete model of the cooling system coupled to the building<br />

load with a time resolution of at least one hour. Very few results of complete<br />

system simulations have been published. In the IEA task 25 several design<br />

methods have been evaluated and a simplified design tool is currently under<br />

development in IEA task 38. In the simplest approach a building load model<br />

provides hourly values of cooling loads and the solar fraction is calculated from<br />

the hourly produced collector energy at the given irradiance conditions. Excess<br />

energy from the collector can be stored in available buffer volumes without<br />

however considering specific temperature levels. Different building types were<br />

compared for a range of climatic conditions in Europe with cooling energy<br />

demands between 10 and 100 kWh per square meter conditioned space and<br />

annum. Collector surfaces between 0.2 - 0.3 m 2 per square meter of<br />

conditioned building space combined with 1 - 2 kWh of storage capacity gave<br />

solar fractions above 70% (Henning, 2004). System simulations for an 11 kW<br />

absorption chiller using the dynamic simulation tool TRNSYS gave an optimum<br />

collector surface of only 15 m 2 for a building with 196 m 2 gross floor area and<br />

90 kWh per m 2 annual cooling load, i.e. less than 0.1 m 2 per square meter of<br />

building surface. A storage volume of 0.6 m³ was found to be optimum (40 litre<br />

per m² collector), which at 20K useful temperature level only corresponds to 14<br />

kWh total or 0.07 kWh per square meter of building gross floor area (Florides, et<br />

al., 2002). Another system simulation study (Atmaca, et al., 2003) considered a<br />

constant cooling load of 10.5 kW and a collector field of 50 m². 75 liters of<br />

storage volume per square meter of collector surface were found to be<br />

optimum. Larger storage volumes were detrimental to performance. The main<br />

limitation of these models is that the storage models are very simple and only<br />

balance energy flows, but do not consider stratification of temperatures. This

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!