19.06.2013 Views

Start-Up, Operation, and Maintenance Instructions - Carrier

Start-Up, Operation, and Maintenance Instructions - Carrier

Start-Up, Operation, and Maintenance Instructions - Carrier

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4. <strong>Start</strong> the pumpout compressor (control switch at ON<br />

position).<br />

5. Operate pumpout compressor until suction gage reads<br />

highest sustained vacuum (about 28 in. Hg VAC or 1<br />

psia [6.9 kPa]).<br />

6. Close valve 8.<br />

7. Stop compressor (control switch at OFF position).<br />

REMOVE AIR AFTER OPENING CHILLER TO ATMO-<br />

SPHERE (Refrigerant Charge in Storage Tank) — Perform<br />

the following procedure. See Fig. 4 for valve numbers.<br />

1. Place the control switch in the OFF position.<br />

2. Close valves 2, 4, 5, 9, 10, 11 <strong>and</strong> 13.<br />

3. Open valves 1, 3, 6, 7, 8, <strong>and</strong> 12.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O C O C C O O O C C C O C<br />

4. <strong>Start</strong> pumpout compressor by putting control switch in<br />

the ON position.<br />

5. Operate pumpout compressor until suction gage reads<br />

highest sustained vacuum (about 28 in. hg or 1 psia<br />

[6.9 kPa]).<br />

6. Close valve 8.<br />

7. Stop compressor by placing the control switch in the OFF<br />

position.<br />

TRANSFER REFRIGERANT CHARGE (From Storage<br />

Tank to Machine) — Perform the following procedure. See<br />

Fig. 4 for valve numbers.<br />

1. Place control switch in OFF position.<br />

2. Operate cooler water pump <strong>and</strong> ensure that there is water<br />

flow through the cooler.<br />

3. Close valves 2, 4, 5, 6, 7, 8, 9, 10, <strong>and</strong> 11.<br />

4. Open valves 1, 3, 12, <strong>and</strong> 13.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O C O C C C C C C C C O O<br />

CAUTION<br />

Follow steps 5 <strong>and</strong> 6 carefully to prevent damage from a<br />

freeze-up.<br />

5. Slowly open valve 5 <strong>and</strong> allow refrigerant vapor into the<br />

chiller until chiller pressure increases to 35 psig (141 kPa)<br />

for R-134a. Feed refrigerant slowly to avoid freeze-up.<br />

6. Close valve 5.<br />

7. <strong>Start</strong> the pumpout compressor (control switch in the<br />

AUTO position).<br />

8. When the cooler pressure is lower than storage tank pressure,<br />

open valve 11 <strong>and</strong> refrigerant will flow from the<br />

storage tank to the machine.<br />

9. Shut valve 11 when refrigerant level reaches the charge<br />

level mark on the cooler sight glass.<br />

10. Turn off the pumpout compressor (control switch in the<br />

OFF position).<br />

11. Close valves 3, 4, <strong>and</strong> 12.<br />

TRANSFER REFRIGERANT CHARGE (From Machine<br />

to Storage Tank Located Below Machine) — Perform the<br />

following procedure. See Fig. 4 for valve numbers.<br />

1. Vent storage tank to machine by opening valves 1, 2, 4,<br />

<strong>and</strong> 12.<br />

2. Open valves 11 <strong>and</strong> drain liquid from the cooler.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O O C O C C C C C C O O C<br />

12<br />

3. Operate the cooler water pump.<br />

4. Open valves 3, 6, 7, <strong>and</strong> 9.<br />

5. Close valves 2, 4, 5, 10 ,11, <strong>and</strong> 13.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O C O C C O O C O C C O C<br />

6. Run cooling water through the pumpout condenser.<br />

7. Operate the pumpout compressor (control switch in the<br />

ON position).<br />

8. At 25 in. Hg VAC (2.5 psia, 17.21 kPa) in cooler, stop the<br />

pumpout compressor. Close all valves <strong>and</strong> shut off<br />

pumps.<br />

TRANSFER REFRIGERANT CHARGE (From Machine<br />

to Storage Tank Located Above or Level with Machine) —<br />

Perform the following procedure. See Fig. 4 for valve<br />

numbers.<br />

1. Operate the cooler <strong>and</strong> machine condenser water pumps.<br />

2. Open valves 1, 2, 5, 6, 7, <strong>and</strong> 12.<br />

3. Close valves 3, 4, 8, 9, 10 ,11, <strong>and</strong> 13.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O O C C O O O C C C C O C<br />

4. Operate the pumpout compressor (control switch in the<br />

ON position).<br />

5. When the storage tank pressure is less than machine pressure,<br />

open valve 11.<br />

6. After the liquid has been transferred, stop the pumpout<br />

compressor <strong>and</strong> the condenser water pump.<br />

Continue to operate the cooler water pump.<br />

7. Open valves 3, 6, 7 <strong>and</strong> 9.<br />

8. Close valves 2, 4, 5, 10, 11, <strong>and</strong> 13.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition O C O C C O O C O C C O C<br />

9. Run cooling water through the pumpout condenser.<br />

10. Operate the pumpout compressor (control switch in the<br />

ON position).<br />

11. At 25 in. Hg VAC (2.5 psia, 17.21 kPa) in cooler, stop the<br />

pumpout compressor. Close all valves <strong>and</strong> shut off<br />

pumps.<br />

PRESSURIZE MACHINE AND STORAGE TANK (No<br />

Refrigerant in System) — Perform the following procedure.<br />

See Fig. 4 for valve numbers.<br />

1. Open valves 3, 4, 6, 7, 9, 11, <strong>and</strong> 13.<br />

2. Close valves 1, 2, 5, 8, 10 , <strong>and</strong> 12.<br />

Valve 1 2 3 4 5 6 7 8 9 10 11 12 13<br />

Condition C C O O C O O C O C O C O<br />

3. Operate the pumpout compressor (control switch in the<br />

ON position) until desired pressure is reached. Do not exceed<br />

design pressure of vessels.<br />

4. Stop the pumpout compressor (control switch in the OFF<br />

position).<br />

5. Close valve 13.<br />

WARNING<br />

Do not use refrigerant or air for leak testing. Personal<br />

injury could result. Only use nitrogen for leak testing.<br />

DISTILL REFRIGERANT CHARGE — Water, oil, <strong>and</strong> impurities<br />

can be removed from the refrigerant while transferring<br />

the charge from storage tank to machine. Perform the following<br />

procedure. See Fig. 4 for valve numbers.<br />

1. Operate the cooler <strong>and</strong> machine condenser water pumps.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!